VII. Pre-Installation Testing

Before mounting the air conditioner to the enclosure, test for proper operation to verify the shipping integrity of
the system. Pre-installation testing must be done in a non-hazardous location.

CAUTION

1

. The unit must sit in an upright position at a minimum room temperature of 65°F to allow the system to

warm-up. This is particularly important during winter months.

2. Refer to the nameplate for proper electrical voltage and current requirements. Connect the power cord

to a properly grounded and fused electrical supply, leaving electrical power to the unit turned off.

3. Turn the electrical power on by turning the switch on the front panel to ON. 

4. Observe the temperature on the digital display. The thermostat must be set a minimum of 5°F below this

temperature for the compressor to operate (the factory setting is 75°F). To adjust the thermostat, push
the SET button for two (2) seconds, then use the arrows to set the temperature. To store the new set
point value push the SET key again, or wait ten (10) seconds.

5. Verify that the evaporator blower or fan is running.

6. After one (1) minute the condenser blower and compressor should start.

7. Verify that the condenser blower is running.

8. Operate the air conditioner for approximately ten (10) minutes. During this period no unusual noise or

vibration should be evident. Both the evaporator and condenser fans or blowers should be delivering air
through their respective discharge ports. The cool air discharged should be less than 70°F when the
room temperature is between 70°F and 80°F.

9. Reset the thermostat to the factory setting (75°F).    

10. Turn off the electrical power and disconnect the air conditioner from the power source. 

NOTE:

Before shipment all Kooltronic Air Conditioners are subjected to a performance test.

CAUTION

VIII. Customer Enclosure Requirements

1

. The internal air conditioner pressurized volume is 10.8 cu. ft. as shown on the air conditioner nameplate.

This volume must be added to the customer enclosure volume for proper selection of the
Purge/Pressurized Control System.

Air conditioner air leakage is 0.4 CFM at pressure 0.5 i.w.g. For other pressures see the table in
“Principles of Operation on page 6. This air leakage should also be taken into account for proper
selection of the Purge/Pressurized Control System.

2. The air conditioner must be connected to the main enclosure’s (panel’s) power, which must be de-energized

upon loss of pressure by the enclosure 

Purge/Pressurized Control System.

10

The air conditioner must be standing in its proper mounting position for a minimum of five (5)

minutes prior to testing. Failure to follow this procedure will cause permanent damage to the

compressor. To avoid compressor damage do not tip the unit more than 45° from its proper

mounting position.

If the air conditioner is mounted to the cabinet door you must be sure that the door hinges will

support the additional weight of the air conditioner. Also be certain that when the door is

opened fully, the cabinet does not become unbalanced. The actual weight of the unit can be

found in the Technical Data on page 14.

Содержание Hazardous Location K3A4C12HL56LV

Страница 1: ...AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 039 80 2 21 CDR 20308 HAZARDOUS LOCATION SERIES K3A4C12HL5...

Страница 2: ...oting 17 18 XII Warranty 19 NOTE Wiring Schematics are available on the specific model page of the Kooltronic website I Introduction Kooltronic Hazardous Location Air Conditioners HL Series are design...

Страница 3: ...nimum of 5 minutes prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the...

Страница 4: ...ES WHEN INSTALLED ON AN APPROVED PRESSURIZED ENCLOSURE AND CONNECTED TO PURGE PRESSURIZATION CONTROL SYSTEM PER NFPA496 ALSO SUITABLE FOR CLASS I ZONE 2 GROUPS IIA IIB PLUS HYDROGEN AND IIC AIR LEAKAG...

Страница 5: ...of combustible materials or unless all devices within have been de energized WARNING HIGH TEMPERATURE INTERNAL PARTS This Air Conditioner must not be opened unless the area atmosphere is known to be...

Страница 6: ...pressurized customer enclosure must be connected to the Purge Pressurized Control System by gas air lines in parallel The Kooltronic HL Series Air Conditioner must be powered from the pressurized cust...

Страница 7: ...ter consists of a heater a heat control thermostat and a heater limiter The heater control thermostat is a bimetal disk with a fixed set point of 60 F When the entering evaporator air temperature rise...

Страница 8: ...the new set point value push the SET key again or wait 10 seconds HOW TO CHANGE A PARAMETER VALUE To change a parameter s value operate as follows 1 Enter the Programming mode by pressing the SET plu...

Страница 9: ...p code 7 0 65535 rEL Software release 0 rSE Real set point 0 onF on off key enabling ES PbC Kind of probe ntc Adr Serial address 1 1 247 HES Differential for energy saving 0 F 54 54 rrd Regulation res...

Страница 10: ...e ports The cool air discharged should be less than 70 F when the room temperature is between 70 F and 80 F 9 Reset the thermostat to the factory setting 75 F 10 Turn off the electrical power and disc...

Страница 11: ...to the enclosure The contact closure may be used with their control system having a timer function and output signal The output signal would energize a solenoid valve equipped with a fixed orifice or...

Страница 12: ...tion 1 It is recommended that a lift truck be used for installation 2 These externally mounted air conditioners utilize a gasket to ensure a proper seal This seal is necessary to maintain the integrit...

Страница 13: ...6 00 152 0 TYP 6 00 152 0 TYP 1 00 25 0 26 7 0 6 00 152 0 TYP 6 00 152 0 TYP 6 00 152 0 TYP 6 00 152 0 TYP 6 00 152 0 TYP 6 00 152 0 TYP 4 49 114 0 TYP 8 87 225 0 11 28 287 0 21 85 555 0 1 2 MOUNTING...

Страница 14: ...T POWER LOCATION 22 80 579 0 56 00 1422 0 14 91 378 8 61 15 0 12 70 323 0 7 41 188 0 INTERNAL FITTING 1 43 36 0 DETAIL VIEW A INTERNAL PURGE PRESSURE FITTING 1 4 NPT SEE DETAIL VIEW A EXTERNAL PURGE P...

Страница 15: ...IIC Hazardous Locations when used with an approved Type X Purge System on the electrical enclosure Meets NEC Class I Division 2 Groups A B C D and Class I Zone 2 Groups IIA IIB plus hydrogen and IIC...

Страница 16: ...ed under warm running water with clean side up If the accumulated dirt is oily washing in a detergent bath is recommended followed by a warm water wash as above After filter removal the exposed conden...

Страница 17: ...ent controller or enclosure see below Removing Air Conditioner from Pressurized Enclosure Conform to the applicable provisions of PROCEDURE FOR PROPER PACKING AND SHIPMENT OF KOOLTRONIC AIR CONDITIONE...

Страница 18: ...ondensate Eliminate the frequency of door openings draining and loss of A C sensible cooling performance Unit overcooling Failed Thermostat Check Thermostat wire connections Evaporator Blower Condense...

Страница 19: ...received by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a...

Отзывы: