background image

Keep This  Manual 

With Air Conditioner

AIR CONDITIONER 

 

OPERATOR'S MANUAL

CAUTION

 

BEFORE INSTALLING AND 

USING THIS AIR CONDITIONER, 

IT IS IMPORTANT THAT THIS 

MANUAL BE READ AND 

UNDERSTOOD THOROUGHLY

KOOLTRONIC, INC. 

30 Pennington-Hopewell Road 

Pennington, NJ 08534 

609 • 466-3400 

FAX: 609 • 466-1114 

www.kooltronic.com

900-039-106 (12/21) 
(CDR: 20369)

INTREPID 

EP56 SERIES 

K2A6C30EP56TR/BR 

Find additional information on this 
model at kooltronic.com, or use the 
Technical Documents QR code 
below.

Technical 

Documents

K2A6C30EP56TR 

with Serial Numbers J21A2011 and above 

K2A6C30EP56BR 

with Serial Numbers H21A1808 and above

Содержание EP56 Series

Страница 1: ...ONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 039 106 12 21 CDR 20369 INTREPID EP56 SERIES K2A6C30EP56TR BR Find additional information...

Страница 2: ...fic model page of the Kooltronic website I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtu...

Страница 3: ...prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper connection...

Страница 4: ...of incorrect type or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permanent damage to the u...

Страница 5: ...then discharged to the environment When the Kooltronic Air Conditioner is properly sized it should operate constantly and maintain 75 F to 115 F enclosure temperature depending on the ambient temperat...

Страница 6: ...the new set point value push the SET key again or wait 10 seconds HOW TO CHANGE A PARAMETER VALUE To change a parameter s value operate as follows 1 Enter the Programming mode by pressing the SET plu...

Страница 7: ...p code 7 0 65535 rEL Software release 0 rSE Real set point 0 onF on off key enabling ES PbC Kind of probe ntc Adr Serial address 1 1 247 HES Differential for energy saving 0 F 54 54 rrd Regulation res...

Страница 8: ...should be delivering air through their respective discharge ports The cool air discharged should be less than 70 F when the room temperature is between 70 F and 80 F It is normal for the condenser bl...

Страница 9: ...nditioner Hang the air conditioner on the hooks Before the lift truck lowers the air conditioner make sure that the hooks are located inside of the small cutouts on the front panel 4 Tighten the air c...

Страница 10: ...4 163 7 11 38 289 1 7 37 187 2 17 75 450 8 18 57 471 7 53 75 1365 3 4 56 115 8 1 78 45 3 33 21 843 6 0 80 20 3 0 95 24 1 7 46 189 4 TYP 20 25 514 3 1 45 36 7 EP56T EP56B 3 4 3 375 9 5 DIA OPTIONAL MOU...

Страница 11: ...WER CORD 1 1 2 2 EP56B EP56T 3 4 EP56T EP56B 3 4 57 04 1448 7 DRAIN K2A6C30EP56TR BR Dimensions inches mm are for reference only and are subject to change Drawings and Dimensions CONDENSER AIR INLET A...

Страница 12: ...or Capacitor 0452111 Condenser Blower Motor 0261 274 Condenser Blower Capacitor 0452 04 Evaporator Blower Motor 0261 275 Evaporator Coil 0667 51 Condenser Coil 0666 59 01 Thermostat 0750 137 NOTE Part...

Страница 13: ...ued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter and condenser coil service The rear panel must be removed in order to clean the filters Af...

Страница 14: ...running Low Line Voltage Check Nameplate Voltage against supply Voltage Compressor and Condenser Blower do not run Return temperature is Failed Compressor Check Compressor wire connections above set...

Страница 15: ...vaporator Clean Coil difference between return and Coil clogged supply air is less than 10 F Evaporator Blower Condenser Loss of Refrigerant Locate and repair leak Blower and Compressor are running Ic...

Страница 16: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...

Отзывы: