![Kober C33GC24 Скачать руководство пользователя страница 25](http://html.mh-extra.com/html/kober/c33gc24/c33gc24_user-manual_1982062025.webp)
©
KÖBER SRL VADURI
BRANCH
24
GARAGE, ANNEX, ETC
LEGEND:
A – distance under the window/ ventilation hole
= 300mm
B - distance over the window/ ventilation hole =
300mm
C – distance left/ right to the window/ ventilation
hole = 300mm
D, E – distance from the roof/ gutter = 250mm
F – distance from the garage roof/ balcony = 250mm
G – distance to vertical gutter = 250mm
H – distance to internal/ external corners = 250mm
H* - distance to windows/ doors = 300mm
I – distance to ground/ balcony = 300mm
J – distance over the door = 600mm
L – distance to the door/ window in the garage =
1200mm
M – vertical distance to another terminal = 1500mm
N – horizontal distance to another terminal = 300mm
O – distance to the wall of another construction =
1200mm
A
B
H
H
N
G
C
A
D,E
D,E
D,E
H*
N
I
J
11.2
Minimum distances recommended for the mounting of the co-axial kit
EN
USER MANUAL C33GC24
M
H
L
F
O