Appendix A-1

Appendix A Generator Selection and Wattage Requirements

General Wattage Requirements

Consider the total wattage requirements (lights, motors,
appliances) when selecting a generator set, or when
sizing wattage usage in which available space and
construction limit the size of the generator set.

Motor Loads

When figuring generator set capacity requirements for
loads that include electric motors, consider the high
current demanded by the motors during startup. The
inrush or starting current is typically 2 to 3 times higher
than that required when the motor reaches normal
operating speed. Allow a reserve for inrush demands
plus other loads that could be on the line as the electric
motor starts. Use Figure 1 as a guide when selecting
generator set capacity requirements involving motor
loads.

Motor

HP

Starting
(Inrush)

Watts

Running

Watts

1/4

750

330

1/3

1000

400

1/2

1500

600

3/4

2000

750

1

3300

1100

2

4000

2000

3

5000

3000

Figure 1

Motor Requirements

Appliance Loads

Generator sets often furnish AC for appliances such as
TVs, stereos, and electric water heaters. Except for the
resistance-type loads such as the water heater, the
requirements for appliances are usually low. Do not
overlook

such

loads

when

figuring

the

total

requirements. Allow a reserve capacity for anticipated
appliance loads to avoid overloading a generator set.

Lighting Load

To calculate the lighting load, add the wattage of each
generator set-operated lamp. Note that not all of the
lights or lamps are on the generator set AC
circuit—some are DC powered by a 12-volt battery.
Ensure that the calculated total wattage includes only
lights actually on the generator set AC circuit.

Air Conditioners

The starting characteristics of air conditioners vary
greatly—for example, one 12,000 Btu unit has lower
starting requirements than a 10,000 Btu unit of another
variety. When using only one unit, there is usually no
starting problem provided that the lighting and appliance
load is not too high when starting the generator set.

Simultaneous starting of two air conditioning units,
however, can present problems if the generator set
capacity is marginal. Because of the variation in starting
characteristics among air conditioners, this publication
makes no statements regarding multiple-motor starting
capabilities of the generator set covered. Consider
delayed starting or the use of easy-starting devices on
air conditioner units whenever simultaneously starting
more than one motor.

See Figure 2 for typical air conditioner requirements.
The requirements vary among different manufacturers.

Air Conditioner Size (Btu)

7,000

9,000

12,000

16,000

24,000

Voltage

115

230

115

230

115

230

115

230

230

Full load amps

9.3

4.8

9.9

5.0

11.8

6.3

16.3

8.0

11.6

Rated load amps

7.7

4.0

7.0

3.5

8.9

4.8

13.0

6.2

10.2

Locked rotor amps

34.0

20.0

40.0

20.0

50.0

31.0

75.0

36.0

56.0

Starting (inrush) watts

3910

4600

4600

4600

5750

7130

8630

8280

12,900

Running watts

886

920

805

805

1020

1100

1500

1430

2350

Figure 2

Typical Air Conditioner Requirements (60 Hz)

Содержание 7ER

Страница 1: ...Commercial Mobile Generator Sets Model 7ER TP 6034 10 02a Installation...

Страница 2: ......

Страница 3: ...nce Requirements 8 4 3 Exhaust Piping If Used 8 Section 5 Fuel System 9 5 1 Fuel Tank 9 5 2 Fuel Lines 10 5 3 Fuel Pump Lift and Fuel Consumption 10 5 4 Fuel Filters or Strainers 10 Section 6 Electric...

Страница 4: ...TP 6034 10 02 Table of Contents Notes...

Страница 5: ...reconnecting the battery Follow these precautions to prevent the starting of the generator set by the remote start stop switch Battery Sulfuric acid in batteries Can cause severe injury or death Wear...

Страница 6: ...xide is an odorless colorless tasteless nonirritating gas that can cause death if inhaled for even a short time Avoid breathingexhaustfumeswhenworking on or near the generator set Never operate the ge...

Страница 7: ...se severe injury or death Operate the generator set only when all guards and electrical enclosures are in place Moving rotor WARNING Hazardous voltage Backfeed to the utility system can cause severe i...

Страница 8: ...t system can ignite adjacent combustible materials Do not locate electrical wiring fuel lines or combustible materials above the exhaust muffler Exercise caution when parking your vehicle to prevent t...

Страница 9: ...itute with inferior grade hardware Screws and nuts are available in different hardness ratings To indicate hardness American Standard hardware uses a series of markings and metric hardware uses a nume...

Страница 10: ...VI Safety Precautions and Instructions TP 6034 10 02 Notes...

Страница 11: ...following and state and local requirements The installer is responsible for improper installations resulting in penalties from noncompliance with CARB or EPA emission standards 1 2 Generator Set Spec...

Страница 12: ...2 Introduction TP 6034 10 02 Notes...

Страница 13: ...em components See the current generator set specification sheet or Section 7 of this manual for generator set dimensions and weights For angular operating limits consult the operation manual 2 3 Vehic...

Страница 14: ...ADV 6450 E Figure 2 1 Extended Shaft Dimensions Figure 2 2 shows a Kohler mobile generator set mounted to a hydraulic pump The generator set equipped with the extended shaft option can power external...

Страница 15: ...e intake restriction The engine generator performance will be adversely affected if these guidelines are neglected Follow these guidelines to optimize generator set performance Model Normal Intake Res...

Страница 16: ...6 Cooling System TP 6034 10 02 Notes...

Страница 17: ...e seek fresh air immediately and remain active Do not sit lie down or fall asleep Alert others to the possibility of carbon monoxide poisoning Seek medical attention if the condition of affected perso...

Страница 18: ...cent combustible materials 4 3 Exhaust Piping If Used Route the exhaust piping to maintain minimum clearances and to minimize exhaust piping bends Use a tail pipe as short as possible with as few bend...

Страница 19: ...atch fuel when draining thefuel system Wipe up spilled fuel after draining the system 5 1 Fuel Tank Fuel system design Design the generator set gasoline fuel system to operate independently of the veh...

Страница 20: ...1 4 in ID Flexible hose sections If a metal fuel line draws fuel from the fuel tank install a flexible hose section to connect the metal line to the fuel pump The flexible section allows generator set...

Страница 21: ...exhaust system and drippage of fuel oil or grease Allow at least a 51 mm 2 in clearance between the electrical wiring and hot exhaust parts Do not locate the wiring directly below or near the fuel sys...

Страница 22: ...otect the AC load circuit of the generator set against overloading or short circuiting with a circuit breaker s Note For standby service connect output of the generator to a suitably rated transfer sw...

Страница 23: ...in the STOP position 2 Disconnect the power to the battery charger if equipped 3 Remove the battery cables negative lead first Reconnect the negative lead last when reconnecting the battery Follow th...

Страница 24: ...s for the following three reconnection systems using circuit breakers Two pole circuit breaker with a single voltage system example 120 volt 3 wire Attach stator leads marked 2 and 4 to the side of th...

Страница 25: ...ate battery the battery can be installed closer to the generator set and the cable length can be minimized to eliminate voltage drop See Figure 6 2 for the minimum cold cranking amps CCA battery recom...

Страница 26: ...ure gauge if equipped D Water temperature gauge if equipped D Battery voltage D Hourmeter D Start Stop switch including run light Available panels D Start Stop switch with hourmeter D Start Stop switc...

Страница 27: ...Installation Drawing 17 TP 6034 10 02 Section 7 Installation Drawing ADV 6450 E Figure 7 1 Dimension Drawing...

Страница 28: ...TP 6034 10 02 18 Installation Drawing Notes...

Страница 29: ...o not connect the load side terminals of the circuit breaker See Figure 8 1 If the installation requires a 100 120 volt 2 wire system use a single pole circuit breaker See Figure 8 2 When connecting s...

Страница 30: ...tator Leads L0 GRD L2 L1 L0 Neutral Line Side Factory Two Pole Circuit Breaker Ground Load Side 100 120 200 240 Volt 3 Wire 60 Hz 50 Hz L0 L1 100 120 Volt 100 120 Volt L0 L2 100 120 Volt 100 120 Volt...

Страница 31: ...regulator Voltage regulator adjustments are possible without removing the voltage regulator The voltage regulator adjustment procedure applies to the PowerBoost IIIE Figure 8 5 voltage regulator Note...

Страница 32: ...an electrical outlet 4 Start the generator set 5 Rotate the voltage adjustment pot clockwise to increase the voltage counterclockwise to decrease the voltage to the desired output voltage 6 Rotate the...

Страница 33: ...age of each generator set operated lamp Note that not all of the lights or lamps are on the generator set AC circuit some are DC powered by a 12 volt battery Ensure that the calculated total wattage i...

Страница 34: ...oled cyl cylinder D A digital to analog DAC digital to analog converter dB decibel dBA decibel A weighted DC direct current DCR direct current resistance deg degree dept department dia diameter DI EO...

Страница 35: ...al OS oversize overspeed OSHA Occupational Safety and Health Administration OV overvoltage oz ounce p pp page pages PC personal computer PCB printed circuit board pF picofarad PF power factor ph phase...

Страница 36: ......

Страница 37: ......

Страница 38: ......

Страница 39: ......

Страница 40: ...Kohler Wisconsin 53044 Phone 920 565 3381 Fax 920 459 1646 For the nearest sales service outlet in the US and Canada phone 1 800 544 2444 KohlerPowerSystems com Kohler Power Systems Asia Pacific Head...

Отзывы: