![Kohler PowerWAVE 3000/P1 Скачать руководство пользователя страница 34](http://html.mh-extra.com/html/kohler/powerwave-3000-p1/powerwave-3000-p1_user-manual_1990173034.webp)
31
34
Synchronous trigger signal
failure
None
73
PFC IGBT over-current in C phase None
35
Parallel communication loss
None
74
INV IGBT over-current in A phase None
36
Parallel output current
unbalance
None
75
INV IGBT over-current in B phase None
38
Battery has reached end of life
expectancy
None
76
INV IGBT over-current in C phase None
41
Over temperature
None
77
ISO Over temperature
None
42
DSP communication failure
None
78
LCD&MCU communication failed
None
3-7. Warning Code
Warning
code
Warning event
Warning
code
Warning event
01
Battery unconnected
21
Line situations are different in parallel system
02
IP Neutral loss
22
Bypass situations are different in parallel system
04
IP phase abnormal
33
Locked in bypass after overload 3 times in 30
minutes
05
Bypass phase
abnormal
34
Converter current unbalanced
07
Over charge
3A
Cover of maintain switch is open
08
Low battery
3C
Utility extremely unbalanced
09
Overload
3D
Bypass is unstable
0A
Fan failure
3E
Battery voltage too high
0B
EPO enable
3F
Battery voltage unbalanced
0D
Over temperature
40
Charger short circuited
0E
Charger failure