VI. Pre-Installation Testing
Before mounting the air conditioner to the enclosure, test for proper operation. This will verify the
shipping integrity of the system. Please follow the steps below prior to installation.
CAUTION
1. Allow the unit to sit in a upright position at a room temperature of 65°F minimum, allowing the
system to warm-up. This is particularly important in winter months.
2. Refer to the nameplate for proper electrical voltage and current requirements. Then connect the
power cord to a properly grounded and fused electrical supply. Leave the electrical power off.
3. Note the factory thermostat setting which is typically 75 to 80°F.
4
Adjust the thermostat to its maximum setting.
5. If the unit is equipped with an on-off switch, move it to the on position.
6. Turn electrical power on.
7. Verify that the evaporator blower or fan is running.
8. Adjust the thermostat to its minimum setting. The compressor should start. On units equipped with
a short cycle protector, the compressor will have a delayed start of six (6) minutes from the time
the power is applied to the unit.
9. Verify that the condenser blower or fan is running. Note that on units equipped with a low ambient
kit, the start of the condenser fan or blower will be delayed until the system pressures rise.
10. Operate the air conditioner for approximately ten (10) minutes. During this period no unusual noise
or vibration should be evident. Both the evaporator and condenser fans or blowers should be
delivering air through their respective discharge ports. The cool air discharged should be less than
70°F when the room temperature is between 70 and 80°F.
11. On units equipped with heaters, adjust both the cooling and heating thermostats to their maximum
settings. Verify that the compressor and condenser fan or blower has stopped. Verify elevated
discharge air temperature from the evaporator air discharge.
12. If the unit is equipped with an on-off switch, leave it in the on position. Return the cooling
thermostat to its original setting. If the unit is equipped with a heater, return the heating thermostat
to its original position.
13. Turn off the electrical power source, and disconnect the air conditioner from the power source.
14. If any cover plug is removed to adjust the unit, make certain to put it back in place to maintain the
integrity of the closed-loop airflow system.
NOTE:
Before shipment all Kooltronic, Inc. Air Conditioners are subjected to a performance test.
The Air Conditioner must be standing in its proper mounting position for a
minimum of five (5) minutes prior to testing. Failure to follow this procedure
will cause permanent damage to the compressor.