Troubleshooting
8
TP-7088 6/17
KohlerPower.com
Replace AVR
With engine stopped, replace AVR with a
new AVR. Start engine and adjust trimmer
on back of AVR. Test terminal voltage.
Voltage should be between 95-135V. If
voltage is met, original AVR is not adjusted
properly or faulty. Replace as necessary. If
voltage not met, check circuit breakers and
receptacles.
Unit
Item
Generator Spec.
REMARK
PRO6.4/6.4E
PRO9.0/9.0E
Main Winding
Red-Blue
0.27
Ω
±10%
0.13
Ω
±10%
Red-White
(PRO9.0E)
White-Black
0.27
Ω
±10%
0.13
Ω
±10%
Field Winding
Between slip ring
46.6
Ω
±10%
56.4
Ω
±10%
Exciter Winding
Blue-Blue
1.60
Ω
±10%
1.02
Ω
±10%
DC Winding
Orange-Orange
0.10
Ω
±10%
0.08
Ω
±10%
Brush
Length
9mm
Service limit:
5mm
Figure 1 Generator Speci
fi
cations
NOTE: Alternator should not be in contact with panel, AVR, etc during above resistance tests. Alternator should be
tested at room temperature.