background image

TP-6727 10/11

41

Section 5 Controller

5.5 Voltage Adjustments

Hazardous voltage.
Can cause severe injury or death.

Operate the generator set only when
all guards and electrical enclosures
are in place.

Moving parts.

WARNING

Short circuits.

Hazardous voltage/current can cause

severe injury or death.

Short circuits can cause bodily injury

and/or equipment damage

.

Do not contact electrical

connections with tools or jewelry while making adjustments or
repairs. Remove all jewelry before servicing the equipment.

The controller’s adjustment mode allows adjustment of
the output voltage, if necessary.

Have adjustments

performed by an authorized distributor/dealer or service
technician.

Note:

A

digital

voltmeter

is

required

for

these

adjustments.

Use a voltmeter to check the output voltage. If the output
voltage is not within specifications, use the ADC
controller to adjust the output voltage while the
generator set is running. The flowcharts in Figure 5-6
and Figure 5-7 outline the adjustment procedures.

Note:

Be sure to save your settings before exiting the
configuration mode.

Voltage changes are lost if they are not saved before the
generator set shuts down. If the changes are not saved,
the generator set continues to run with the new settings
until it shuts down but then reverts to the previous
settings at the next startup.

Pressing the Select button when SAVE is displayed
returns to the first parameter, voltage adjust (1P).

Voltage Adjustment Procedure

Note:

Refer to the flowcharts in Figure 5-6 and
Figure 5-7

during

the

voltage

adjustment

procedure.

1. With the generator set off, connect a digital

multimeter to the output leads or an electrical outlet
on the load side of the generator set. Set the meter
to measure AC voltage.

2. Start the generator set by moving the generator set

master switch to the RUN position.

3. Use the ADC controller to adjust the voltage

(parameter 1P) until the output voltage reaches the
desired value. See Figure 5-5 for the approximate
change in voltage per step in parameter 1P.

Measured

Voltage, VAC

Voltage Change per Step, VAC

Coarse Adjust

Fine Adjust

85--132

5

0.5

180--251

7

0.7

Figure 5-5

Voltage Adjustment (approximate)

4. Adjust the voltage stability (gain, parameter 2P) to

minimize light flicker.

5. Readjust the voltage, if necessary.

6. Stop the generator set.

Содержание 15REYG

Страница 1: ...Commercial Generator Sets Models 15REYG 30REYG TP 6727 10 11c Installation...

Страница 2: ...y available for future reference Record field installed kit numbers after installing the kits Generator Set Identification Numbers Record the product identification numbers from the generator set name...

Страница 3: ...3 1 8 6 Batteries 14 1 8 7 Battery Chargers 14 1 8 8 Remote Start Connection optional 15 1 8 9 Automatic Transfer Switches 15 Section 2 Open Units 17 2 1 Introduction 17 2 2 Air and Cooling 18 2 2 1 I...

Страница 4: ...ADC 2100 37 5 2 Firmware Version 37 5 3 Controller Automatic Power Down 37 5 4 Controller Configuration 37 5 5 Voltage Adjustments 41 Section 6 Generator Reconnection 45 6 1 Voltage Reconnection 45 6...

Страница 5: ...harger 3 Remove the battery cables negative lead first Reconnect the negative lead last when reconnecting the battery Follow these precautions to prevent starting of the generator set by an automatic...

Страница 6: ...r death Install carbon monoxide detectors on each level of the building Locate the detectors to adequately warn the building s occupants of the presence of carbon monoxide Keep the detectors operation...

Страница 7: ...lectrocution Welding on the generator set Can cause severe electrical equipment damage Before welding on the generator set perform the following steps 1 Remove the battery cables negative lead first 2...

Страница 8: ...vere injury or death Before removing the pressure cap stop the generator set and allow it to cool Then loosen the pressure cap to relieve pressure WARNING Hot engine and exhaust system Can cause sever...

Страница 9: ...y Precautions and Instructions section at the beginning of this manual Keep this manual with the equipment for future reference List of Related Materials Figure 1 identifies related literature availab...

Страница 10: ...dquarters Europe Middle East Africa EMEA Kohler Power Systems 3 rue de Brennus 93200 Saint Denis France Phone 33 1 49 178300 Fax 33 1 49 178301 Asia Pacific Power Systems Asia Pacific Regional Office...

Страница 11: ...erations are especially important The building engineer must determine whether the structure can support the weight of the generator set The location of the generator set must D Support the weight of...

Страница 12: ...ss factors D Pipe length D Other appliances on the same fuel supply D Number of fittings Flexible connections Rigid mount the piping but protect it from vibration Use flexible connections spanning a m...

Страница 13: ...onfiguration Various regulations and site configurations including the National Electrical Code NEC local codes and the type of transfer switch used in the application determine the grounding of the n...

Страница 14: ...16 13 8 120 5 6 7 32 17 0 150 6 4 1 4 22 6 200 7 9 5 16 31 1 275 9 5 3 8 42 4 375 12 7 1 2 56 5 500 14 3 9 16 67 8 600 Note For values of slot width or length not corresponding to those specified sele...

Страница 15: ...tch uses a set of contacts to signal the engine generator to start When the normal source fails and the generator set master switch is in the AUTO position the transfer switch contacts close to start...

Страница 16: ...TP 6727 10 11 16 Section 1 General Notes...

Страница 17: ...ical open unit installation For the protection of the building s occupants install carbon monoxide CO detectors on each level of the building Locate the detectors to adequately warn the building s occ...

Страница 18: ...igure 2 2 When using ductwork and ventilating fans check the exhaust fan capacity in m3 min cfm If using exhaust fans install fan operated louvers with exhaust fans to regulate airflow See Figure 2 5...

Страница 19: ...erheating especially in high ambient air temperatures Use heavy canvas silicone rubber or similar flexible material for the connection between the radiator duct flange and the ductwork to prevent nois...

Страница 20: ...ess on the engine exhaust manifold or turbocharger Never allow the engine manifold or turbocharger to support the silencer or exhausting piping Note Do not bend the flexible section or use it to compe...

Страница 21: ...himbles If the exhaust pipe passes through a wall or roof use a double sleeved exhaust thimble to prevent the transmission of exhaust pipe heat to the combustible material Figure 2 11 shows constructi...

Страница 22: ...r is too small D The exhaust pipe is too long D The exhaust system has too many sharp bends D The exhaust silencer is too small D The exhaust silencer is not the correct design for the application The...

Страница 23: ...12 2 8 equiv ft or 0 86 equiv m Equivalent of straight pipe 3 0 2 8 5 8 equiv straight ft 0 9 0 86 1 76 equiv straight m 6 Determine the total length of straight pipe used in the exhaust system Add t...

Страница 24: ...TP 6727 10 11 24 Section 2 Open Units P Backpressure in Hg per foot kPa per m inches d Pipe Diameter mm Figure 2 13 Backpressure using Pipe Size 4 in 152 m or Less...

Страница 25: ...ons in this manual and observe the decals on the equipment Refer to the diagrams and drawings in Section 7 for dimensions and electrical connections during the installation procedure Read the entire i...

Страница 26: ...jacent walls or obstructions to allow access for maintenance and service See Figure 2 1 for a typical open unit installation Prepare an area for mounting the generator set 1 Clear all combustible mate...

Страница 27: ...still do not clear the protruding component s temporarily remove the component s 3 4 Mount and Ground Generator Set 1 Place the generator set on the concrete mounting pad Secure the generator set wit...

Страница 28: ...end panel or make connections inside the junction box Load Lead and Engine Start Connections 1 Install a 120 VAC receptacle for the generator set battery charger and block heater if equipped Supply p...

Страница 29: ...te the battery chargerfrom explosive fumes WARNING Battery gases Explosion can cause severe injury or death Battery gases can cause an explosion Do not smoke or permit flames or sparks to occur near a...

Страница 30: ...Check that the primary regulator and gas meter have sufficient capacity for the fuel requirements for the generator set plus all other gas fired equipment Have the fuel supplier install a larger gas...

Страница 31: ...e the fuel valves disconnect the lines at the location of the leak clean the fittings and apply fresh pipe sealant Reconnect the lines and recheck for leaks Note After the system installation is compl...

Страница 32: ...em is set up for the type of fuel that will be used See Figure 3 8 for the location of the fuel solenoid valve To change the fuel type change the connection to the fuel solenoid valve as described bel...

Страница 33: ...ay not provide adequate freezing and overheating protection A coolant solution with more than 50 ethylene glycol can cause engine or component damage Do not use alcohol or methanol antifreeze or mix t...

Страница 34: ...output voltage from the generator set If voltage adjustments are required refer to Section 5 5 for instructions to use the ADC 2100 voltage adjustment menu 4 Perform voltage checks as described in the...

Страница 35: ...ctions The following sections detail a few common accessories and their functions The instructions provided with the accessory kit supersede these instructions if different 4 2 Common Fault and Run Re...

Страница 36: ...ptional oil makeup kit available for 30 kW generator sets provides an additional 2 quarts of oil for extended run time Follow the instructions provided with the kit to add oil if necessary and to chec...

Страница 37: ...ations parameter setting Cn00 see Section 5 4 the controller will power down after 48 hours of no activity If the generator set has been started the controller will power down 48 hours after the gener...

Страница 38: ...es between 12 and 24 VDC for the engine starting battery voltage Communications setting Cn This setting allows the user to set the controller for communication with optional meters The factory setting...

Страница 39: ...ype to Ec03 OR Ec06 if necessary See Figure 5 1 U u X X U c 0 1 U u 0 1 3 2 5 0 A d n c Press Now release the Select button or To enter advanced configuration mode Go to Figure 5 3 or To proceed to th...

Страница 40: ...last saved settings when the master switch is moved to the OFF RESET position Figure 5 3 Advanced Configuration Mode engine data input types battery voltage and engine communications To save changes T...

Страница 41: ...ting the configuration mode Voltage changes are lost if they are not saved before the generator set shuts down If the changes are not saved the generator set continues to run with the new settings unt...

Страница 42: ...or Hold Wait about 5 seconds until the display changes from runtime hours to the program version number Press the down arrow key and then the up arrow key 3 times to enter the adjustment mode This is...

Страница 43: ...en the display says SAVE Press or To return to the first parameter coarse voltage adjustment to check or change settings before saving See Figure 5 6 Yes or no flashes when the up or down arrow is pre...

Страница 44: ...TP 6727 10 11 44 Section 5 Controller Notes...

Страница 45: ...e injury or death Before working on the generator set or connected equipment disable the generator set as follows 1 Move the generator set master switch to the OFF position 2 Disconnect the power to t...

Страница 46: ...rs and other accessories match the selected line voltage Reconnection Procedure 1 Place the generator set master switch in the OFF RESET position 2 Disconnect engine starting battery negative lead fir...

Страница 47: ...47 Section 6 Generator Reconnection ADV 5875B J Note The current transformers CTs shown are not used on generator sets equipped with the Advanced Digital Control ADC 2100 Figure 6 2 12 Lead Generator...

Страница 48: ...TP 6727 10 11 48 Section 6 Generator Reconnection Notes...

Страница 49: ...ng diagrams refer to TP 6719 Wiring Diagram Manual Dimension Drawing Description Drawing Number Page Generator Set without Customer Connection Box Sheet 1 ADV 7692 50 Sheet 2 ADV 7692 51 Generator Set...

Страница 50: ...TP 6727 10 11 50 Section 7 Dimension Drawings Note Dimensions are in mm in Figure 7 2 Dimension Drawing ADV 7692 Sheet 1 Generator Set...

Страница 51: ...TP 6727 10 11 51 Section 7 Dimension Drawings Note Dimensions are in mm in Figure 7 3 Dimension Drawing ADV 7692 Sheet 2 Generator Set...

Страница 52: ...TP 6727 10 11 52 Section 7 Dimension Drawings Note Dimensions are in mm in 05 14 2010 Controlled Document Figure 7 4 Dimension Drawing ADV 7693 Accessories...

Страница 53: ...TP 6727 10 11 53 Section 7 Dimension Drawings ADV 7695 Note Dimensions are in mm in Figure 7 5 Dimension Drawing ADV 7695 Sheet 1 Weather Enclosure and Weather Enclosure with Sound Kit...

Страница 54: ...TP 6727 10 11 54 Section 7 Dimension Drawings Note Dimensions are in mm in Figure 7 6 Dimension Drawing ADV 7695 Sheet 2 Sound Enclosure...

Страница 55: ...TP 6727 10 11 55 Section 7 Dimension Drawings Note Dimensions are in mm in Figure 7 7 Dimension Drawing ADV 7695 Sheet 3 Dropover Sound Enclosure...

Страница 56: ...TP 6727 10 11 56 Section 7 Dimension Drawings Note Dimensions are in mm in Figure 7 8 ADV 7695 Sheet 4 150 MPH High Wind Mounting Details...

Страница 57: ...TP 6727 10 11 57 Section 7 Dimension Drawings Note Dimensions are in mm in Figure 7 9 Dimension Drawing ADV 8159 Sheet 1 Generator Set with Customer Connection Box...

Страница 58: ...TP 6727 10 11 58 Section 7 Dimension Drawings Note Dimensions are in mm in Figure 7 10 Dimension Drawing ADV 8159 Sheet 2 Generator Set with Customer Connection Box...

Страница 59: ...ies cu in cubic inch cw clockwise CWC city water cooled cyl cylinder D A digital to analog DAC digital to analog converter dB decibel dB A decibel A weighted DC direct current DCR direct current resis...

Страница 60: ...C Phillipsr head Crimptiter screw PHH Phillipsr hex head screw PHM pan head machine screw PLC programmable logic control PMG permanent magnet generator pot potentiometer potential ppm parts per millio...

Страница 61: ...s Physical Properties Characteristic LP Gas Butane Propane Formula C4H10 C3H8 Boiling point C F 0 32 42 44 Specific gravity of gas air 1 00 2 00 1 53 Specific gravity of liquid water 1 00 0 58 0 51 Bt...

Страница 62: ...1 41 kg cm2 20 psi 0 kg cm2 0 psi 40 C 40 F 28 C 20 F 18 C 0 F 7 C 20 F 4 C 40 F 15 C 60 F 27 C 80 F 38 C 100 F Figure 1 Heat Rejection to Ambient Air Temperature C F Approximate Pressure PSIG Propan...

Страница 63: ...141000 30 45000 66000 85000 107000 118000 20 36000 51000 68000 83000 92000 10 28000 38000 49000 60000 66000 Figure 1 Vaporization Rate 100 lb Propane Cylinders Approximate Determining Propane Vaporiz...

Страница 64: ...TP 6727 10 11 64 Notes...

Страница 65: ...TP 6727 10 11 65 Notes...

Страница 66: ...TP 6727 10 11 66 Notes...

Страница 67: ......

Страница 68: ...he nearest sales service outlet in the US and Canada phone 1 800 544 2444 KohlerPower com Kohler Power Systems Asia Pacific Headquarters 7 Jurong Pier Road Singapore 619159 Phone 65 6264 6422 Fax 65 6...

Отзывы: