6. Operating mode for all models

6.1 Line mode

The LCD display in Line mode is shown in the following diagram. The
information about the utility power, the battery, the UPS output and
the load could be displayed.

If output overloaded, the load percent is shown and alarm will keep

twice every second. You should get rid of some unnecessary loads

one by one to decrease the loads connected to the UPS less than

90% of its nominal power capacity.

Note: Please follow the following steps to connect the generator

Activate the generator and wait until the operation is stable before

supplying power of the generator to the UPS (be sure that the UPS

is in idle mode). Then turn on the UPS according to the start-up

procedure. After the UPS is turned on, then the loads can be

connected to the UPS one by one.

The power capacity of the AC generator should be at least twice of

the UPS capacity.

The Line mode

Содержание Black 1K

Страница 1: ...USER MANUAL ONLINE UPS 1 3K 220Vac LCD Uninterruptible Power Systems...

Страница 2: ...th all warnings and operating instructions in this manual and on the unit strictly Save this manual properly Do not operate this unit before reading through all safety information and operating instru...

Страница 3: ......

Страница 4: ......

Страница 5: ...ation openings in the UPS s housing Do not connect appliances or items of equipment which would overload the UPS e g laser printers etc to the UPS output Place cables in such a way that no one can ste...

Страница 6: ...with no previous experience 1 3 Maintenance servicing and faults The UPS operates with hazardous voltages Repairs may be carried out only by qualified maintenance personnel Caution risk of electric s...

Страница 7: ...same type of batteries Do not attempt to dispose of batteries by burning them It could cause explosion Do not open or destroy batteries effluent electrolyte can cause injury to the skin and eyes It m...

Страница 8: ...1 Radiated Emission IEC EN 62040 2 Category C1 Harmonic Current IEC EN 61000 3 2 Voltage Fluctuation and Flicker IEC EN 61000 3 3 EMS ESD IEC EN 61000 4 2 Level 4 RS IEC EN 61000 4 3 Level 3 EFT IEC E...

Страница 9: ...5 2 Description of commonly used symbols Some or all of the following symbols may be used in this manual It is advisable to familiarize yourself with them and understand their meaning...

Страница 10: ...eries and powers the inverter On the basis of this DC voltage the inverter generates a sinusoidal AC voltage which permanently supplies the loads Computers and periphery are thus powered entirely by t...

Страница 11: ...verter is off At this moment if Bypass is enabled then the output sockets are supplied with voltage via the bypass if the mains power is available Select Button If the UPS system is No output or Bypas...

Страница 12: ...d be displayed from 0 to 999Vac Indicates the frequency value of input Line voltage which could be displayed from 0 to 99Hz Indicates the input Line current value which could be displayed from 0 to 99...

Страница 13: ...ltage value which could be displayed from 0 to 999Vdc Indicates the battery current value which could be displayed from 0 to 99 9A Indicates the battery capacitance percent and every grid represent 25...

Страница 14: ...be attention UPS setting Information The four value of the output voltage could be selected when the UPS is in No output or Bypass mode and only one of them could be active in the same time Derating 1...

Страница 15: ...ower cord please use a proper socket with protection against electric current and pay attention to the capacity of the socket over 10A for 1K S 2K over 16A for 2KS 3K S 2 UPS Output Connection The out...

Страница 16: ...ter to the outlet sockets of the UPS system following the above diagram 5 3 Battery Charge Fully charge the batteries of the UPS system by leaving the UPS system connected to the mains for 1 2 hours Y...

Страница 17: ...power and breaker is turned on This can be configured by monitoring the LCD panel or firmware 5 5 Test Function Test the function of the UPS system by either pressing the On button or disconnecting t...

Страница 18: ...or connecting the UPS and the other end has a plug for connecting the user battery cabinet 3 Do not connect the UPS to any load yet Then connect the power cord of the UPS to supply utility power to th...

Страница 19: ...e by one to decrease the loads connected to the UPS less than 90 of its nominal power capacity Note Please follow the following steps to connect the generator Activate the generator and wait until the...

Страница 20: ...n the front panel is pressed for more than 1 second again the buzzer will stop beeping in silence mode Press the ON button once again for more than 1 second to resume the alarm function 2 The display...

Страница 21: ...by the load is supplied from the utility power via internal filter 6 4 NO output mode The LCD display in no output mode is shown in the following diagram The information about the utility power the ba...

Страница 22: ...fault etc the corresponding fault code would be shown to indicate the operating mode of the UPS And some warning words could also be shown for example short would be shown when the load or the UPS out...

Страница 23: ...ass Enable in turn And if pressing the Enter button for more than one second at this time the flickering black line would turn to flickerless and the output voltage or frequency or bypass state settin...

Страница 24: ...ut voltage from 220Vac to 230Vac through the LCD panel Setp 1 One flickering black line would appear under 208Vac after pressing the Select button Setp 2 The flickering line would move to 230Vac after...

Страница 25: ...p 3 The line under 230Vac would turn to flickerless after pressing the Enter button and the flickering line would move to the next 240Vac Setp 4 The output voltage would be 230Vac after the UPS is tur...

Страница 26: ...fail warning 09 Inverter fault 06 Fan fail warning 10 Overload fault 07 Bat over warning 11 Over temperature fault 08 Bat weak warning 12 Charger fail warning 13 If the UPS system does not operate cor...

Страница 27: ...once a second Charger or Batteries damaged Notify dealer Warning code is shown as 10 Fan is locked or not working Check fans and notify dealer Fault code is shown as 07 warning tone once a second Over...

Страница 28: ...mbient temperature has been exceeded the batteries must be replaced In this case please contact your dealer 9 2 Storage If the batteries are stored in temperate climatic zones they should be charged e...

Страница 29: ...VA 0 7kW 2kVA 1 4kW 3kVA 2 1kW Voltage 208 220 230 240 1 2 VAC Frequency 50 60 1 0 2 Hz Battery mode Wave form sinusoidal Derating 10 when the output voltage is adjusted to 208VAC BATTERIES Model No 1...

Страница 30: ...t 25 C in minutes Model No 100 Load 50 Load 1K 5 14 2K 9 21 3K 5 15 10 4 Dimensions and weights Model No Dimensions W D H mm Net Weight kg 1K 145 400 220 14 1KS 145 400 220 7 2K 192 460 340 34 5 2KS 1...

Страница 31: ...eries UPS has AS400 card an optional accessory for AS400 communication protocol Please contact your local distributor for details The following is the pin assignment and description of DB 9 connector...

Страница 32: ...control any UPS on the same LAN no matter how far from the UPSs Installation procedure 1 Go to the website http www ups software download com winpower htm 2 Choose the operation system you need and fo...

Страница 33: ...29 Appendix Rear panel Back View of 1K 1KS Back View of 2K...

Страница 34: ...30 Back View of 2KS 3K S...

Страница 35: ...31 614 00275 00...

Отзывы: