8

UAB KOMFOVENT reserves the right to make changes without prior notice

ZC-19-02

2.2. Zone module connection to Verso Pro units

To Verso Pro unit zone module must be connected to connection box PD2. Connection box is located in the supply fan 

section, fixed on the wall near the supply air outlet. Depending on the AHU model, inside of the PD2 box it can already be 

connected cable for electrical heater section (please refer to the wiring diagram of the exact unit). In that case zone module 

cable is connected to the same contacts, without disconnecting electrical heater cable. 

CAT5 or similar twisted pair cable is recommended for the connection. If more than one zone module will be used, the 

second module can be connected in parallel from the PD2 box or from the first zone module. Maximum length of the cable 

from C5 board to the last zone module cannot exceed 150 m.

Zone control module is not needed, if complete Verso Pro electrical heater section is used as additional temperature zone 

heater or additional heating step (see application examples in section 1.2.). In such case the electrical wiring is the same as 

above, but cable from PD2 box is connected directly to the PM board located inside of electrical heater.

PD2 connection box

Zone module 1

(PM board)

Zone module 2

(PM board)

PD2 

connection box

1
2

3

4

9

10
11

12

A
B
+24V
GND

9

10
11

12

A

B

+24V

GND

+24V

GND 

A

B

Содержание C5

Страница 1: ...21 C 22 C 20 C ADDITIONAL ZONE CONTROL C5 INSTALLATION MANUAL ...

Страница 2: ...Zone module connection to Verso Standard units 7 2 2 Zone module connection to Verso Pro units 8 3 CONFIGURATION AND WIRING 9 3 1 Zone module configuration for water heater cooler 10 3 2 Zone module configuration for modulating type direct expansion DX units 11 3 3 Zone module configuration for ON OFF type direct expansion DX units 12 3 4 Zone module configuration for additional electrical heater ...

Страница 3: ...ne modules which will control additional duct mounted heaters coolers and temperature sensors connected Temperature set point for each independent temperature zone will be available from the control panel of the AHU If needed zone modules can also control additional heaters coolers to be used in the same airflow as additional steps when main heater cooler power is not enough In that case additiona...

Страница 4: ... same purpose Aditional heating cooling steps VERSO STANDARD Zone 1 module Zone 2 module 20 C C5 MAIN ZONE MAIN ZONE ZONE 1 Independent VERSO PRO PM PM 23 C 22 C 20 C PD2 VM1 C5 PM MAIN ZONE ZONE 1 ZONE 2 Zone 1 module Zone 2 module 21 C 22 C 20 C PD2 VM1 PM C5 MAIN ZONE ZONE 1 ZONE 2 PD2 VM1 C5 PD2 VM1 C5 Independent VERSO PRO Zone 2 module 0 C PRE HEATER Aditional heating cooling steps VER AIN Z...

Страница 5: ...le 20 C PD2 VM1 C5 PM MAIN ZONE PM PM 20 C PD2 VM1 C5 PM MAIN ZONE Independent VERSO PRO Zone 1 module Zone 2 module 0 C 22 C MAIN ZONE PRE HEATER ZONE 1 20 C PD2 VM1 C5 PM Aditional heating cooling steps VERSO PRO MAIN ZONE MAIN ZONE Zone 1 module Zone 2 module 20 C PD2 VM1 C5 PM MAIN ZONE PM PM 20 C PD2 VM1 C5 PM MAIN ZONE Independent VERSO PRO Zone 1 module Zone 2 module 0 C 22 C MAIN ZONE PRE ...

Страница 6: ...erent independent temperature zones supply temperature sensor must be installed after the heating cooling device In cases if zone module is used to control a preheater temperature sensor must be installed between preheater and the AHU Supply temperature sensor should be mounted in the straight air duct after heating cooling device or pre heater at a distance of at least of two duct diameters or tw...

Страница 7: ...lease refer to the Verso Standard installation manual Also external 24 VDC power supply is needed CAT5 or similar twisted pair cable is recommended for the connection If more than one zone module will be used the sec ond module can be connected in parallel from the C5 board or from the first zone module Maximum length of the cable from C5 board to the last zone module cannot exceed 150 m C5 contro...

Страница 8: ...similar twisted pair cable is recommended for the connection If more than one zone module will be used the second module can be connected in parallel from the PD2 box or from the first zone module Maximum length of the cable from C5 board to the last zone module cannot exceed 150 m Zone control module is not needed if complete Verso Pro electrical heater section is used as additional temperature z...

Страница 9: ...witch is intended for zone number selection and SW2 switch is for heater cooler configuration At first assign zone number to the zone module by configuring SW1 DIP switches as follows ON ON 1 2 3 4 5 6 7 1 2 ON ON 1 2 3 4 5 6 7 1 2 SW1 SW2 DIP switches SW1 Zone 1 Zone 2 ON ON 1 2 1 2 Water heater cooler ON 1 2 3 4 5 Heating ON 1 2 3 4 5 Cooling ON 1 2 3 4 5 Heating Cooling ON 1 2 3 4 5 Combi coil ...

Страница 10: ...ee way valve actuators and two circulation pumps Combi coil the same one water coil one three way valve and one circulation pump will be used for heating and for cooling Additional input is needed to switch between heating cooling modes for example from the thermostat or signal from boiler If water heaters coolers are intended to be used in negative air temperatures frost protection is needed For ...

Страница 11: ...l 5V Electrical wiring of external components GN 24 0 10 GN GN GN A B 24 24 0 10 0 10 NO5 C NO2 NO3 NO4 NO1 NTC NTC NO C NO C NO C NO C Hot water Combi coil mixing valve DX unit capacity regulation Cold water mixing valve Cold water mixing valve optional Cold water mixing valve optional Communication with AHU Water circulation pump Common Heating Combi Cooling Supply air temperature sensor Return ...

Страница 12: ... Step3 DX1 DX2 DX3 Binary when all DX units are starting according binary code and in such a way more steps can be achieved This type is recommended when capacities of DX units are different and in ideal case the capacity of each of the following DX unit is double the previous Example of binary control Step1 DX1 Step2 DX2 Step3 DX1 DX2 Step4 DX3 Step5 DX3 DX1 Step6 DX3 DX2 Step7 DX3 DX2 DX1 Electr...

Страница 13: ... 10V Output Output Input Modbus 2 3 4 5 6 7 8 9 10 11 12 25 26 27 28 29 30 31 32 33 34 35 36 Output Output NO5 C NO2 NO3 NO4 NO1 13 14 15 16 17 18 19 20 21 22 23 24 Input Input Input Input Input Input NTC NTC NO C NO C NO C NO C Communication with AHU DX unit control Common DX1 DX2 DX3 DX4 Reverse Close Heating Supply air temperature sensor DX unit failure Open OK Close Alarm 1 GND 24V 0 10V GND G...

Страница 14: ... which additional zones will be used For the control of independent temperature zones or pre heater see application examples in section 1 check mark option Independent and enter desired temperature setpoint Heat exchanger Supply air fan Exhaust air fan Outdoor air filter Extract air filter Air dampers Electric heater Water heater Water cooler DX unit Recirculation Humidity control unit Heat pump A...

Страница 15: ...perate Enable Setpoint 20 0 C 120 8 Kp Ki Independent 1ST ADDITIONAL ZONE CONTROL ZN1 Heat exchanger Supply air fan Exhaust air fan Outdoor air filter Extract air filter Air dampers Electric heater Water heater Water cooler DX unit Recirculation Humidity control unit Heat pump Additional zone 1 Additional zone 2 CF defrost module Rotary None STRUCTURE Stage 1 Stage 2 Stage 3 Stage 4 Water Zone1 Zo...

Страница 16: ...T Légtechnikai Zrt www airvent hu Gevent Magyarország Kft www gevent hu Merkapt www merkapt hu IR Fantech Ventilation Ltd www fantech ie IS Blikk Tækniþjónustan ehf www bogt is Hitataekni ehf www hitataekni is IT Icaria srl www icariavmc it NL Ventilair group www ventilairgroup com DECIPOL Vortvent www vortvent nl NO Ventistål AS www ventistal no Thermo Control AS www thermocontrol no PL Ventia Sp...

Отзывы: