it can be counted from the initial value to the maximum value of 65535, and then it can be re-counted from 0.
The DI signal must be kept for several sampling periods before it can be confirmed. The default value is 0x6, which
means that 6 sample periods are required to be confirmed. This value can be modified according to the site
conditions, and the range is 0-20.
When set to auto-zero, the DI positive/negative pulse count or DI logic level count value will be automatically
cleared after each reading.
When set to manually clear, DI positive/negative pulse count and DI logic level count value will not be cleared
every time, and need to be cleared manually. (Manually write the value 0 to clear)
• Level mode: The on-off state of the relay can only be changed by the command.
• Pulse mode: After set to pulse mode, the relay will automatically change the state of NO and COM from close to
open within a certain time. The time can be set by the pulse width, and the pulse width can be set in the range of
50 ~ 65535 ms.