Roughing-In - Upper Supply Connection
Measure the distance between the 1/2
″
-14 NPT elbow and the
finished wall surface. The distance must be between 1-3/8
″
(35
mm) and 2-7/8
″
(73 mm).
IMPORTANT!
The shower column connection will not seal
properly if the distance exceeds 2-7/8
″
(73 mm); see below for the
required deep roughing-in kit.
If the distance is between 2-7/8
″
(73 mm) and 4
″
(102 mm):
Order the 1194630 Deep Roughing-in Kit.
If the distance is less than 1-3/8
″
(35 mm):
Order the 1187917
Shallow Roughing-in Kit.
1" (25 mm) Maximum
Wall Surface Offset
1/2"-14 NPT Elbow
1-3/8" (35 mm) –
2-7/8" (73 mm)
1-3/4" (44 mm) Minimum
Escutcheon Clearance
Finished Wall Surface
1213116-2-A
4
Kohler Co.