Trouble Shooting Guide Continued
HEAD PRESSURE TROUBLESHOOTING
Too high
1 Condenser dirty, clogged or restricted.
1 Replace condenser coil.
2 Air or non-condensable gases in system
2 Recover refrigerant, install filter/dryer, evacuate system and
weigh in proper charge of virgin refrigerant.
3 Fan blade or motor defective
3 Check and replace.
4 Refrigerant overcharged
4 Recover entire refrigerant charge and weigh in proper charge.
Too low
1 Compressor motor or mechanism defective 1 Replace compressor
2 Capillary tube or strainer restricted
2 Replace restricted capillary tube.
3 Low refrigerant charge
3 Locate refrigerant leak, recover refrigerant, repair leak, install
filter/dryer, evacuate system and weigh in proper charge.
4 Evaporator dirty, clogged or restricted
4 Clean evaporator coil.
5 Leak in system
5 Locate refrigerant leak, recover refrigerant, repair leak, install
filter/dryer, evacuate system and weigh in proper charge.
6 Dirty air filter (air flow restricted)
6 Clean filter .
7 Inlet water temperature below 50°F.
7 Adjust regulator valve. Change water supply.
EVAPORATOR TROUBLESHOOTING
Coil freezes
1 Capillary tube or strainer restricted.
1 Replace restricted capillary tube.
2 Fan blade or blower wheel stuck.
2 Check for obstruction and clear. Realign blower within housing
and tighten set screw onto fan motor shaft.
3 Compressor contactor stuck closed.
3 Replace contactor.
4 Return air sensor defective.
4 Replace sensor.
5 Low refrigerant charge.
5 Locate refrigerant leak, recover refrigerant, repair leak, install
filter/dryer, evacuate system and weigh in proper charge.
6 Evaporator dirty, clogged or restricted.
6 Clean evaporator coil.
7 Dirty air filter (air flow restricted).
7 Clean filter.
8 Defective fan motor.
8 Replace fan motor.
CONDENSER TROUBLESHOOTING
Water outlet temperature
exceeds 110°F.
1 Condenser dirty, clogged or restricted.
1 Replace condenser coil.
2 Air or non-condensable gases in system.
2 Recover refrigerant, install filter/dryer, evacuate system and
weigh in proper charge of virgin refrigerant.
3 Refrigerant overcharged
3 Recover entire refrigerant charge and weigh in proper charge.
4 High head-pressure
4 Adjust water regulating valve.