background image

Inner Circuit Diagrams

Setting

Nomenclature and functions

Output mode

No.

 Name

 Display 

Shows effective measuring range %, setting details, error indicators.

  Switch output indicators 

Light when switch output is ON (CH1 to CH4).

  UP key ( 

Use to increase a setting value.

  DOWN key ( 

 ) 

Use to decrease a setting value.

  MODE key  ( 

 ) 

Use when configuring settings.

ZL2

1

2

3

4

SW.OUT

Window comparator mode

Display 

OUT1

LCD display

1000

600

400

0F

Response 

differential (fixed)

t

Response 

differential (fixed)

)

)

Effective

setting range

signal

(STABI)

The ON range of each output can be set within the effective 

measuring range (sensor head ON range).

Response differential is fixed (2 digits)

When the controller setting and sensor heat setting positions are as shown below.

OUT1   Threshold value setting   Upper limit: 600   Lower limit: 400

Display when hand is full open: 900

ZL2

ZL2

ZL2

ZL2

Hand full open Holding workpiece Hand fully closed Hand full open

Hysteresis mode

Display 

OUT1

LCD display

CAUTION: When the effective measuring range signal is OFF 

(outside the measuring range), OUT also becomes OFF.

1000

200

400

0F

t

Hand full open Holding workpiece Hand fully closed Hand full open

Effective 

setting range

signal

STABI

The ON position and OFF position each output can be set within the 

effective measuring range (sensor head ON range).

When the controller setting and sensor heat setting positions are as shown below.

OUT1   Threshold value setting   Upper limit: 400   Lower limit: 200

Display when hand is full open: 900

ZL2

ZL2

ZL2

ZL2

 

CAUTION

1.  Incorrect wiring of the sensor head or power/switch cable will damage both the controller and the sensor head. Be sure to double-

check and make sure that wiring is correct before supplying power.

2.  Parameters that are set are recorded into flash memory and retained there. Note that flash memory has a limited service life. The 

guaranteed number of rewrites is 10,000.

Getting ready to configure settings

  Connect the sensor head and power/switch cable to the controller. (Refer to "Attaching and detaching of the sensor head and power/

switch cables" on page 

).

Configuring settings

24 VDC

±10

+

D

Linear magneticsensor controller

Sensor head

Power/switch cable

Note: Note that extending the cable can cause a drop in voltage due to cable resistance.

1

4

2

3

5

6

OV (blue lead)

C_IN (yellow lead)

B_IN (black lead)

A_IN (white lead)

LED (red lead)

+V (brown lead)

Tr

1

Tr

2

Tr

3

Tr

4

Tr

5

Z

D5

Z

D4

Z

D3

Z

D2

Z

D1

3

5

1

6

7

8

4

2

STABI (black lead)

+Vcc (brown lead)

OUT1 (white lead)

OUT2 (red lead)

OUT3 (green lead)

OUT4 (yellow lead)

GND (blue lead)

Analog output (gray lead)

Signal  D  

: Power supply reverse-polarity protection diode

 Z

D1

~ Z

D5

  : Surge voltage absorption zener diode

 Tr

1

~Tr

5

 

: NPN output transistors

Load

Load

Load

Load

Load

Main circuit

Sensor section

Main circuit

YES

Purchase the set of the  

controller and the sensor head

Install direction setting

(SET0)

Equipped cylinder setting

(SET2)

Threshold and switch output mode 

setting (SET1&SET3)

Additional settings as needed

(SET4~9)

Start  

detection

Sensor head  

parameter setting

(SETd)

NO

First specify the cylinder model that is equipped (SET2), and then configure the other settings (as shown below).

You also can use the procedure below to modify settings.

General flow

Note 1:  Always be sure to 

configure the 

equipped cylinder 

model setting. Failure 

to do so creates the 

risk of malfunction.

        2:  Note that initialization 

(SETA, SETB) 

initializes all settings, 

so any settings you 

have configured are 

lost.

Note 2

Note 1

increases 

the value,

 

decreases 

it.

Detection mode

Detection

mode is

Indicated

when LCD 

shows OF or 

OFF.

Button operation

Long press

Install direction  

setting

Configures the install 

direction

Sn-0

Sets the output range of 

each channel.

HI:600 

LO:400

Selects the model of the 

equipped cylinder.

18

Selects the output mode 

of each channel.

CO

Can be used to invert the 

switch output of each channel.

S-0

Changes the display position of 

the sensor head LED indicator.

HI:600

LO:400

Configures the scaling 

setting.

OFS:0

FS:1000

Configures the display 

panel setting.

bL-1

Configures the LCD 

display cycle setting.

dt-1

Adjusts the switch output 

response time of each channel.

FL-0

Performs Initialization 1.

Performs Initialization 2 

(display, output check).

Adjusts the maximum output 

voltage of analog output.

Configures the sensor 

head parameters.

Exits the settings and returns 

to the detection mode

Setting items

LCD display

Description

Initial default

Switch output 

threshold setting

Equipped cylinder 

model setting

Switch output 

mode setting

Switch output 

reverse setting

Sensor head LED indicator 

display range setting

Scaling setting

Display backlight 

color setting

Display refresh 

cycle setting

Adjustment setting

Initialization (except SETC&SETd)

[Press 

△▽□

 at the same time]

Initializes all settings

[Press 

△▽□

 at the same time]

Analog output maximum 

voltage setting

Sensor head 

parameter setting

Exit setting

Press

Detailed 

configuration 

of each 

setting is 

supported.

Содержание ZL2

Страница 1: ...essed into the body Connection is complete when the cover is even with the connector body 6 Double check to make sure that wiring is correct 654321 Sensor head RedBlackWhite Brown 654321 Sensor head Yellow Blue Attaching and detaching of the sensor head and power switch cables To attach the sensor head and the power switch cables position the lock levers as shown in the illustration above and then...

Страница 2: ...ead V brown lead Tr1 Tr2 Tr3 Tr4 Tr5 ZD5 ZD4 ZD3 ZD2 ZD1 3 5 1 6 7 8 4 2 STABI black lead Vcc brown lead OUT1 white lead OUT2 red lead OUT3 green lead OUT4 yellow lead GND blue lead Analog output gray lead Signal D Power supply reverse polarity protection diode ZD1 ZD5 Surge voltage absorption zener diode Tr1 Tr5 NPN output transistors Load Load Load Load Load Main circuit Sensor section Main circ...

Страница 3: ...corresponding to the setting CH turns on Backlight color green Backlight color green Use or key to change the setting values Input value 0 to 1000 Factory setting 400 1 second later Press Press Press ALL when selected moves to the next CH setting If not completed to CH4 1P 1 Point teaching threshold setting 2P 2 Point teaching threshold setting Set the threshold Use or key to change the tolerance ...

Страница 4: ...or key to select the switch output reverse mode from the list below Switch output reverse mode No reverse Factory setting Reverse Press Press Press Press Press Press Press Press Press Press Press Press Press Press Press Press Press Press The set value is displayed for 1 second 1 second later 1 second later 1 second later 1 second later 1 second later Return to Return to Sensor head LED indicator l...

Отзывы: