6
TT-1684 3/16
AUTO/INHIBIT SWITCH
Figure 11
Auto/Inhibit Switch Disconnected
10. Disconnect the AUTO/TEST switch and the
bypass time delay pushbutton. See Figure 12.
Figure 12
Disconnect the AUTO/TEST Switch and
Bypass Time Delay Button
11. Remove the AUTO/TEST switch, the BYPASS
TIME
DELAY
pushbutton,
the
ATS
(AUTO/INHIBIT) disconnect switch, and any other
optional switches in this area. See Figure 13.
Keep the ATS (AUTO/INHIBIT) disconnect switch
for reinstallation later in this procedure. Other
switch functions are integrated into the new
Decision-Maker
r
MPAC 1500 controller.
SWITCHES
REMOVED
Figure 13
Switches and Pushbutton Removed