VI. Pre-Installation Testing

Before mounting the air conditioner to the enclosure, test for proper operation. This will verify the
shipping integrity of the system. Please follow the steps below prior to installation.

CAUTION

1. Allow the unit to sit in a upright position at a room temperature of 65°F minimum, allowing the

system to warm-up. This is particularly important in winter months.

2. Refer to the identification label for proper electrical voltage and current requirements. Then connect

the power cord to a properly grounded and fused electrical supply. Leave the electrical power off.

3. Note the factory thermostat setting which is typically 75 to 80°F.

4. Adjust thermostat to its maximum setting.  

5. If your unit is equipped with an on-off switch, move it to the on position.

6. Turn electrical power on.

7. Verify that the evaporator blower or fan is running.

8. Adjust the thermostat to its minimum setting. The compressor should start. On units equipped with a

short cycle protector, the compressor will have a delayed start of 6 minutes from the time power is
applied to the unit.  

9. Verify that the condenser blower or fan is running. Note, on units equipped with a low ambient kit, the

start of the condenser fan or blower will be delayed until the system pressures rise.

10. Operate the air conditioner for approximately ten (10) minutes. During this period no unusual

noise or vibration should be evident. Both the evaporator and condenser fans or blowers should
be delivering air through their respective discharge ports. The cool discharged air should be less
than 70°F when the room temperature is between 70 and 80°F.

11. On units equipped with heaters, adjust both the cooling and heating thermostats to their maximum

settings. Verify that the compressor and condenser fan or blower has stopped. Verify elevated
discharge air temperature from the evaporator air discharge.

12. If your unit is equipped with an on-off switch, leave it in the on position.  Return the cooling

thermostat to its original setting.  If unit is equipped with a heater, return the heating thermostat to
its original position.

13. Turn off the electrical power source, and disconnect the air conditioner from the power source.

14. If any cover plug is removed to adjust the unit, make certain to put it back in place to maintain the

integrity of the closed-loop airflow system.

NOTE:

Before shipment all Kooltronic, Inc. Air Conditioners are subjected to a performance test.

The Air Conditioner must be standing in its proper mounting position for a minimum of

five (5) minutes prior to testing. Failure to follow this procedure will cause permanent

damage to the compressor.

Содержание K2A3C10HTL

Страница 1: ...E INSTALLING AND USING THIS AIR CONDITIONER IT IS IMPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1...

Страница 2: ...tion Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all sizes and shapes of electronic enclosures...

Страница 3: ...e in a horizontal position only This placement must be done a minimum of 5 minutes prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operati...

Страница 4: ...e that the power source matches these requirements y Use of incorrect type or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met...

Страница 5: ...by means of the vapor compression refrigeration cycle This takes place in a hermetically sealed refrigeration system utilizing either an air cooled or water cooled condenser heat exchanger The warm ai...

Страница 6: ...blower will be delayed until the system pressures rise 10 Operate the air conditioner for approximately ten 10 minutes During this period no unusual noise or vibration should be evident Both the evapo...

Страница 7: ...rity of the closed loop system Use all existing mounting holes to insure stability and a tight seal High strength mounting screws are recommended The external drain hose must not be elevated above the...

Страница 8: ...200 60 50 12 1 150 155 K2A3C9HTL5 9000 125 50 230 50 12 0 150 155 KA3C10HTR 10000 110 50 115 100 60 50 20 0 150 155 KA3C10HTR56 10000 110 50 115 50 60 20 0 150 155 K2A3C10HTL 10000 125 50 230 200 60...

Страница 9: ...ser Blower Motor Capacitor 0452 03 0452 03 0452 03 Condenser Blower Assembly 6076 00 23 6076 00 23 6076 00 23 Evaporator Blower Motor 0261 54 0261 54 0261 150 Evaporator Blower Motor Capacitor 0452 06...

Страница 10: ...2 4 3 6 8 7 0 1 2 4 3 0 6 8 7 1 YELLOW BLUE RED h COMMON RED TO YELLOW CLOSES ON TEMP INCREASE RED TO BLUE OPENS ON TEMP INCREASE COOLING EFFECT DETECTOR TERMINAL BLOCK TO CUSTOMER ALARM SYSTEM LOW A...

Страница 11: ...the filter clears the upper filter retainer 2 After removal the filters should be flushed under warm running water with the clean side up driving contaminants out the dirty side of the filter If the...

Страница 12: ...onditioner from equipment controller or enclosure I Conform to the applicable provisions of PROCEDURE FOR PROPER PACKING AND SHIPMENT OF KOOLTRONIC AIR CONDITIONERS in this manual under Section III PR...

Страница 13: ...or and Evaporator Blower Check Blower Capacitor are running Condenser Blower does Replace Condenser Blower not run Failed Condenser Blower Replace Condenser Blower Thermostat Thermostat or Sensor Repl...

Страница 14: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...

Отзывы: