1-5. Operation
Do not disconnect the grounding/earthing conductor cable on the UPS or to the building wiring
terminals under any circumstance.
The UPS system features its own, internal current source (batteries). The UPS output sockets or
output terminal blocks may be electrically live even if the UPS system is not connected to the
building mains/live wires. (only for standard models)
In order to fully disconnect the UPS system, first press the “OFF” button and then
disconnect
the mains/live cables.
Ensure that no liquid or other foreign objects can enter into the UPS system.
The UPS can be operated by any individuals with no previous experience.
1-6. Standards
* Safety
IEC/EN 62040-1
* EMI
Conducted Emission...............................:IEC/EN 62040-2
Category C3
Radiated Emission..................................:IEC/EN 62040-2
Category C3
*EMS
ESD........................................................:IEC/EN 61000-4-2
Level 4
RS..........................................................:IEC/EN 61000-4-3
Level 3
EFT.........................................................:IEC/EN 61000-4-4
Level 4
SURGE...................................................:IEC/EN 61000-4-5
Level 4
CS..........................................................:IEC/EN 61000-4-6
Level 3
Power-frequency Magnetic field................:IEC/EN 61000-4-8
Level 4
Low Frequency Signals............................:IEC/EN 61000-2-2
Warning:
This is a product for commercial and industrial application in the
second environment-installation restrictions or additional measures may be
needed to prevent disturbances.