KAL-K
KAL-K K03/0516
Page 5
6. Mechanical
Connection
Prior to installation
Ensure that the actual system flow rate is within the switching range of the
KAL-K.
Ensure that the maximum system temperature and pressure are within the
limits specified per section. (see section 12. Technical Information)
Fitting
Mount the sensor into the piping and make sure that it is completely filled with
fluid. The probe tip has to reach at least 5 mm (better > 5 mm) into the pipe (see
below).
Fitting position
The sensor can be mounted in any orientation
as long as the piping is completely filled with
fluid. The mounting position has to be smooth
and free of turbulence.
(Recommended input and output length: 5 x
pipe diameter, of straight - run piping both
upstream and downstream of the flow switch).
In case of sediments in the pipe the shown
mounting position is recommended.
7. Electrical Connection and Operational Elements
Attention ! Ensure that the power is disconnected during the
connection of the cable.
Ensure that the voltage of your installation corresponds to the
voltage values given on the device's specification plate.
24 V
DC
-Version (terminal connector)
Remove electronic cover
(The fixing screws are secured against falling out)
Strip 3-wire cable (approx. 40-60 mm), strip single
wires (approx. 4-6 mm) and pull through cable
gland.
Sediments