 CAUTION

1.  

Incorrect wiring of the sensor head or power/switch cable will damage both the controller and the sensor head. Be sure to double-check and make sure that 
wiring is correct before supplying power.

2.  

Parameters that are set are recorded into flash memory and retained there. Note that flash memory has a limited service life. The guaranteed number of 
rewrites is 10,000.

Getting ready to configure settings

  Connect the sensor head and power/switch cable to the controller. (Refer to "Attaching and detaching of the sensor head and power/switch cables" on page 

w

).

Configuring settings

   

Description

Initial default

 

Sets the output range of each chan-
nel.

HI: 60

LO: 40

   

 

Selects the model of the equipped 
cylinder.

10

   

 

Selects the output mode of each 
channel.

CO4

   

 

Can be used to invert the switch 
output of each channel.

S-0

   

 

Changes the display position of the 
sensor head LED indicator. 

HI: 60

LO: 40

   

 

Configures the scaling setting.

OFS: 0

FS: 100

   

 

Configures the display panel set-
ting.

bL-1

   

 

Configures the LCD display cycle 
setting.

dT-1

   

 

Adjusts the switch output response 
time of each channel.

Sd-1

   

 

Performs Initialization 1.

   

 

Performs Initialization 2 (display, 
output check).

   

 

Adjusts the maximum output volt-
age of analog output.

Detection 

mode

Button operation

Press

LCD display

Button operation

Release

LCD display

Press

Does nothing. Returns to detection mode.

Detection 
mode is 
indicated 
when LCD 
shows OF 
or OFF.

Causes 
LCD back-
light to 
brighten.

increases 
the value, 

decreases 

it. 

Detailed 
configura-
tion of 
each set-
ting is 
supported.

r

e

Inner Circuit Diagrams

Setting

Nomenclature and functions

Output mode

No.

 Name 

Description

q

 Display 

Shows effective measuring range %, setting details, error indicators.

w

 

Switch output indicators. 

Light when switch output is ON (CH1 

 CH4).

e

 

UP key (

). 

Use to increase a setting value.

r

 

DOWN key (

). 

Use to decrease a setting value.

t

 

MODE key (

). 

Use when configuring settings.

=

@

;

:

.

ZL1

1

2

3

4

SW.OUT

Window comparator mode

Hysteresis mode

Display (%) 

OUT1

LCD display

100

60
40

0F

Response differential (fixed)

t

Hand full open

Holding workpiece Hand full open

Hand full open

Response differential (fixed)

)

)

Effective setting

range signal

(STABI)

The ON range of each output can be set within the effective measuring range (sensor head ON range).
Response differential is fixed (2% F.S).

When the controller setting and sensor heat setting positions are as shown below.
OUT1    Threshold value setting    Upper limit: 60    Lower limit: 40
Display when hand is full open: 

9

0

Display (%) 

OUT1

LCD display

CAUTION: When the effective measuring range signal is OFF (outside the measuring range), OUT also becomes OFF.

100

20

40

0F

t

Hand full open

Holding workpiece Hand full open

Hand full open

Effective setting

range signal

(STABI)

The ON position and OFF position each output can be set within the effective measuring range (sensor head ON range).

When the controller setting and sensor heat setting positions are as shown below.
OUT1    Threshold value setting    Upper limit: 40    Lower limit: 20
Display when hand is full open: 

9

0

First specify the cylinder model that is equipped (SET2), and then configure the other settings (as shown below).
You also can use the procedure below to modify settings.

General flow

Note 1:  Always be sure to configure the equipped cylinder model setting. Failure 

to do so creates the risk of malfunction.

2:  Note that initialization (SETA, SETB) initializes all settings, so any set-

tings you have configured are lost.

Note 2

Note 1

24 VDC

±

10%

D

Main circuit

Linear magnetic sensor controller

Sensor head

Power switch cable

Note: Note that extending the cable can cause a drop in voltage due to cable resistance.

1

2

3

4

5

0 V (blue lead)

LED (red lead)

B_IN (black lead)

A_IN (white lead)

+V (brown lead)

Main circuit

Tr

1

Tr

2

Tr

3

Tr

4

Tr

5

Z

D5

Z

D4

Z

D3

Z

D2

Z

D1

3

5

1

6

7

8

4

2

Load

Load

Load

Load

Load

STAB (black lead)

+Vcc (brown lead)

OUT1 (white lead)

OUT2 (red lead)

OUT3 (green lead)

OUT4 (yellow lead)

GND (blue lead)

Analog output (gray lead)

Signal D 

: Power supply reverse-polarity protection diode

 

Z

D1

 

 Z

D5

 

: Surge voltage absorption zener diode

 Tr

1

 

 Tr

5

 

: NPN output transistors