background image

10

VIII. Maintenance

 

 
Kooltronic Water-Cooled Air Conditioners require no maintenance. Air-Cooled Air 
Conditioners are designed to require only the routine cleaning of air filters to assure 
unimpeded airflow through the condenser heat exchanger. It is not possible to 
recommend specific filter cleaning intervals since the level and the nature of airborne 
particulate matter differs widely with each installation. It is generally sufficient to remove 
and wash the reusable aluminum mesh air filters when the outer surfaces of these filters 
appear covered with a thin layer of dust or lint. Filter recoating adhesive is recommended. 
Appropriate disposable filters are available from Kooltronic. 
 
If filter service is neglected or delayed, the air conditioner will not perform at its design 
capacity. The first indication of excessively clogged air filters is usually a gradual 
increase of temperature within the equipment cabinet. If operation is continued under 
these conditions, the compressor will be shut off by the thermal overload device. The 
compressor will restart when its external temperature drops below the protector threshold 
setting and the compressor will continue to cycle on and off. Continued operation under 
these conditions will cause damage, shorten compressor life and void the warranty. 

 

A. Filter Removal and Service

 

 

Kooltronic Air Conditioners feature an easily removable inlet filter to facilitate 
necessary cleaning. 
 

CAUTION 

 
 

 

 
 
 
 

1) Lift the filter using the attached tab to clear the lower filter retainer. 
 
2) After removal, the filters should be flushed under warm running water with 

the clean side up, driving contaminants out the dirty side of the filter. If the 
accumulated dirt is oily, washing in a detergent bath is recommended, followed 
by a warm water rinse as above. 

 
3) The filters may be sprayed with 

Kooltronic A-16 Filter Recoating Adhesive

 to 

trap fine airborne contaminants, or they may simply be dried and reinstalled as 
strainer type filters. 

Recoating is recommended for best results. 

 
4) Reinstall the filter: (a) keeping the tab at the bottom, slide filter into the upper 

retainer, (b) press filter against the unit and, (c) slide down into lower retainer.

Do not operate the Air Conditioner for extended periods of time with the 

filter removed. The condenser coil may become clogged with dust or 

lint from the air entering the face. A clogged condenser coil is not 

readily detected and will give the same reaction as a clogged filter. A 

clean filter is the best protection.

Содержание L17A3573

Страница 1: ...AUTION BEFORE INSTALLING AND USING THIS AIR CONDITIONER IT IS IMPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 F...

Страница 2: ...age of the Kooltronic website I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all si...

Страница 3: ...prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper connection...

Страница 4: ...ect type or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permanent damage to the unit ALL MO...

Страница 5: ...ure accumulated on the evaporator coil is collected in the condensate tray and released to the ambient air through the drain tube or the condensate evaporator The heat removed through the evaporator c...

Страница 6: ...be delayed until the system pressures rise 10 Operate the air conditioner for approximately ten 10 minutes During this period no unusual noise or vibration should be evident Both the evaporator and co...

Страница 7: ...TAB 6 Insert the remaining 10 32 screws and seal washers supplied by Kooltronic through the Air Conditioner side panel and into the M TAB To avoid misalignment of parts do not tighten any of the scre...

Страница 8: ...8 Drawings and Dimensions NP33 SERIES Other drain outlets are available contact KOOLTRONIC Dimensions inches are for reference only and are subject to change...

Страница 9: ...12 8 90 K2A4C4NP33L 4000 120 50 230 200 60 50 5 5 90 K2A4C4NP33L5 4000 120 50 230 50 5 8 90 KA4C5NP33L 5000 125 50 115 100 60 50 12 8 90 KA4C5NP33L56 5000 125 50 115 50 60 12 8 90 K2A3C5NP33L 5000 125...

Страница 10: ...nd the compressor will continue to cycle on and off Continued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter Removal and Service Kooltronic A...

Страница 11: ...pass valve fails it is strongly recommended that the Air Conditioner be returned to Kooltronic for service D Refrigerant Loss Kooltronic Air Conditioners are subjected to a series of tests to detect r...

Страница 12: ...Control Replace Thermostat or Relay Thermostat defective when applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Ap...

Страница 13: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...

Отзывы: