background image

7

VII. Specific Model Data 

    Mounting 

CAUTION 

 
 
 

Kooltronic Air Conditioners have been engineered to be installed easily. To avoid damaging your 
Air Conditioner, please read the following information before installation: 

1.

Loosen the four screws holding the Mounting Template and Assembly Bracket (M/TAB) to the
unit. Remove the M/TAB.

2.

See Figure 1 for proper orientation.Place the M/TAB flush against the outside of the cabinet
to locate cutouts and mounting holes.

3.

NOTE: The top cutout for the warm air return does not have to match the full 7" opening on
the M/TAB. You can locate your cutout anywhere within this opening. Locate your cutout close
to the top and not less than 3" high. 

Make sure the cutouts don't interfere with components

inside your cabinet.

4.

Mount the M/TAB to the outside of the cabinet using all the mounting hardware supplied by
Kooltronic (

1/4

-20 screws/nuts/washers). Preferred positions: one in each corner and two near

center on each side. NOTE: Make sure the screws are inserted with heads toward you. Tighten
nuts securely.

5.

Route the power cord through the top cut out in your cabinet. Mount the unit to the M/TAB by
sliding the 4 studs on the side panel into the 4 slots on the M/TAB. After unit is in place,
tighten 2 screws at bottom of unit. These two screws will force the M/TAB into studs on side
panel for a tight seal.

6.

Attach overflow drain hose supplied to the drain exit at the bottom of the unit.  This hose must
not be elevated above the exit port. Improper mounting will impede the flow of condensate and
may cause internal malfunctions.

If the Air Conditioner is mounted to the cabinet door you must be sure that the 

door hinges will support the additional weight of the Air Conditioner. Also be certain 

that when the door is opened fully, the cabinet does not become unbalanced. The 

actual weight of the unit can be found in the performance specifications.

Dimensions (inches) are for reference only and are subject to change.

MOUNTING PLAN

28

1/

2

2

3/

4

1

1/

2

10

1/

8

28

1/

2

THERMOSTAT
ADJUSTMENT

FILTER

11

1/

2

DRAIN*

M/TAB

POWER
CORD

10

1/8

8
7

1

1/

16

1

9/

16

7

3/

4

3

3/8

3

5/

8

7

3/

4

4

3/

16

7

1/

2

TYP.

(8)

.312 DIA.

HOLES

2

15/

16

4

5/

16

FILTERED
CONDENSER AIR INLET
(Ambient Air In) (NP28 only)

CONDENSER OUTLET
(Warm Ambient Air Out)
(NP28 only)

WARM AIR RETURN
FROM ENCLOSURE

COOL AIR OUTLET
TO ENCLOSURE

FIGURE 1

Содержание E16A1554

Страница 1: ...ION BEFORE INSTALLING AND USING THIS AIR CONDITIONER IT IS IMPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX...

Страница 2: ...age of the Kooltronic website I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all si...

Страница 3: ...prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper connection...

Страница 4: ...ect type or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permanent damage to the unit ALL MO...

Страница 5: ...ure accumulated on the evaporator coil is collected in the condensate tray and released to the ambient air through the drain tube or the condensate evaporator The heat removed through the evaporator c...

Страница 6: ...be delayed until the system pressures rise 10 Operate the air conditioner for approximately ten 10 minutes During this period no unusual noise or vibration should be evident Both the evaporator and co...

Страница 7: ...r cord through the top cut out in your cabinet Mount the unit to the M TAB by sliding the 4 studs on the side panel into the 4 slots on the M TAB After unit is in place tighten 2 screws at bottom of u...

Страница 8: ...INLET Ambient Air In NP28 only CONDENSER OUTLET Warm Ambient Air Out NP28 only WARM AIR RETURN FROM ENCLOSURE COOL AIR OUTLET TO ENCLOSURE Drawings and Dimensions NP28 SERIES Other drain outlets are...

Страница 9: ...5 50 60 13 0 85 K2A4C3NP28L 3000 120 50 230 200 60 50 6 0 85 K2A4C3NP28L5 3000 125 50 230 50 6 5 85 KA4C4NP28L 4000 125 50 115 100 60 50 13 0 12 0 85 KA4C4NP28L56 4000 125 50 115 50 60 13 0 85 K2A4C4N...

Страница 10: ...nd the compressor will continue to cycle on and off Continued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter Removal and Service Kooltronic A...

Страница 11: ...pass valve fails it is strongly recommended that the Air Conditioner be returned to Kooltronic for service D Refrigerant Loss Kooltronic Air Conditioners are subjected to a series of tests to detect r...

Страница 12: ...Control Replace Thermostat or Relay Thermostat defective when applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Ap...

Страница 13: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...

Отзывы: