Operating fluids and maintenance
Operation and Maintenance Manual
Lubricants and operating materials
– BASF GLYSANTIN® G48™ change interval 4 years
The recommended coolant concentration is 40% to 50%.
The coolant can be monitored by means of an coolant analysis and the change
interval can be adjusted if required. Control parameter for the coolant:
Analysis
Standard
Unit Value
Visual appearance
Typical color, clear, normal
smell, like new coolant
pH value
DIN EN ISO
10523:2012-04
6.7 — 9.0
Chloride (ions)
mg/l < 100
Sulfate
mg/l < 100
Bacteria and toxic
constituents
without
Tab. 15: Control parameter
44
© 2018 by Kohler Co. All rights reserved.
KD45V20 33521030001_4_1 en 2018-08-01