SMLD smoke evacuation damper

Mounting instructions

ELECTRICAL CONNECTIONS

Left

Right

FCU: single-pole safety position contact (end 

position)

DCU: single-pole standby position contact (start 

position)

FCB: two-pole safety position contact (end

position)

DCB: two-pole standby setting contact (start 

position)

Note:

 The micro-contacts are shown in their

working position, closed damper slats

(DC contact actuated and FC contact free)

•   Remote-controlled version

The remote control and supply voltage for the position contact connections must be:

SELV (24 or 48 V).

Left

Right

Standby position 

contacts  (DCB)            

Safety position con-

tacts (FCB)

Remote-

controlled system

Standby position 

contacts  (DCU)            

Safety position

contacts (FCU)

9

Содержание SMLD

Страница 1: ...www koolair com SMLD Mounting instructions Smoke evacuation damper...

Страница 2: ...g to product type 2 Damper drawing 4 Fire resistance as per EN 13501 4 4 Product code explanation 4 Dimensions and openings 4 Testing and certification 5 Installation and on site placement 6 Frame mou...

Страница 3: ...control Safety options Built in level 1 open close manual control Standby position contact DCU Safety position contact FCU Operating mode With intrinsic power supply With intrinsic power supply Contr...

Страница 4: ...ection Any Any Fire direction Any Any Type of mounting Wall recessed Attachment with or without frame Wall recessed Attachment with or without frame Protection grille With RPK protection grille With R...

Страница 5: ...oduct labelling FIRE RESISTANCE AS PER EN 13501 4 EI 120 Ved i o S 1500 AA MULTI PRODUCT CODE EXPLANATION E Integrity 120 Resistance time in min i o Either side of fire 1500 Pressure level in pascals...

Страница 6: ...de la chaleur Partie 8 Volets de d senfumage Organisme Certificateur LGAI Technological Center S A Campus UAB Ronda de la Font del Carmen s n E 08193 Bellaterra Barcelona T 34 93 567 20 00 F 34 93 567...

Страница 7: ...IN DUCTS OTHER THAN THOSE TESTED The multi com partment smoke control dampers are used with ducts subject to tests as per EN 1366 8 as appropria te or constructed from materials with the same density...

Страница 8: ...in the duct with the help of 4 screws supplied with the frame Drill a hole to pass the connections to the duct SMLD MOUNTING Mount the damper in the mounting frame the folding feet of the damper are...

Страница 9: ...rom moisture Avoid deterioration Avoid contact with water Avoid damper body deformation during assembly and sealing Avoid damper blows and tilting during transport Grille x4 Screws ACCESSORIES The use...

Страница 10: ...wo pole standby setting contact start position Note The micro contacts are shown in their working position closed damper slats DC contact actuated and FC contact free Remote controlled version The rem...

Страница 11: ...l Power Left Right Standby position contacts DCB Safety position contacts FCB Motor Standby position contacts DCU Safety position contacts FCU Remote controlled version motor Right Standby position co...

Страница 12: ...on of sealing products and handled with care During commissioning of the installation clean all dust and grime on the assembly to prevent risks of slat deterioration The electromagnetic coil is an ext...

Страница 13: ...g the key provided with the damper MAINTENANCE AND WARRANTY INSTRUCTIONS No maintenance in particular Perform at least one operational test per year KOOLAIR shall be released from its liability in the...

Страница 14: ...THIS CATALOGUE IS COPYRIGHTED Partial or full reproduction of its content is strictly prohibited without express written authorisation from KOOLAIR S A CEN MISMLD 1115 00 13...

Страница 15: ...2 La Fuensanta 28936 M stoles MADRID Tel 34 91 645 00 33 Fax 34 91 645 69 62 e mail comercial comercial koolair com e mail Koolair info koolair com Koolair S A reserves the right to change publisher...

Отзывы: