Komaes KC3 Скачать руководство пользователя страница 9

           

KC3 PV Charge Controller Instruction Manual 

 

 

9

7)  No.7 is to set the voltage when lighting control is on or off. 

This setting is for KC3 to check grade of the sunlight under Lighting Mode. 

8)  No.8 is to set the delay time when solar modules reach the opening voltage under Lighting 

Mode. 

Note: 

The data won’t be saved if the set one exceeds to require one, KC3 will still run according 

to the previous setting 

 

 
 
 
 
 

 

Diagram 6      First roll (page) shown on LCD

 

 
 
 
                                                           
 

 

Diagram 7      Second roll (page) shown on LCD

 

 

 

Buttons Operations 

LCD Light turns on when Buttons Operations, turns off 10 seconds after Buttons Operations. 

LCD Light keeps on under setting status, turns off 5 seconds after back to normal status. 

4 buttons on KC3: “setting button”       “next”     “up/increase”    “down/reduce”  

 “setting button”     

Under normal status (when LCD shows the working status), press and hold 5 seconds setting 

button to enter the setting status. 

 

Under setting status, cursor flashes on where data needs adjusted, the position of cursor is   

moveable. Press “next” to change the cursor position. Press “up/increase” or “down/reduce” to 

adjust the data where cursor located. 

Press setting button under setting status to save the changed data, the LCD turns over to next 

page. Under setting status, press and hold 5 or 10 seconds of setting button, setting status       

done and turn back to normal status. 

Under normal status, press setting button, LCD turns over to next page to show more working 

1.TIME HH:MM:SS 
2.Ibat(max)

  XX.X 

3.Vbat(max) 

XX.X 

4.Vbat(min)

..

 XX.X 

5.LD_M

..

...

..

PV 

6.LD_T

XX:XX

          XX:XX   

7.PV_ON_V

..

..

X.X 

8.PV_DLY_T

..

XX 

SET 

SET

Содержание KC3

Страница 1: ...ts under different working conditions 1 6 Protection for Batteries Overcharge Overdischarge Low volt Protection for Overload Short Circuit Protection for Reverse Polarity of solar modules Protection f...

Страница 2: ...de of batteries anode of loads cathode of loads Cables Selections according to Current of Loads Selected cables to connect batteries are better shorter thicker to prevent power loss Note KC3 is design...

Страница 3: ...agement 4 Control modes are optional Time shall be reset when controller re connected with power Light Switch Mode Default Mode Under this mode it will activate voltage when Light gets lower to the se...

Страница 4: ...s from Initial Impact Current Efficient PWM begins to charge after a certain charge from the battery and turns to Voltage Limit Charge when goes into the limited line Float Charge begins and keeps its...

Страница 5: ...high charging voltage Overdischarge Low volt Protection Low volt flashes when the batteries voltage is too low it will stop flashing to turn to red if voltage keeps down to the Protection Line and lo...

Страница 6: ...fault mode when electrified Data on LCD under Working Status All the data Working Mode Switch Status Input DC Voltage of Solar Modules Input DC Current of Solar Modules Input Power of Solar Modules Ba...

Страница 7: ...TIME Current Time HH MM SS 00 00 0 0 hour minute second For time checking 2 Ibat max Maximum Battery charging current A XX X 40 0 Set within 5 0A 40 0A 3 Vbat max Allowed Maximum Battery Charging Curr...

Страница 8: ...to pause charging when battery voltage exceeds to this set voltage Re charging starts at a low current when the battery voltage is back to charging voltage 4 No 4 is set to disconnect the load when th...

Страница 9: ...ormal status 4 buttons on KC3 setting button next up increase down reduce setting button Under normal status when LCD shows the working status press and hold 5 seconds setting button to enter the sett...

Страница 10: ...he cursor is located on working mode selection press up increase 4 modes will be shown orderly as PV PV TIME TIME MANUAL Under normal status press down reduce LCD turns over to next page When KC3 unde...

Страница 11: ...to required one Sunlight works but voltage of solar module indicates 0 Check the connection of the modules and make sure right connection for and Over volt turns on no output Check the connection of...

Страница 12: ...when the current 1 5 times more than rate one Low voltage alarm 11 4V 22 8V Overdischarge Low volt protection voltage 10 8V 21 6V Overdischarge Low volt recovery voltage 13 4V 26 8V Over voltage alar...

Отзывы: