SPECIFICATIONS

Pressures and Flow Rates

Note!

 For optimum performance, dynamic supply pressures should be nominally 

equal.

Recommended Minimum Dynamic Supply Pressure: 

0.15 bar.

Recommended Maximum Dynamic Supply Pressure: 

5 bar.

Maximum Static Pressure: 

10 bar.

Recommended Minimum Flow Rate: 

3 L/min at mid-blend with equal dynamic 

supply pressures.

Recommended Maximum Flow Rate: 

35 L/min at mid-blend (which equates to 

maximum pressure loss of 1.8 bar).

Temperatures

Optimum performance is obtained when temperature differentials of 20°C or more 

exist between blend and either supply. Blend control accuracy will begin to diminish 

at temperature differentials below 12°C.

Blend Temperature Range: 

between ambient cold and approximately 60°C, 

according to hot water supply temperature.

Thermostatic Control Range: 

approximately 25-60°C.

Optimum Thermostatic Control Range: 

30-50°C.

Recommended Minimum Cold Water Temperature: 

1°C.

Recommended Maximum Hot Water Supply Temperature: 

85°C.

Connections

Inlets and Outlet: 1/2” BSP external union or 15 mm compression.

Pressure Loss (bar)

Flow Rate (L/Min)

0.5

1.0

1.5

2.0

0

0

10

20

30

40

50

Содержание 1190330-NA

Страница 1: ...TOMER AND MUST BE RETAINED WITH THE PRODUCT FOR MAINTENANCE AND OPERATIONAL PURPOSES Installation and User Guide Built In Shower Valve MODEL NUMBERS Important Please quote the above model number s whe...

Страница 2: ...res and Flow Rates 6 Dimensions 7 Installation 8 Suitable Plumbing Systems 8 General 8 Reversing the Outlet Position 10 Installation Procedure 11 Operation 15 Commissioning 16 Maximum Temperature Sett...

Страница 3: ...ith these instructions and must be conducted by designated qualified and competent personnel 4 Pass on this guide in the event of change of ownership of the installation site 5 Follow all warnings cau...

Страница 4: ...ppliance to thaw and check for leaks before using 17 Insulate any pipework that could be exposed to freezing conditions 18 The water supplies to this product must be isolated if the product is not to...

Страница 5: ...5 1095640 W2 B PACK CONTENTS Or q 1 x Mixer Valve Single Sequential Temperature Only q 1 x Building in Shroud q 1 x Adapter Pack q 3 x Screws q 3 x Wall Plugs...

Страница 6: ...mperatures Optimum performance is obtained when temperature differentials of 20 C or more exist between blend and either supply Blend control accuracy will begin to diminish at temperature differentia...

Страница 7: ...7 1095640 W2 B DIMENSIONS All dimensions are nominal and in mm 140 16 77 140 53 Single Sequential Temperature Only 16 77 53...

Страница 8: ...se instructions and must be conducted by designated qualified and competent personnel The installation must comply with the Water Supply Regulations 1999 Water Fittings or any particular regulations a...

Страница 9: ...on or if the product is dismantled during installation or servicing then the product must be inspected to ensure that there are no leaks 14 Having completed the installation make sure that the user is...

Страница 10: ...d 2 Remove the outlet blanking plug using a 12 mm hexagonal wrench 3 Screw the outlet adapter complete with O seal into the bottom hole previously blanked and tighten 4 Screw the outlet blanking plug...

Страница 11: ...e side of the mixer This is to prevent the flexible hose from obstructing the shower controls 2 Remove the shroud screw retain for later use and remove the mixer from the building in shroud 3 Determin...

Страница 12: ...ting e g timber noggin to the front of the wall before tiling 7 Make sure that the mixer is level central in the hole and square to the finished wall surface or the control components will not fit cor...

Страница 13: ...nstallations alternative fixings may be required not supplied to fix the mixer to the rear face of the wall cavity or to a timber noggin 11 Make sure that the olives are fitted connect the hot and col...

Страница 14: ...nly The Temperature Adapter must be fitted before the trim kit 19 1 Fit the Spline Adapter to the cartridge 19 2 Fit the retaining screw into the centre of the spline adapter Tighten the screw 19 3 Fi...

Страница 15: ...Turning the control knob anti clockwise will increase the flow and temperature from off through cold to the preset maximum Temperature Only Turning the control knob anti clockwise will increase the t...

Страница 16: ...Adapter until the grubscrew can be seen in the cutout then unscrew the grubscrew approx 2 turns 3 2 Remove the temperature adapter and the adapter ring 3 3 Unscrew and remove the Hub Retaining Screw...

Страница 17: ...17 1095640 W2 B Hub Retaining Screw Temperature Adapter Single Sequential Temperature Only Cartridge Drive Adapter Maximum Temperature Setting Cartridge Adapter Ring Adapter Cutout Grubscrew...

Страница 18: ...tory a Check strainers and inlet outlet fittings for flow restriction b Make sure that the minimum flow rate is sufficient for the supply conditions c Make sure that the dynamic inlet pressures are no...

Страница 19: ...icant types may cause rapid deterioration of seals Cleaning The chrome plated parts should be cleaned using a mild washing up detergent or soap solution rinsed and then wiped dry with a soft cloth War...

Страница 20: ...ing of residual water 4 Continue to unscrew and remove the non return valve assembly Caution Some residual water may be released 5 The non return valve assembly and or strainer screens can be cleaned...

Страница 21: ...pplied 1595 070 Component Pack identified A 1624 102 Screw Pack identified B 1624 109 Seal Pack identified C 408 71 Flat Faced Insert 1624 113 Outlet Adaptor 1624 114 Blanking Plug 1624 110 Filter Non...

Страница 22: ...22 1095640 W2 B NOTES...

Страница 23: ...23 1095640 W2 B NOTES...

Страница 24: ...esolve any material defects by providing replacement parts modules or complete product as we deem appropriate To be free of charge work must be undertaken by Kohler approved personnel To ensure that a...

Отзывы: