6.4 Fan-Only Mode
If the temperature can’t be controlled by the selected mode and the room ambient temperature is
shown on the display the unit will default to fan only mode.
The readout can only display a temperature of 32 to 99
℉
(0 to 37
℃
.) lf the temperature is out of that
range the display will show LO or HI.
The Timer function works in fan-only mode.
6.5 Dry Mode
In this mode, the air conditioner will operate as a dehumidifier. Because the conditioned space is
closed or sealed, some degree of cooling will continue to occur.
The dry mode temperature can be set from 62 to 86
℉
(17 to 30
℃
.)
The fan speed is automatically set to Low and can’t be controlled.
Sleep function works in dry mode.
6.6 Cooling Mode
The cooling temperature can be set from 62 to 86
℉
(17 to 30
℃
.)
Sleep, Timer and Energy Saver functions work in cooling mode.
The compressor will run when the difference between the set temperature and the actual ambient
room temperature conforms to the chart below:
When TA≤TS (for 1 minute) the compressor turns off.
When T1>TS+2
℉
the compressor turns on.
(TA-Ts)
℉
+2
0
Operation conditon
compressor off with a delay of 1 minute
compressor on