Control Units CU 5x-2xxx – Rev. 1.A
// 24
Figure 5: Interfaces/Connectors Extension part Back side of the model CU 5x-2x1x
RS232 Connector X8
Table 13: RS232 Connector X8
Pin
Signal
Type
Comment
1
-
2
RxD
IN
RS232 Receive Data
3
TxD
OUT
RS232 Transmit Data
4
-
5
GND
GND
6
-
7
RTS
OUT
RS232 Request to Send
8
CTS
IN
RS232 Clear to Send
9
-
CASE
GND
GND
Cable (acc. to chapter 2.2/ EMC): max. 3 m, shielded
CAN Connector X9.1
Table 14: CAN Connector X9.1
Pin
Signal
Type
Comment
1
SHIELD
SHLD
2
CANH
I/O
CAN Signal CAN_HIGH
3
CANL
I/O
CAN Signal CAN_LOW
4
GND_CAN
GND
Cable (acc. to chapter 2.2/ EMC): max. 30 m, shielded
Connector Type: Phoenix MCDN 1.5/ 4-G1-3.5 – 1953732
Mating connector: e.g. Phoenix FMC 1.5/ 4-ST-3.5 – 1952283
Associated permissible cable cross-sections:
Conductor cross-section min: 0.2 mm² (corresponds AWG 24)
Conductor cross-section max: 1.5 mm² (corresponds AWG 16)*
*max. conductor cross-section reduced to 0.75 mm
2
for ferrules with plastic ferrule
E1
X6
Содержание CU 5 -2 Series
Страница 1: ...USER GUIDE www kontron com Control Units CU 5x 2xxx Doc Rev 1 A Doc ID 90216 EN...
Страница 2: ...Control Units CU 5x 2xxx Rev 1 A www kontron com 2 This page has been intentionally left blank...
Страница 42: ...Control Units CU 5x 2xxx Rev 1 A www kontron com 42 This page has been intentionally left blank...
Страница 43: ...Control Units CU 5x 2xxx Rev 1 A www kontron com 43 This page has been intentionally left blank...