-23-
The status indicates the
UPS is in battery mode,
and audible alarm
sounding every 1 beep
in every 4 seconds
Mains power
supply has failed
or input power
and/or frequency
are out of
tolerance
Switching to battery mode
automatically. When audible
alarm sounding every second,
battery is almost empty.
Check input power source and
inform dealer if necessary
Warning code is shown
as 09
Phase and neutral
conductor at input
of UPS system
are reversed
Rotate mains power socket by
180
°
or connect UPS system.
Warning code is shown
as 13, warning tone
once a second
Charger or
Batteries
damaged
Notify dealer!!
Warning code is shown
as 10
Fan is locked or
not working
Check fans and notify dealer!!
Fault code is shown as
07, warning tone once
a second
Overload
Remove loads of UPS output and
restart.
Fault code is shown as
05 or 06 or 08,
permanent warning
tone
UPS fault
Notify dealer!!
Emergency supply
period shorter than
nominal value
Batteries not fully
charged / batteries
defect
Charge the batteries for at least
1 ~ 2 hours and then check
capacity. If the problem still
persists, consult your dealer.
Please have the following information at hand before calling the
After-Sales Service Department:
1. Model number, serial number
2. Date on which the problem occurred
3. Detailed description of the problem
Содержание Black 1K
Страница 1: ...USER MANUAL ONLINE UPS 1 3K 220Vac LCD Uninterruptible Power Systems...
Страница 3: ......
Страница 4: ......
Страница 33: ...29 Appendix Rear panel Back View of 1K 1KS Back View of 2K...
Страница 34: ...30 Back View of 2KS 3K S...
Страница 35: ...31 614 00275 00...