Section 5 Controller

Section 5 Controller

5.1 Advanced Digital Control

(ADC 2100)

The generator sets use the Advanced Digital Control
(ADC 2100). The ADC 2100 uses password-protected
menus for generator output adjustments and controller
configuration.

This section contains instructions for using the
controller’s password-protected menus to check and
adjust the generator output and controller configuration.
The controller configuration and generator set output
are factory-set and should not require field adjustment
under normal circumstances. Check and adjust the
configuration and/or output in the following cases:

D

Check and adjust the controller configuration and

generator output after generator set reconnection to a
different voltage.

D

Check

the

controller

configuration

when

troubleshooting generator set problems.

D

Check and adjust the generator set output after

installation if the voltage requires adjustment for a
particular application.

5.2 Firmware Version

These models require ADC 2100 firmware version 3.25
or later. The Firmware version number is displayed as
you enter the controller configuration mode.

See

Figure 5-2.

5.3 Controller Automatic Power

Down

With the generator set master switch in the AUTO
position, there are three possible controller power
modes,

which

are

selected

by

setting

the

communications parameter as described below. Also
see Section 5.4.

48-hour power down.

If the communications

parameter is set to Cn00, the controller will power down
after 48 hours of no activity. If the generator set has
been started, the controller will power down 48 hours
after the generator stops. A remote start signal from a
transfer switch or remote switch connected to engine
start leads 3 and 4 will signal the controller to power up
and the generator set to start.

If the ADC 2100 is not configured for a CAN gauge
(communications

parameter

setting

Cn00,

see

Section 5.4), the controller will power down after 48
hours of no activity.

If the generator set has been

started, the controller will power down 48 hours after the
generator stops. A remote start signal from a transfer
switch or remote switch connected to engine start leads
3 and 4 will signal the controller to power up and the
generator set to start.

If the ADC 2100 is configured for a CAN gauge
(communications parameter setting Cn01 or Cn02), the
controller will not power down. The ADC 2100 remains
powered at all times to allow remote start commands
from the remote CAN gauge.

Continuous power mode.

If the ADC 2100 controller

is configured for a CAN gauge by setting the
communications parameter to Cn01, the controller will
not power down.

The ADC 2100 controller remains

powered at all times to allow remote start commands
from the remote CAN gauge.

1-hour power down.

Setting the communications

parameter to Cn06 will cause the controller to power
down after 1 hour of no activity. In this mode, a remote
start/stop switch or the generator set master switch
must be used to activate the controller after it has
powered down.

Controller application code version

1.21 or higher is required for the 1-hour power down
option.

5.4 Controller Configuration

The controller configuration for each generator model is
set at the factory and should not normally require
changes. The controller’s configuration mode allows
adjustment of the system parameters listed in this
section. If necessary, use the instructions in this section
to check the configuration after installation and change
the parameters to match the settings shown in
Figure 5-1.

The controller will automatically exit the configuration
mode without saving any changes after about 1 minute
if no buttons are pressed.

Start the configuration

procedure over again from the beginning if the controller
exits the configuration mode before the settings have
been saved.

Follow the instructions in Figure 5-2 to enter the
configuration mode while the engine is

not

running and

Содержание 15REYG

Страница 1: ...Commercial Generator Sets Models 15REYG 30REYG TP 6727 10 11c Installation...

Страница 2: ...y available for future reference Record field installed kit numbers after installing the kits Generator Set Identification Numbers Record the product identification numbers from the generator set name...

Страница 3: ...3 1 8 6 Batteries 14 1 8 7 Battery Chargers 14 1 8 8 Remote Start Connection optional 15 1 8 9 Automatic Transfer Switches 15 Section 2 Open Units 17 2 1 Introduction 17 2 2 Air and Cooling 18 2 2 1 I...

Страница 4: ...ADC 2100 37 5 2 Firmware Version 37 5 3 Controller Automatic Power Down 37 5 4 Controller Configuration 37 5 5 Voltage Adjustments 41 Section 6 Generator Reconnection 45 6 1 Voltage Reconnection 45 6...

Страница 5: ...harger 3 Remove the battery cables negative lead first Reconnect the negative lead last when reconnecting the battery Follow these precautions to prevent starting of the generator set by an automatic...

Страница 6: ...r death Install carbon monoxide detectors on each level of the building Locate the detectors to adequately warn the building s occupants of the presence of carbon monoxide Keep the detectors operation...

Страница 7: ...lectrocution Welding on the generator set Can cause severe electrical equipment damage Before welding on the generator set perform the following steps 1 Remove the battery cables negative lead first 2...

Страница 8: ...vere injury or death Before removing the pressure cap stop the generator set and allow it to cool Then loosen the pressure cap to relieve pressure WARNING Hot engine and exhaust system Can cause sever...

Страница 9: ...y Precautions and Instructions section at the beginning of this manual Keep this manual with the equipment for future reference List of Related Materials Figure 1 identifies related literature availab...

Страница 10: ...dquarters Europe Middle East Africa EMEA Kohler Power Systems 3 rue de Brennus 93200 Saint Denis France Phone 33 1 49 178300 Fax 33 1 49 178301 Asia Pacific Power Systems Asia Pacific Regional Office...

Страница 11: ...erations are especially important The building engineer must determine whether the structure can support the weight of the generator set The location of the generator set must D Support the weight of...

Страница 12: ...ss factors D Pipe length D Other appliances on the same fuel supply D Number of fittings Flexible connections Rigid mount the piping but protect it from vibration Use flexible connections spanning a m...

Страница 13: ...onfiguration Various regulations and site configurations including the National Electrical Code NEC local codes and the type of transfer switch used in the application determine the grounding of the n...

Страница 14: ...16 13 8 120 5 6 7 32 17 0 150 6 4 1 4 22 6 200 7 9 5 16 31 1 275 9 5 3 8 42 4 375 12 7 1 2 56 5 500 14 3 9 16 67 8 600 Note For values of slot width or length not corresponding to those specified sele...

Страница 15: ...tch uses a set of contacts to signal the engine generator to start When the normal source fails and the generator set master switch is in the AUTO position the transfer switch contacts close to start...

Страница 16: ...TP 6727 10 11 16 Section 1 General Notes...

Страница 17: ...ical open unit installation For the protection of the building s occupants install carbon monoxide CO detectors on each level of the building Locate the detectors to adequately warn the building s occ...

Страница 18: ...igure 2 2 When using ductwork and ventilating fans check the exhaust fan capacity in m3 min cfm If using exhaust fans install fan operated louvers with exhaust fans to regulate airflow See Figure 2 5...

Страница 19: ...erheating especially in high ambient air temperatures Use heavy canvas silicone rubber or similar flexible material for the connection between the radiator duct flange and the ductwork to prevent nois...

Страница 20: ...ess on the engine exhaust manifold or turbocharger Never allow the engine manifold or turbocharger to support the silencer or exhausting piping Note Do not bend the flexible section or use it to compe...

Страница 21: ...himbles If the exhaust pipe passes through a wall or roof use a double sleeved exhaust thimble to prevent the transmission of exhaust pipe heat to the combustible material Figure 2 11 shows constructi...

Страница 22: ...r is too small D The exhaust pipe is too long D The exhaust system has too many sharp bends D The exhaust silencer is too small D The exhaust silencer is not the correct design for the application The...

Страница 23: ...12 2 8 equiv ft or 0 86 equiv m Equivalent of straight pipe 3 0 2 8 5 8 equiv straight ft 0 9 0 86 1 76 equiv straight m 6 Determine the total length of straight pipe used in the exhaust system Add t...

Страница 24: ...TP 6727 10 11 24 Section 2 Open Units P Backpressure in Hg per foot kPa per m inches d Pipe Diameter mm Figure 2 13 Backpressure using Pipe Size 4 in 152 m or Less...

Страница 25: ...ons in this manual and observe the decals on the equipment Refer to the diagrams and drawings in Section 7 for dimensions and electrical connections during the installation procedure Read the entire i...

Страница 26: ...jacent walls or obstructions to allow access for maintenance and service See Figure 2 1 for a typical open unit installation Prepare an area for mounting the generator set 1 Clear all combustible mate...

Страница 27: ...still do not clear the protruding component s temporarily remove the component s 3 4 Mount and Ground Generator Set 1 Place the generator set on the concrete mounting pad Secure the generator set wit...

Страница 28: ...end panel or make connections inside the junction box Load Lead and Engine Start Connections 1 Install a 120 VAC receptacle for the generator set battery charger and block heater if equipped Supply p...

Страница 29: ...te the battery chargerfrom explosive fumes WARNING Battery gases Explosion can cause severe injury or death Battery gases can cause an explosion Do not smoke or permit flames or sparks to occur near a...

Страница 30: ...Check that the primary regulator and gas meter have sufficient capacity for the fuel requirements for the generator set plus all other gas fired equipment Have the fuel supplier install a larger gas...

Страница 31: ...e the fuel valves disconnect the lines at the location of the leak clean the fittings and apply fresh pipe sealant Reconnect the lines and recheck for leaks Note After the system installation is compl...

Страница 32: ...em is set up for the type of fuel that will be used See Figure 3 8 for the location of the fuel solenoid valve To change the fuel type change the connection to the fuel solenoid valve as described bel...

Страница 33: ...ay not provide adequate freezing and overheating protection A coolant solution with more than 50 ethylene glycol can cause engine or component damage Do not use alcohol or methanol antifreeze or mix t...

Страница 34: ...output voltage from the generator set If voltage adjustments are required refer to Section 5 5 for instructions to use the ADC 2100 voltage adjustment menu 4 Perform voltage checks as described in the...

Страница 35: ...ctions The following sections detail a few common accessories and their functions The instructions provided with the accessory kit supersede these instructions if different 4 2 Common Fault and Run Re...

Страница 36: ...ptional oil makeup kit available for 30 kW generator sets provides an additional 2 quarts of oil for extended run time Follow the instructions provided with the kit to add oil if necessary and to chec...

Страница 37: ...ations parameter setting Cn00 see Section 5 4 the controller will power down after 48 hours of no activity If the generator set has been started the controller will power down 48 hours after the gener...

Страница 38: ...es between 12 and 24 VDC for the engine starting battery voltage Communications setting Cn This setting allows the user to set the controller for communication with optional meters The factory setting...

Страница 39: ...ype to Ec03 OR Ec06 if necessary See Figure 5 1 U u X X U c 0 1 U u 0 1 3 2 5 0 A d n c Press Now release the Select button or To enter advanced configuration mode Go to Figure 5 3 or To proceed to th...

Страница 40: ...last saved settings when the master switch is moved to the OFF RESET position Figure 5 3 Advanced Configuration Mode engine data input types battery voltage and engine communications To save changes T...

Страница 41: ...ting the configuration mode Voltage changes are lost if they are not saved before the generator set shuts down If the changes are not saved the generator set continues to run with the new settings unt...

Страница 42: ...or Hold Wait about 5 seconds until the display changes from runtime hours to the program version number Press the down arrow key and then the up arrow key 3 times to enter the adjustment mode This is...

Страница 43: ...en the display says SAVE Press or To return to the first parameter coarse voltage adjustment to check or change settings before saving See Figure 5 6 Yes or no flashes when the up or down arrow is pre...

Страница 44: ...TP 6727 10 11 44 Section 5 Controller Notes...

Страница 45: ...e injury or death Before working on the generator set or connected equipment disable the generator set as follows 1 Move the generator set master switch to the OFF position 2 Disconnect the power to t...

Страница 46: ...rs and other accessories match the selected line voltage Reconnection Procedure 1 Place the generator set master switch in the OFF RESET position 2 Disconnect engine starting battery negative lead fir...

Страница 47: ...47 Section 6 Generator Reconnection ADV 5875B J Note The current transformers CTs shown are not used on generator sets equipped with the Advanced Digital Control ADC 2100 Figure 6 2 12 Lead Generator...

Страница 48: ...TP 6727 10 11 48 Section 6 Generator Reconnection Notes...

Страница 49: ...ng diagrams refer to TP 6719 Wiring Diagram Manual Dimension Drawing Description Drawing Number Page Generator Set without Customer Connection Box Sheet 1 ADV 7692 50 Sheet 2 ADV 7692 51 Generator Set...

Страница 50: ...TP 6727 10 11 50 Section 7 Dimension Drawings Note Dimensions are in mm in Figure 7 2 Dimension Drawing ADV 7692 Sheet 1 Generator Set...

Страница 51: ...TP 6727 10 11 51 Section 7 Dimension Drawings Note Dimensions are in mm in Figure 7 3 Dimension Drawing ADV 7692 Sheet 2 Generator Set...

Страница 52: ...TP 6727 10 11 52 Section 7 Dimension Drawings Note Dimensions are in mm in 05 14 2010 Controlled Document Figure 7 4 Dimension Drawing ADV 7693 Accessories...

Страница 53: ...TP 6727 10 11 53 Section 7 Dimension Drawings ADV 7695 Note Dimensions are in mm in Figure 7 5 Dimension Drawing ADV 7695 Sheet 1 Weather Enclosure and Weather Enclosure with Sound Kit...

Страница 54: ...TP 6727 10 11 54 Section 7 Dimension Drawings Note Dimensions are in mm in Figure 7 6 Dimension Drawing ADV 7695 Sheet 2 Sound Enclosure...

Страница 55: ...TP 6727 10 11 55 Section 7 Dimension Drawings Note Dimensions are in mm in Figure 7 7 Dimension Drawing ADV 7695 Sheet 3 Dropover Sound Enclosure...

Страница 56: ...TP 6727 10 11 56 Section 7 Dimension Drawings Note Dimensions are in mm in Figure 7 8 ADV 7695 Sheet 4 150 MPH High Wind Mounting Details...

Страница 57: ...TP 6727 10 11 57 Section 7 Dimension Drawings Note Dimensions are in mm in Figure 7 9 Dimension Drawing ADV 8159 Sheet 1 Generator Set with Customer Connection Box...

Страница 58: ...TP 6727 10 11 58 Section 7 Dimension Drawings Note Dimensions are in mm in Figure 7 10 Dimension Drawing ADV 8159 Sheet 2 Generator Set with Customer Connection Box...

Страница 59: ...ies cu in cubic inch cw clockwise CWC city water cooled cyl cylinder D A digital to analog DAC digital to analog converter dB decibel dB A decibel A weighted DC direct current DCR direct current resis...

Страница 60: ...C Phillipsr head Crimptiter screw PHH Phillipsr hex head screw PHM pan head machine screw PLC programmable logic control PMG permanent magnet generator pot potentiometer potential ppm parts per millio...

Страница 61: ...s Physical Properties Characteristic LP Gas Butane Propane Formula C4H10 C3H8 Boiling point C F 0 32 42 44 Specific gravity of gas air 1 00 2 00 1 53 Specific gravity of liquid water 1 00 0 58 0 51 Bt...

Страница 62: ...1 41 kg cm2 20 psi 0 kg cm2 0 psi 40 C 40 F 28 C 20 F 18 C 0 F 7 C 20 F 4 C 40 F 15 C 60 F 27 C 80 F 38 C 100 F Figure 1 Heat Rejection to Ambient Air Temperature C F Approximate Pressure PSIG Propan...

Страница 63: ...141000 30 45000 66000 85000 107000 118000 20 36000 51000 68000 83000 92000 10 28000 38000 49000 60000 66000 Figure 1 Vaporization Rate 100 lb Propane Cylinders Approximate Determining Propane Vaporiz...