Vacuum Drying and Leakage Checking
7. Vacuum Drying and Leakage Checking
7.1 Purpose of vacuum drying
Eliminating moisture in
the
system to prevent the phenomena of ice-blockage and copper oxidation.
Ice-blockage shall cause abnormal operation of system, while copper oxide shall damage compressor.
Eliminating the non-condensable gas (air) in system to prevent the components oxidizing, pressure
fluctuation and bad heat exchange during the operation of system.
7.2 Selection of vacuum pump
The ultimate vacuum degree of vacuum pump shall be -756mmHg or above.
Precision of vacuum pump shall reach 0.02mmHg or above.
7.3 Operation procedure for vacuum drying
Due to different construction environment, two kinds of vacuum drying ways could be chosen, namely
ordinary vacuum drying and special vacuum drying.
7.3.1 Ordinary vacuum drying
1. When conduct
ing
first vacuum drying, connect pressure gauge to the infusing mouth of gas pipe and liquid
pipe, and keep vacuum pump running for 1hour (vacuum degree of vacuum pump shall be reached
-755mmHg).
2 If the vacuum degree of vacuum pump could not reach -755mmHg after 1 hour of drying, it indicates
that there is moisture or leakage in pipeline system and need to go on with drying for half an hour.
3 If the vacuum degree of vacuum pump still could not reach -755mmHg after 1.5 hours of drying, check
whether there is leakage source.
4 Leakage test: After the vacuum degree reaches -755mmHg, stop vacuum drying and keep the pressure
for 1 hour. If the indicator of vacuum gauge does not go up, it is qualified. If going up, it indicates that
there is moisture or leak source.
7.3.2 Special vacuum drying
The special vacuum drying method shall be adopted when:
1. Finding moisture during flushing refrigerant pipe.
2. Conducting construction on rainy day, because rain water might penetrated into pipeline.
3. Construction period is long, and rain water might penetrated into pipeline.
4. Rain water might penetrate into pipeline during construction.
Procedures of special vacuum drying are as follows:
1. Vacuum drying for 1 hour.
2. Vacuum damage, filling nitrogen to reach 0.5Kgf/cm2 .
Because nitrogen is dry gas, vacuum damage could achieve the effect of vacuum drying, but this
method could not achieve drying thoroughly when there is too much moisture. Therefore, special
attention shall be drawn to prevent the entering of water and the formation of condensate water.
3. Vacuum drying again for half an hour.
If the pressure reached -755mmHg, start to pressure leakage test. If it cannot reached the value,
repeat vacuum damage and vacuum drying again for 1 hour.
4 Leakage test: After the vacuum degree reaches -755mmHg, stop vacuum drying and keep the pressure
for 1 hour. If the indicator of vacuum gauge does not go up, it is qualified. If going up, it indicates that
there is moisture or leak source.
98
Содержание KV 24CC-ARF21
Страница 1: ......
Страница 5: ...3...
Страница 13: ...Dimensions 2 Dimensions Unit mm MODEL A B C H KV24CC ARF21 230 15 9 9 52 260 11...
Страница 14: ...Service Space 3 Service Space 1000mm 1000mm 1000mm 1000mm 12...
Страница 15: ...Wiring Diagrams 4 Wiring Diagrams KV24CC ARF21 13...
Страница 21: ...Field Wiring 11 Field Wiring KV24CC ARF21 19...
Страница 27: ...Dimensions 2 Dimensions Capacity Btu h A H 36 245 275 48 245 275 25...
Страница 28: ...Service Space 3 Service Space 1000mm 1000mm 1000mm 1000m m 26...
Страница 29: ...Wiring Diagrams 4 Wiring Diagrams KV36CC ARF21B KV48CC ARF21B 27...
Страница 34: ...Field Wiring 9 Field Wiring KV36CC ARF21B KV48CC ARF21B 32...
Страница 36: ...34...
Страница 38: ...Service Space 3 Service Space 36...
Страница 39: ...Wiring Diagrams 4 Wiring Diagrams KV24CM ARF21 37...
Страница 42: ...Air Velocity and Temperature Distributions Reference Data Discharge angle 60 FLOOR Airflow velocity 40...
Страница 46: ...Field Wiring 11 Field Wiring KV24CM ARF21 44...
Страница 48: ...46...
Страница 50: ...Service Space 3 Service Space 48...
Страница 51: ...Wiring Diagrams 4 Wiring Diagrams KV36CM ARF21B KV48CM ARF21B 49...
Страница 54: ...Field Wiring 9 Field Wiring KV36CM ARF21B KV48CM ARF21B 52...
Страница 56: ...54...
Страница 57: ...Dimensions 2 Dimensions Dimension Mode W mm D mm H mm KV36FM ARF21 550 350 1800 KV60FM ARF21 610 390 1925 55...
Страница 58: ...Service Space 56 GA Floor standing Type 3 Service Space 56...
Страница 59: ...Wiring Diagrams 4 W iring Diagrams KV36FM ARF21 KV60FM ARF21 57...
Страница 61: ...Sound Levels 6 Sound Levels Model Noise level dB A H L KV36FM ARF21 56 51 KV60FM ARF21 57 51 59...
Страница 62: ...Accessories 7 Accessories 60...
Страница 64: ...Field Wiring 9 Field Wiring KV36FM ARF21 KV60FM ARF21 62...
Страница 70: ...Wiring Diagrams 4 Wiring Diagrams KV24ODU ARF21 220075301510 KV24ODU ARF21 220075301740 68...
Страница 71: ...Wiring Diagrams KV36ODU ARF21 B 220075501730 KV36ODU ARF21 B 220075502120 69...
Страница 72: ...Wiring Diagrams KV48ODU ARF21B 70...
Страница 73: ...Wiring Diagrams KV60ODU CRF21 71...
Страница 113: ...Troubleshooting 2 1 5 Display board of Floor standing 111...
Страница 118: ...2 4 1 2 Outdoor unit malfunction 116...
Страница 121: ...Troubleshooting Electrical Control System 2 4 2 2 E2 malfunction 119...
Страница 122: ...2 4 2 3 E3 malfunction 120...
Страница 126: ...2 4 2 7 P1 malfunction Only for 36K 52K 124...
Страница 127: ...Troubleshooting 2 4 2 8 P2 malfunction Only for 36K 52K 125...
Страница 128: ...2 4 2 9 P3 malfunction 126...
Страница 131: ...Troubleshooting 2 4 2 12 P6 malfunction For single phase units 129...
Страница 133: ...Troubleshooting 2 4 2 14 P7 malfunction 131...