Kooltronic Air Conditioners are required when the equipment operating temperature must be kept near or
lower than the ambient room temperature, and/or the cabinet must be sealed from dust, fumes, oil, corrosives
and other contaminants. This Air Conditioner utilizes a "Closed-Loop Cooling System" to ensure optimum
performance of the installed components.

Closed-Loop cooling seals the electronic enclosure from hostile elements in the environment. Two separate
circulation systems are employed. The internal system cools and dehumidifies the air inside the cabinet,
totally isolating the sensitive electronics and other components from the environment. The external system
uses circulating ambient air or water to discharge the heat removed from the electronics. The heat is
dissipated from the enclosure by means of the vapor compression refrigeration cycle. This takes place in a
hermetically-sealed refrigeration system, utilizing either an air-cooled or water-cooled condenser heat
exchanger. The warm air inside the enclosure is drawn through the evaporator coil where it is cooled,
dehumidified and returned.

Enclosure moisture accumulated on the evaporator coil is collected and evaporated in the condensate
evaporator tray and released to the ambient air by the condenser blower. Excess condensate is released to
the ambient through the drain tube.

The heat removed through the evaporator coil is transferred by the compressed refrigerant to the condenser
coil. Ambient air or water is then passed through the condenser coil, where it absorbs the heat and is then
discharged to the environment.

The unit is equipped with a Bypass Thermostat to prevent the evaporator coil from freezing and eliminate
compressor cycling. The Bypass Thermostat controls a solenoid bypass valve which allows hot liquid
refrigerant to bypass the evaporator coil. The Bypass Thermostat must not be set below the factory setting
of 75°F (6°F differential). The air conditioner running in bypass mode has 20% of its maximum cooling
capacity. The RP55 is also equipped with a Low Temperature Thermostat. The set point of this thermostat is
5°F lower than the set point of the Bypass Thermostat. If low ambient temperature and internal enclosure
load is less than 20% of the air conditioner’s capacity, the thermostat will shut off the compressor. If
necessary, the thermostat may be adjusted to increase the temperature within the cabinet. Unlike the
thermostats used in household air conditioners that control room temperature, the thermostats used in the
RP55 monitor the return air from the enclosure to prevent the evaporator from freezing. In conditions of low
ambient temperature and low enclosure load, the thermostat regulates the return air temperature from 75°F
to 85°F. If the unit is equipped with an optional non-adjustable high temperature alarm, it will activate when
the return air temperature reaches 130°F.

    

EVAPORATOR

HEAT EXCHANGER

   

 CONDENSATE

EVAPORATOR TRAY

    

CONDENSER HEAT

          EXCHANGER

     

CONDENSER OUTLET

      (Heated Ambient Air Out)

   

 COMPRESSOR

   

     

CONDENSER

        AIR INLET
    ( Ambient Air In)

   

ACCUMULATOR

   

         REFRIGERANT
          FILTER DRIER

         HEATED AIR FROM
              ENCLOSURE

                   COOL AIR TO
                   ENCLOSURE

                   M/TAB 
                   

V. Principles of Operation

RP55

Содержание Advantage RP55 Series

Страница 1: ...TANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 039 38 2 19 CDR 20131 ADVANT...

Страница 2: ...tion Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all sizes and shapes of electronic enclosures...

Страница 3: ...e in a horizontal position only This placement must be done a minimum of 5 minutes prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operati...

Страница 4: ...Use of incorrect type or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permanent damage to t...

Страница 5: ...hen passed through the condenser coil where it absorbs the heat and is then discharged to the environment The unit is equipped with a Bypass Thermostat to prevent the evaporator coil from freezing and...

Страница 6: ...r respective discharge ports The cool air discharged should be less than 70 F when the room temperature is between 70 F and 80 F 10 Turn off the electrical power and disconnect the air conditioner fro...

Страница 7: ...e front panel on the hooks of the M TAB Using the two hooks on each side of the M TAB as a guide be sure that the air conditioner is absolutely parallel to the M TAB We recommend using a lift truck fo...

Страница 8: ...1 25 31 7 0 74 18 7 19 25 488 9 1 00 31 44 798 5 10 00 1 36 34 5 18 00 457 2 25 4 53 35 1355 0 20 64 524 2 7 31 185 6 TYP LEFT FRONT RIGHT REAR BOTTOM TOP 254 0 10 00 254 0 0 69 17 5 6 00 15 2 21 99...

Страница 9: ...P55R Part Part Number Compressor 0665 78 Compressor Capacitor 0452 61 Condenser Blower Motor 0261 138 Condenser Blower Capacitor 0452 44 Evaporator Blower Motor 0261 288 Evaporator Blower Capacitor 04...

Страница 10: ...OTOR CAP BK WE CRANKCASE HEATER PRESSURE SWITCH N O COOLING EFFECT DETECTOR TERMINAL BLOCK TO CUSTOMER ALARM SYSTEM RELAY 1 R CONTROL Y B T STAT HEATER HEATER B C T STAT CUT OUT THERMAL TRANSFORMER DI...

Страница 11: ...operation under these conditions will cause damage shorten compressor life and void the warranty A Filter Removal and Service Kooltronic Air Conditioners feature an easily removable inlet filter to fa...

Страница 12: ...ss valve fails it is strongly recommended that the air conditioner be returned to Kooltronic for service D Refrigerant Loss Kooltronic Air Conditioners are subjected to a series of tests to detect ref...

Страница 13: ...applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Application Failed Evaporator Blower Replace Evaporator Blower Mo...

Страница 14: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...

Отзывы: