TP-6727 10/11
37
Section 5 Controller
Section 5 Controller
5.1 Advanced Digital Control
(ADC 2100)
The generator sets use the Advanced Digital Control
(ADC 2100). The ADC 2100 uses password-protected
menus for generator output adjustments and controller
configuration.
This section contains instructions for using the
controller’s password-protected menus to check and
adjust the generator output and controller configuration.
The controller configuration and generator set output
are factory-set and should not require field adjustment
under normal circumstances. Check and adjust the
configuration and/or output in the following cases:
D
Check and adjust the controller configuration and
generator output after generator set reconnection to a
different voltage.
D
Check
the
controller
configuration
when
troubleshooting generator set problems.
D
Check and adjust the generator set output after
installation if the voltage requires adjustment for a
particular application.
5.2 Firmware Version
These models require ADC 2100 firmware version 3.25
or later. The Firmware version number is displayed as
you enter the controller configuration mode.
See
Figure 5-2.
5.3 Controller Automatic Power
Down
With the generator set master switch in the AUTO
position, there are three possible controller power
modes,
which
are
selected
by
setting
the
communications parameter as described below. Also
see Section 5.4.
48-hour power down.
If the communications
parameter is set to Cn00, the controller will power down
after 48 hours of no activity. If the generator set has
been started, the controller will power down 48 hours
after the generator stops. A remote start signal from a
transfer switch or remote switch connected to engine
start leads 3 and 4 will signal the controller to power up
and the generator set to start.
If the ADC 2100 is not configured for a CAN gauge
(communications
parameter
setting
Cn00,
see
Section 5.4), the controller will power down after 48
hours of no activity.
If the generator set has been
started, the controller will power down 48 hours after the
generator stops. A remote start signal from a transfer
switch or remote switch connected to engine start leads
3 and 4 will signal the controller to power up and the
generator set to start.
If the ADC 2100 is configured for a CAN gauge
(communications parameter setting Cn01 or Cn02), the
controller will not power down. The ADC 2100 remains
powered at all times to allow remote start commands
from the remote CAN gauge.
Continuous power mode.
If the ADC 2100 controller
is configured for a CAN gauge by setting the
communications parameter to Cn01, the controller will
not power down.
The ADC 2100 controller remains
powered at all times to allow remote start commands
from the remote CAN gauge.
1-hour power down.
Setting the communications
parameter to Cn06 will cause the controller to power
down after 1 hour of no activity. In this mode, a remote
start/stop switch or the generator set master switch
must be used to activate the controller after it has
powered down.
Controller application code version
1.21 or higher is required for the 1-hour power down
option.
5.4 Controller Configuration
The controller configuration for each generator model is
set at the factory and should not normally require
changes. The controller’s configuration mode allows
adjustment of the system parameters listed in this
section. If necessary, use the instructions in this section
to check the configuration after installation and change
the parameters to match the settings shown in
Figure 5-1.
The controller will automatically exit the configuration
mode without saving any changes after about 1 minute
if no buttons are pressed.
Start the configuration
procedure over again from the beginning if the controller
exits the configuration mode before the settings have
been saved.
Follow the instructions in Figure 5-2 to enter the
configuration mode while the engine is
not
running and
Содержание 15REYG
Страница 1: ...Commercial Generator Sets Models 15REYG 30REYG TP 6727 10 11c Installation...
Страница 16: ...TP 6727 10 11 16 Section 1 General Notes...
Страница 44: ...TP 6727 10 11 44 Section 5 Controller Notes...
Страница 48: ...TP 6727 10 11 48 Section 6 Generator Reconnection Notes...
Страница 64: ...TP 6727 10 11 64 Notes...
Страница 65: ...TP 6727 10 11 65 Notes...
Страница 66: ...TP 6727 10 11 66 Notes...
Страница 67: ......