Problem

Cause

Solution

Unit not cooling. (Temperature

Failed Thermostat

Check Thermostat and Relay wire connections.

difference between return and

or Relay.

Replace Thermostat or Relay.

supply air is less than 10°F).

Evaporator Blower is running. 

Low Line Voltage.

Check Nameplate Voltage against supply Voltage.

Compressor and Condenser Blower
do not run. Return temperature is

Failed Compressor.

Check Compressor wire connections.

above set point plus differential (90°F).

Check Compressor overload.
Check Compressor Capacitor.
Replace Compressor.

Unit not cooling. (Temperature

Failed Evaporator Blower.

Check Blower wire connections.

difference between return and

Check Blower Capacitor.

supply air is less than 10°F).

Replace Evaporator Blower.

Compressor and Condenser Blower
are running. Evaporator Blower does
not run.

Unit not cooling. (Temperature

Low Refrigerant charge.

Check discharge and suction pressure for

difference between return and

Refrigerant leak.

supply air is less than 10°F).

Failed Condenser Blower.

Check Blower wire connections.

Compressor and Evaporator Blower 

Check Blower Capacitor.

are running. Condenser Blower does

Replace Condenser Blower.

not run.

Failed Condenser Blower

Replace Condenser Blower Thermostat

Thermostat or Sensor.

Replace Sensor

Unit not cooling. (Temperature

Condenser or Evaporator

Clean Coil.

difference between return and

Coil clogged.

supply air is less than 10°F).

Evaporator Blower, Condenser

Loss of Refrigerant.

Locate and repair leak.

Blower and Compressor are running.

Ice on Evaporator Coil.

Clean Evaporator Coil.
Check discharge and suction pressure for 
Refrigerant leak.
Check for any obstruction of Evaporator airflow.
Check and seal all openings.

Excessive condensate 

Eliminate the frequency of door openings.

draining and loss of A/C 
sensible cooling performance.

Unit overcooling.

Failed Thermostat.

Check Thermostat wire connections

.

Evaporator Blower, Condenser

Replace Thermostat.

Blower and Compressor are running.

Failed Relay.

Replace Relay.

Compressor cycling more than

Short circuiting of air

Provide baffle in the enclosure separating A/C

.

10 cycles per hour.

between A/C discharge 

outlet and inlet.

and inlet openings.

Excess vibration.

Defective motor in Blower.

Replace motor.

Defective wheel in Blower.

Replace wheel.

Bad Compressor.

Replace Compressor.

Содержание K2A3C10HTL

Страница 1: ...E INSTALLING AND USING THIS AIR CONDITIONER IT IS IMPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1...

Страница 2: ...tion Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all sizes and shapes of electronic enclosures...

Страница 3: ...e in a horizontal position only This placement must be done a minimum of 5 minutes prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operati...

Страница 4: ...e that the power source matches these requirements y Use of incorrect type or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met...

Страница 5: ...by means of the vapor compression refrigeration cycle This takes place in a hermetically sealed refrigeration system utilizing either an air cooled or water cooled condenser heat exchanger The warm ai...

Страница 6: ...blower will be delayed until the system pressures rise 10 Operate the air conditioner for approximately ten 10 minutes During this period no unusual noise or vibration should be evident Both the evapo...

Страница 7: ...rity of the closed loop system Use all existing mounting holes to insure stability and a tight seal High strength mounting screws are recommended The external drain hose must not be elevated above the...

Страница 8: ...200 60 50 12 1 150 155 K2A3C9HTL5 9000 125 50 230 50 12 0 150 155 KA3C10HTR 10000 110 50 115 100 60 50 20 0 150 155 KA3C10HTR56 10000 110 50 115 50 60 20 0 150 155 K2A3C10HTL 10000 125 50 230 200 60...

Страница 9: ...ser Blower Motor Capacitor 0452 03 0452 03 0452 03 Condenser Blower Assembly 6076 00 23 6076 00 23 6076 00 23 Evaporator Blower Motor 0261 54 0261 54 0261 150 Evaporator Blower Motor Capacitor 0452 06...

Страница 10: ...2 4 3 6 8 7 0 1 2 4 3 0 6 8 7 1 YELLOW BLUE RED h COMMON RED TO YELLOW CLOSES ON TEMP INCREASE RED TO BLUE OPENS ON TEMP INCREASE COOLING EFFECT DETECTOR TERMINAL BLOCK TO CUSTOMER ALARM SYSTEM LOW A...

Страница 11: ...the filter clears the upper filter retainer 2 After removal the filters should be flushed under warm running water with the clean side up driving contaminants out the dirty side of the filter If the...

Страница 12: ...onditioner from equipment controller or enclosure I Conform to the applicable provisions of PROCEDURE FOR PROPER PACKING AND SHIPMENT OF KOOLTRONIC AIR CONDITIONERS in this manual under Section III PR...

Страница 13: ...or and Evaporator Blower Check Blower Capacitor are running Condenser Blower does Replace Condenser Blower not run Failed Condenser Blower Replace Condenser Blower Thermostat Thermostat or Sensor Repl...

Страница 14: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...

Отзывы: