Circular fire dampers

Standards

The dampers are approved in accordance with European Test Standard UNE-EN 1366-2 and European

classification standard UNE-EN 13501-3, where:

(E) Integrity

(I) Isolation

(ho) Installed in Horizontal slab. Mounted in horizontal enclosure.

(ve) Installed in wall or stud wall. Mounted in vertical enclosure.

(i ↔ o) Symmetric (independent of airflow direction). Suitable for fire in both directions (interior-exterior and

exterior-interior)

(S) Airtightness. Leakage through the damper closing blade <200 m

3

/h*m

2

Option for fire dampers to be supplied with airtightness C to comply with EN 1751.

Motor-driven fire dampers can be integrated into the building management system (BMS) and/or fire panel with the

KOOLCOM system from KOOLAIR.

To guarantee the correct fire damper operation, it is essential to read and follow the recommendations in the

installation and operation manual. In addition, the installation must comply with all current national standards.

Further information and updates, as well as the installation and operating manual, can be found on our website

(www.koolair.com).

CE Marking

Koolair fire dampers carry the CE marking in compliance with RPC-305/2011/EU, according to EN15650:2010.

NF Marking

The SCFR-PD, SCFR-GD, SCFC-PD and SCFC-GD models are certified under NF (NF264 Certification Standard,

NF S 61-937-5 fire dampers).

Series SF

3

Содержание SCFC-GD

Страница 1: ...series Fire dampers SF www koolair com...

Страница 2: ...rcular fire dampers CONTENTS Description 2 Declared performance 4 Applications 6 Model and dimensions 8 Accessories 13 Installation 14 Operating Mechanisms 19 Special finishes 22 Technical data 23 Cod...

Страница 3: ...xceeds 72 C It is reset manually in all instances except when incorporating a servomotor with return spring and a thermoelectric fusible link calibrated at 72 C All dampers comply with requirements of...

Страница 4: ...C to comply with EN 1751 Motor driven fire dampers can be integrated into the building management system BMS and or fire panel with the KOOLCOM system from KOOLAIR To guarantee the correct fire damper...

Страница 5: ...6 SCFR GD CPR 2591 16 SFR3K1GT CPR 1493 14 Dimensions mm Dimensions mm Construction details Construction details Installation location Installation location Installation location Installation Installa...

Страница 6: ...EI 90 2 sheets of laminated fireproof plasterboard ref KNAUF cortafuego DF thickness 12 5 mm Rock wool panel ref ProRox SL960 ROCKWOOL 2 sheets of laminated fireproof plasterboard ref KNAUF cortafuego...

Страница 7: ...0 100 200 300 400 500 600 650 700 800 H mm SCFR PD SCFR GD SCFR GD L mm 200 300 400 500 600 700 800 100 200 300 400 500 600 H mm SCFR PD Applications FIXED WALL EI 180 EI 180 ve i o S RECTANGULAR FIXE...

Страница 8: ...0 125 160 200 250 315 355 400 450 500 560 630 650 700 710 750 800 SCFC GD EI 120 S SCFC PD EI 120 S SCFC GD EI 180 S mm 100 125 160 200 250 315 355 400 450 500 560 630 SCFC PD SCFC GD Applications SLA...

Страница 9: ...are available in standard sizes duct size with a length L dimension from 200 to 800 mm increasing in 50mm increments and a height dimension H from 100 to 600 mm increasing in 50mm increments 1 Galvan...

Страница 10: ...dimensions 1 Galvanised steel frame 2 Damper blade 3 Mechanism motor housing 4 Intumescent seal 5 30 mm flange Drive shaft SCFR GD fire dampers are available in standard sizes duct size with a length...

Страница 11: ...R3K1GT fire dampers are available in standard sizes duct size with a length L dimension from 200 to 1500 mm increasing in 50mm increments and a height dimension H from 200 to 800 mm increasing in 50mm...

Страница 12: ...dimensions The standard dimensions duct dimensions of SCFC PD fire dampers are 100 125 160 200 250 315 and 355 mm Drive shaft nom inal 2 1 Galvanised steel frame 2 Blade 3 Mechanism motor housing 4 In...

Страница 13: ...CFC GD Model and dimensions The standard dimensions duct dimensions of SCFC GD fire dampers are 400 450 500 560 630 650 700 710 750 and 800 mm nominal 2 nominal 48 Drive shaft 1 Galvanised steel frame...

Страница 14: ...in FUSIBLE LINK DAS ELECTRIC COIL DAS CONTACT POSITION SIEMENS SERVOMOTOR DAS SAFETY OPERATING DEVICES DAS AND ACCESSORIES Start and end of run position contacts Electrical devices that indicate the...

Страница 15: ...or partition As such when the fire damper blade is in the closed position it will be exactly vertical in the firewall as if it were an extension of this wall as required by UNE EN 1366 2 Likewise the...

Страница 16: ...and uprights in 400 mm spacing Pladur FOC 12 5 Pladur FOC 12 5 Pladur FOC 12 5 Pladur FOC 12 5 TYPE A Pladur FOC 12 5 TYPE B Type A Type A Type B Type B Type A Pladur FOC 12 5 NOTE The distance betwee...

Страница 17: ...ly to horizontal and vertical dampers There must be a minimum separation of 75 mm between fire dampers and building elements There must be a minimum separation of 200 mm between fire dampers The slot...

Страница 18: ...device at 0 Airflow direction is not critical ve i o o ho i o Manual device at top Manual device at 180 Manual device at bottom Motor driven Motor driven Motor driven device at 0 Motor driven device...

Страница 19: ...l device at 0 Manual device at top Manual device at 180 Manual device at bottom Motor driven Motor driven Moto driven device at 0 Motor driven device at top Motor driven device at 180 Motor driven dev...

Страница 20: ...en alloy fuse is triggered by temperatures over 72 C The damper is reset opened by pressing the E shaft until the electromagnet is energised undervoltage release or de energised shunt release and inse...

Страница 21: ...ith return spring A or D Manually inserting the lever in hole A and turning clockwise Damper is closed operated by providing electric supply to shunt release or by switching off supply to undervoltage...

Страница 22: ...r 24 48 V AC DC to the same terminals as shown in the electrical wiring diagram Manually inserting the lever in hole A and turning clockwise Damper is closed operated by providing an electrical supply...

Страница 23: ...ssible to supply rectangular and circular dampers with transformation spigots on request as a non standard finish These couplings may require a longer frame length than the defined standard in order t...

Страница 24: ...300 AL m2 0 19 0 14 0 14 0 14 0 14 0 14 0 14 0 14 0 14 0 14 0 14 0 14 0 14 kp 4 4 3 3 3 3 2 2 2 2 2 1 1 kdB A 450 0 085 0 106 0 128 0 149 0 170 0 191 0 213 0 234 0 255 0 276 0 298 0 319 0 340 AL m2 0...

Страница 25: ...ect a 600 x 500 mm SCFR PD damper We use the table on the previous page to find the following data AL 0 285 m2 kp 0 14 kdB A 1 The technical data to achieve a flow rate of 5450 m3 h is required Referr...

Страница 26: ...1 0 0 0 0 kdB A 800 0 150 0 188 0 225 0 263 0 300 0 338 0 375 0 413 0 450 0 488 0 525 0 563 0 600 AL m2 0 75 0 67 0 60 0 54 0 49 0 44 0 40 0 37 0 34 0 30 0 28 0 25 0 23 kp 3 2 2 2 1 1 1 1 0 0 0 0 0 k...

Страница 27: ...0 0 0 0 kdB A 500 0 383 0 405 0 428 0 450 0 473 0 495 0 518 0 540 0 563 0 585 0 608 0 630 0 653 0 675 AL m2 0 40 0 38 0 35 0 34 0 32 0 30 0 28 0 27 0 25 0 23 0 22 0 21 0 19 0 18 kp 1 1 1 0 0 0 0 0 0 0...

Страница 28: ...ct a 1000 x 300 mm SCFR GD damper We use the table on the previous page to find the following data AL 0 25 m2 kp 0 56 kdB A 2 The technical data to achieve a flow rate of 5500 m3 h is required Referri...

Страница 29: ...533 0 572 AL m2 0 48 0 43 0 39 0 37 0 34 0 33 0 31 0 30 0 29 0 28 0 27 0 26 0 26 kp 11 7 5 3 1 0 0 1 2 3 4 5 6 kdB A 900 0 120 0 163 0 207 0 251 0 295 0 339 0 382 0 426 0 470 0 514 0 558 0 601 0 645 A...

Страница 30: ...0 45 50 0 25 0 35 0 50 0 90 veff m s kp P Pa 5000 7500 10000 12500 15000 25000 3000 2000 1000 800 600 400 200 1 10 veff m s 0 01 0 10 1 00 A L m 2 Q m3 h 0 20 20 55 60 LwA dB A 17500 20000 22500 Techn...

Страница 31: ...m s 20 25 Technical data Selection example For the given duct dimensions we select a SCFC PD damper with a diameter of 200 mm for a flow rate of 500 m3 h Referring to the diagram above using this flo...

Страница 32: ...25 710 750 800 Technical data Selection example For the given duct dimensions we select a SCFC GD damper with a diameter of 500 mm for a flow rate of 5000 m3 h Referring to the diagram above using th...

Страница 33: ...FC PC MOTOR 24 48 RESET B IMP 48 V AC FC PC MOTOR 24 48 RESET B IMP 220 V AC FC PC MOTOR 110 230 RESET B RUPT 24 V CC FC PC MOTOR 24 RESET B RUPT 48 V CC FC PC MOTOR 24 48 RESET B RUPT 24 V AC FC PC...

Страница 34: ...THIS CATALOG IS INTELLECTUAL PROPERTY The partial or total reproduction of its contents is forbidden without the express and authoritative authorisation of KOOLAIR S A CEN SF 1117 00 Series SF 33...

Страница 35: ...KOOLAIR S A Calle Urano 26 Poligono industrial n 2 La Fuensanta 28936 M stoles Madrid Espa a Tel 34 91 645 00 33 Fax 34 91 645 69 62 e mail info koolair com www koolair com...

Отзывы: