After independent temperature zone was configured, temperature setpoint can be adjusted from the user level on the
computer or from the control panel.
In cases when zone module is used for additional heating/cooling steps and should start when the capacity of main heaters/
cooler is not enough (see application examples in section 1), leave the “Independent” check box empty and main temperature
setpoint set in the “Operation modes” will be used.
Additionally, for such regulation, it is needed to configure “Heating/cooling sequence” (Service level ->Functions) and select
the order in which heating/cooling devices and zone modules should operate.
Enable
Setpoint
20.0
°C
120
8
Kp
Ki
Independent
1ST ADDITIONAL ZONE CONTROL (ZN1)
Heat exchanger
Supply air fan
Exhaust air fan
Outdoor air filter
Extract air filter
Air dampers
Electric heater
Water heater
Water cooler
DX unit
Recirculation
Humidity control unit
Heat pump
Additional zone 1
Additional zone 2
CF defrost module
Rotary
None
STRUCTURE
Stage 1
Stage 2
Stage 3
Stage 4
Stage 5
Stage 6
Min. switching delay between heating/cooling
Water
Zone1
Zone2
DX
Electric
Heat pump
20
min
HEATING/COOLING SEQUENCE
Enable
Setpoint
22.0
°C
120
8
Kp
Ki
Independent
2ND ADDITIONAL ZONE CONTROL (ZN2)
Enable
Setpoint
20.0
°C
120
8
Kp
Ki
Independent
1ST ADDITIONAL ZONE CONTROL (ZN1)
Heat exchanger
Supply air fan
Exhaust air fan
Outdoor air filter
Extract air filter
Air dampers
Electric heater
Water heater
Water cooler
DX unit
Recirculation
Humidity control unit
Heat pump
Additional zone 1
Additional zone 2
CF defrost module
Rotary
None
STRUCTURE
Stage 1
Stage 2
Stage 3
Stage 4
Stage 5
Stage 6
Min. switching delay between heating/cooling
Water
Zone1
Zone2
DX
Electric
Heat pump
20
min
HEATING/COOLING SEQUENCE
Enable
Setpoint
22.0
°C
120
8
Kp
Ki
Independent
2ND ADDITIONAL ZONE CONTROL (ZN2)