Installation
Mounting in stud wall
SCFR-PD
SCFC-PD
Wall studs must be offset
Test conditions:
- 15-8577-939 (SCFC-PD): KNAUF “cortafuego DF” fireboard.
- 15-8577-1076 (SCFR-PD): KNAUF “cortafuego DF” fireboard.
Wall studs must be offset
L n 70
Ø n 150
L n 400
H n 70
Ø nominal
+ 150
(Ø nominal/2) + 75
(Ø nominal/2) + 150
Ø n 150
Ø n 300
Ø nominaL
Ø nominal
Ø nominal
Ø n 150
(Ø nominal/2) + 103
H n 400
48 mm
channels
and uprights
in 400 mm
spacing
48 mm
channels
and uprights
in 400 mm
spacing
Pladur FOC 12.5
Pladur FOC 12.5
Pladur FOC 12.5
Pladur FOC 12.5
TYPE A
Pladur FOC 12.5
TYPE B
Type A
Type A
Type B
Type B
Type A
Pladur FOC 12.5
NOTE: The distance between
screws should not exceed 150 mm
NOTE: The distance
between screws should not exceed 150 mm
Pladur FOC 12.5
Screw PL 3.5x25
Screw PL 3.5x25
Screw PL 3.5x35
Screw PL 3.5x35
Screw PL 3.5x35
Screw PL 3.5x35
Screw PL 3.5x35
Rock wool
40 mm of 100 Kg/m
3
Rock wool
40 mm of 100 Kg/m
3
To guarantee the correct fire damper operation, it is essential to read and follow the recommendations in the
installation and operation manual. In addition, the installation must comply with all current national standards.