30
UAB KOMFOVENT we reserve the right to make changes without prior notice
RHP STANDARD_21-04
EN
7. FILTERS
Air filters are intended for removing dust, bacteria and other fine particles from the supplied and extracted air. RHP
Standard air handling units use compact filters. Filters are made of synthetic fabric and can have different filtration classes
1
,
i.e., intended for removing particles of different sizes. In general, supply air flow is equipped with better filtering class filters
than extracted air since the cleaned outdoor air is supplied to the premises.
The contamination of the filters is monitored by pressure switches installed inside the unit and set to a certain differential
pressure, based on the type of filter used. If filters of other manufacturer or different filtration class is used, the range of the
pressure switches must be set correctly after their replacement. The pressure switches are set by removing the top cover and
turning the knob to the necessary limit of differential pressure. After the filter becomes dirty and the differential pressure
value is reached, a message will be displayed on the control panel or computer screen.
Fig. 24.
Pressure switch
Filters
Unit
Filter type
Supply
Exhaust
Class
BxHxL, mm
Class
BxHxL, mm
RHP
400 V
Compact
ePM1 55% (F7)
462x200x46
ePM10 50% (M5)
2
462x200x46
600 U
Compact
ePM1 55% (F7)
500x280x46
ePM10 50% (M5)
2
500x280x46
800 U
Compact
ePM1 55% (F7)
750x400x46
ePM10 50% (M5)
2
750x400x46
1300 U
Compact
ePM1 55% (F7)
750x400x46
ePM10 50% (M5)
2
750x400x46
1500 U
Compact
ePM1 55% (F7)
750x400x46
ePM10 50% (M5)
2
750x400x46
1
Depends on the order.
2
Class ePM1 55% (F7) is available on request.