5
VI. Specific Model Data
Mounting
Kooltronic Heat Exchangers have been engineered to be installed easily. To avoid damaging your
Heat Exchanger, please read the following information before installation:
1.
Remove tape that holds M/TAB to the unit. Remove the M/TAB.
2.
See DRAWING & DIMENSIONS for proper orientation. Place the M/TAB flush against the
outside of the cabinet to locate cutouts and mounting holes.
3.
Make sure the cutouts don't interfere with components inside your cabinet.
4.
Mount the M/TAB to the outside of the cabinet using all the mounting hardware supplied by
Kooltronic (
1/4
-20 screws/nuts/washers). Preferred positions: one in each corner and two near
center on each side. NOTE: Make sure the screws are inserted with heads toward you. Tighten
nuts securely.
5.
Route the power cord through the bottom cut out in your cabinet. Mount the unit to the M/TAB.
Tighten the unit to the enclosure using supplied hardware (10-32 screws/nuts/washers).
6.
Attach overflow drain hose supplied to the drain exit at the bottom of the unit. This hose
must not
be elevated above the exit port. Improper mounting may impede the flow of condensate and may
cause internal malfunctions.
7. Attach supply line to 3/8" O.D. copper tubing Inlet on the side of unit.
8. Attach discharge line to 3/8" O.D. copper tubing Outlet on the side of unit.
Mounting Plan
UNIT
M/TAB
11.63
[295.4]
0.81
[20.6]
3.31
[84.1]
28.75
[730.3]
0.38
[9.7]
10.88
[276.4]
0.63
[16.0]
3.88
[98.6]
TYP.
UNIT
OUTLINE
M/TAB
OUTLINE
(20) .250
[6.4] DIA.
HOLES
0.38
[9.7]
7.13
[181.1]
8.00
[203.2]
2.25
[57.2]
1.81
[46.0]
10.00
[254.0]
15.44
[392.2]
7.50
[190.5]
TYP.
2.25
[57.2]
3.31
[84.1]
6.44
[163.6]
4.13
[104.9]
5.06
[128.5]
(8) .281 [7.0]
DIA. HOLES
1
1
2
2
DRAIN*
POWER
CORD
1
2
3
WATER
INLET
WATER
OUTLET
3
10.13
[257.3]
28.00
[711.2]
11.63
[295.4]
11.63
[295.4]
1
WARM AIR RETURN FROM ENCLOSURE
2
COOL AIR OUTLET TO ENCLOSURE ( Enclosure opening should be located
as high as possible within this area and equal or exceed the size of the cool air outlet).
3
3/8 " COPPER TUBING HOOKUPS
DRAWING & DIMENSIONS
Dimensions, inches [mm], are for reference only and are subject to change.