Periodically check the connections at the connection po-
ints, tighten the terminals if necessary. It is forbidden to
use a cable without a fuse or if the fuse is blown
The generator can only be used to charge the battery. It
is forbidden to use the generator for direct connection to
voltage consumers.
IMPORTANT!
IMPORTANT!
All connecting the generator to the network must be
made by certified electrician in accordance with all elect
-
rical rules and regulations.
WARNING!
COMMISSIONING
COMMISSIONING
1. Fill the crankcase with engine oil. The recommended amount of oil for each model is indicated in the
specification chart.
2. Check oil level with an oil dipstick. It should be between the MIN and MAX marks on the oil dipstick.
3. Check fuel level.
4. Check the air filter for correct installation
5.To connect the generator, use the original wires that come in a kit together with the generator.
6. The wires should first be attached to the terminals on the generator panel and then to the battery.
7. When connecting the wires, tighten the terminals well - both on the generator panel and on the side
consumer.
8. Be sure to observe the polarity when connecting.
“
+” - (red)
“-” - (black)
When the „AUTO” mode is activated on the front panel, the generator will be controlled automatically using
the built-in controller.
To switch to „AUTO” mode you need
1. Set the mode switch to „AUTO”.
2. On the generator panel, turn the switch wheel to the ON position.
FUNCTIONS OF GENERATOR
FUNCTIONS OF GENERATOR
1. The generator is started when the battery voltage drops to 48V.
2. Reaction time before starting the generator - 5 seconds.
3. The generator stops when the voltage on the consumer reaches 53.5-54V, as well as the power drop
current lower than 20A.
4. Reaction time to stop the generator - 30 seconds.
AUTOMATIC CONTROL FUNCTIONAL DESCRIPTION
7
If there is no fuel in the tank the generator will do 5
attempts to start the generator, then go to error mode.
To unlock, you need to update the switch to the OFF po-
sition, refuel, and follow the instructions to switch to the
desired mode.
NOTE