VII. Specific Model Data
Mounting
Kooltronic Air Conditioners have been engineered to be easily installed. To avoid damaging your air
conditioner, please read the following information before installation:
1. Loosen two screws on the bottom of the unit.
2. See Figure 1 for proper M/TAB orientation.Place the M/TAB flush against the outside of the enclosure
to locate cutouts and mounting holes.
3. NOTE: The top cutout for the warm air return does not have to match the full opening on the M/TAB.
You can locate your cutout anywhere within this opening. Locate your cutout close to the bottom and
not less than 4" high. Make sure the cutouts don't interfere with components inside your cabinet.
4. Mount the M/TAB to the outside of the cabinet using all the mounting hardware supplied by Kooltronic
(
1/
4
-20 screws/nuts/washers). NOTE: Make sure the screws are inserted with heads on M/TAB side.
Tighten nuts securely.
5. Route the power cord through the top cut out in your cabinet. Mount the unit to the M/TAB by sliding
the slots located on the front panel on the hooks of the M/TAB. Using the two hooks on each side of
the M/TAB as a guide, be sure that the air conditioner is absolutely parallel to the M/TAB. We
recommend using a lift truck for mounting the air conditioner. Before the lift truck moves the air
conditioner down, ensure that the M/TAB hooks are located inside of the front panel slots.
6. Tighten two screws on the bottom of the unit and seal the unit against the enclosure.
7. Attach supplied overflow drain hose to the drain exit in the bottom of the unit.
CAUTION
7
If the air conditioner is mounted to the cabinet door you must be sure
that the door hinges will support the additional weight of the air
conditioner. Also be certain that when the door is opened fully, the
cabinet does not become unbalanced. The actual weight of the unit can
be found in the performance specifications.
Dimensions, inches [metric], are for reference only and are subject to change.
CONDENSER AIR
OUTLET
COOL AIR OUTLET
TO ENCLOSURE
WARM AIR RETURN
FROM ENCLOSURE
CONDENSER AIR
INLET
1.00
[25.4]
[7.1]
(16) 0.281
DIA.
HOLES
1.25
[31.7]
0.74
[18.7]
19.25
[488.9]
1.00
31.44
[798.5]
10.00
[254.0]
1.36
[34.5]
18.00
[457.2]
10.00
[254.0]
[25.4]
53.35
[1355.0]
20.64
[524.2]
7.31
[185.6]
(TYP.)
FIGURE 1
MOUNTING PLAN