Circular fire dampers
Standards
The dampers are approved in accordance with European Test Standard UNE-EN 1366-2 and European
classification standard UNE-EN 13501-3, where:
(E) Integrity
(I) Isolation
(ho) Installed in Horizontal slab. Mounted in horizontal enclosure.
(ve) Installed in wall or stud wall. Mounted in vertical enclosure.
(i ↔ o) Symmetric (independent of airflow direction). Suitable for fire in both directions (interior-exterior and
exterior-interior)
(S) Airtightness. Leakage through the damper closing blade <200 m
3
/h*m
2
Option for fire dampers to be supplied with airtightness C to comply with EN 1751.
Motor-driven fire dampers can be integrated into the building management system (BMS) and/or fire panel with the
KOOLCOM system from KOOLAIR.
To guarantee the correct fire damper operation, it is essential to read and follow the recommendations in the
installation and operation manual. In addition, the installation must comply with all current national standards.
Further information and updates, as well as the installation and operating manual, can be found on our website
(www.koolair.com).
CE Marking
Koolair fire dampers carry the CE marking in compliance with RPC-305/2011/EU, according to EN15650:2010.
NF Marking
The SCFR-PD, SCFR-GD, SCFC-PD and SCFC-GD models are certified under NF (NF264 Certification Standard,
NF S 61-937-5 fire dampers).