TP-6862 6/14
55
Section 8 Reconnection/Adjustments
7
6
8
5
11
10
12
9
15
14
16
13
L2
L3
To Generator
Set
To Shore
Power
To Load
4-Wire, 3-Phase Generator Sets
L0
3
2
4
1
L1
L2
L3
L0
L1
L2
L3
L0
L1
Kraus Naimler/American Solenoid
I-940
Figure 8-2
Marine Manual (Ship-to-Shore) Transfer
Switch, continued
8.1 Twelve-Lead Reconnection
The
reconnection
procedure
details
voltage
reconnections only.
If the generator set requires
frequency changes, adjust the governor and voltage
regulator. See the generator set service manual for
information regarding frequency adjustment.
The following information illustrates the reconnection of
twelve-lead generator sets. In all cases, conform to the
National Electrical Code (NEC).
Reconnect the stator leads of the generator set to
change output phase or voltage. Refer to the following
procedure and connection schematics. Follow all safety
precautions at the front of this manual and in the text
during the reconnection procedure.
NOTICE
Voltage reconnection.
Affix a notice to the generator set after
reconnecting the set to a voltage different from the voltage on
the nameplate. Order voltage reconnection decal 246242
from an authorized service distributor/dealer.
Twelve-Lead Reconnection Procedure
1. Place the generator start/stop switch in the STOP
position.
2. Disconnect generator set engine starting battery,
negative (--) lead first.
3. Disconnect power to battery charger, if equipped.
4. Use Figure 8-3 to determine the generator set
voltage configuration. Note the original voltage
and reconnect the generator set as needed. For
units with current transformers, route leads
through current transformers (CTs) and connect
the leads according to the diagram for the desired
phase and voltage.
Содержание 33-125EFOZCJ
Страница 2: ...TP 6862 6 14 2...
Страница 8: ...TP 6862 6 14 8 Safety Precautions and Instructions Notes...
Страница 10: ...TP 6862 6 14 10 Section 1 Introduction Notes...
Страница 12: ...TP 6862 6 14 12 Section 2 Location and Mounting Notes...
Страница 28: ...TP 6862 6 14 28 Section 5 Fuel System Notes...
Страница 34: ...TP 6862 6 14 34 Section 6 Electrical System Notes...
Страница 52: ...TP 6862 6 14 52 Section 7 Installation Drawings Notes...
Страница 56: ...TP 6862 6 14 56 Section 8 Reconnection Adjustments Figure 8 3 Generator Reconnection ADV 5875F R...
Страница 78: ...TP 6862 6 14 78 Section 9 Paralleling Generator Sets Notes...
Страница 82: ...TP 6862 6 14 82...
Страница 83: ...TP 6862 6 14 83...