USER MANUAL CENTRAL HEATING STATION TYPE C15SPV24MEFM / C17SPV31MEF

 

 

10 din 17

 

9.1.2.

 

Graphic context – station startup  

When started, the station is in an intermediary state for 5 seconds, necessary to initialise the system. During this interval the 
diplay shows only the message “

On

” on the S1 symbol on the interface (see figure 1.6). 

9.1.3.

 

Graphic context - Stand-by  

 This context is associated with an inactive/ waiting state of the central heating station. In the stand-by 
s t a t e   a l l   t h e   a c t i v a t i o n   e l e m e n t s   a r e   i n a c t i v e   a n d   e v e r y   b u r n i n g  
d e m a n d   i s   i g n o r e d . 
An exception to the rule: 

the  anti-freezing  function

  (generated by a value of water temperature 

in  the  installation  lower  than  9°C,  w h i c h   w i l l   i n i t i a t e   a   b u r n i n g   c y c l e   t o   p r e v e n t   t h e  
f r e e z i n g   o f   t h e   t h e r m a l   a g e n t   i n   t h e   i n s t a l l a t i o n . 
Intrarea si iesirea din acest regim se face prin apasarea tastei 

POWER

 cel putin o secunda. 

Actiuni posibile: 

POWER

  -  comutarea  intre  starea  ON/  Entering  and  exiting  this  regine  is  done  by  pressing 

POWER

  key  for  at  least  one 

second. 
Possible actions: 

POWER

 – comute between ON/OFF states; 

LIGHT

 – activation or deactivation of light functions. 

  Figure 1.7 is a good example of display in the stand-by state (pressure on the thermal installation 1,8 bar). 
 

9.1.4.

 

Graphic context – error state 

The  display  of  an  error  is  sometimes  asociated  with  a  state  of  malfunctioning/  error  of  the  station. 
There are three types of errors: 

Critical  errors:  all  the  activating/state  elements  of  the  central  heating  station  are  inactive  and  any 

burning request is ignored. Getting out of this critical error state is done by pressing the RESET key; 

Normal  errors:  all  the  activating/state  elements  of  the  central  heating  station  are  active  and  any 

burning request is ignored.  Getting out of a normal error state is done by pressing the RESET key; 

Informative  errors:  all  the  activating/state  elements  of  the  central  heating  station  are  active  and  all  burning  requests  are 

accepted. Getting out of an informative state is done automatically when the cause of error disappears.  
In this context the diplay flashes a message with the error code. 
Possible actions: 

RESET 

– reset critical or normal errors; 

LIGHT

 - activation or deactivation of light functions – possible only if the central heating station is not in a state of critical 

error. 
Figura 1.8 is a good example of display of an error (in our case E20). 

9.1.5.

 

Graphic context – waiting state 

Waiting state is associated with a functioning state of the station, but with no burning request. All the 
activating/state elements of the central heating station are active and all burning requests are accepted 
if no error is present. In this state, the display shows pressure and thermal temperature, as well as the 
functioning mode summer/ winter. 
Possible actions: 

POWER

 - comute between ON/OFF states; 

IN/SU

 – comute between summer/ winter functioning modes; 

LIGHT

 - activation or deactivation of light functions; 

CH+

 - display and setting of maximum thermal temperature; 

CH-

 - display and setting of minimum thermal temperature;  

DHW+

 - display and setting of maximum hot water temperature; 

DHW-

 - display and setting of minimum hot water temperature. 

Figura 1.9 is an example of display in the waiting state (pressure in the heating installation is 1,4 bar,  working mode is summer, 
and the temperature in the installation is 17°C). 

9.1.6.

 

Graphic context – functioning state 

This state is associated with  the presence of flame or  the functioning of  the circulation pump of  the station. In  this state, all  the 
activating/state elements of the central heating station are active and the burning request is accepted. The display shows the 
delivered instant temperature on the circuit meeting the request (heating ot hot water – symbols S5 or S6), regardless of the 
presence or lack of flame, the pressure inside the installation and the functioning mode summer/ winter. 
Possible actions: 

POWER

 - comute between ON/OFF states; 

IN/SU

 comute between summer/ winter functioning modes; 

LIGHT

 - activation or deactivation of light functions; 

CH+

 - display and setting of maximum thermal temperature; 

CH-

 - display and setting of minimum thermal temperature; 

DHW+

 - display and setting of maximum hot water temperature; 

DHW-

 - display and setting of minimum hot water temperature. 

Figures  1.10 and  1.11 are two examples of graphic display of this context.  Figure 1.10  – pressure in the heating installation is 
1,8  bar,  central  heating  station  is  in  winter  mode,  flame  is  present,  heating  demand  is  satisfied  and  the  instant  thermal 
temperature is  43°C;   
Figura  1.11  –  pressure  in  the  heating  installation  is  1,7  bar,  central  heating  station  is  set  on  winter 
mode, flame is present, station deliveres hot water, and the instant hot water temperature is 53°C. 

9.1.7.

 

Graphic context – adjustment of functioning parameters 

The adjustment of the main functions of the station (thermal temperature, hot water temperature) can be 
done both in the waiting state and in the functioning state  
When we enter the state display of these values, the last value previously set will be displayed. Only in the period the set value is 
displayed we can make changes of its value. Practically, at any moment of functioning of the station, by pressing 

J1

 (

CH+

) or 

J2

 

(

CH-

) keys, the set value of the thermal temperature will be displayed and can be changed. 

Fig.1.7

 

 

Fig.1.8

 

 

Fig.1.9

 

 

Fig.1.10

 

 

Fig.1.11

 

 

Fig.1.10

 

 

Содержание C15SPV24MEFM

Страница 1: ...DURI BRANCH USER MANUAL MURAL CENTRAL HEATING STATION C15SPV24MEFM C17SPV31MEF KÖBER SRL no 25 Vaduri Alexandru cel Bun Commune Neamt 617511 Romania Tel 40 233 24 17 46 233 24 19 33 Fax 40 233 24 19 29 www motan ro ...

Страница 2: ... instructions 9 9 1 Control Panel 9 9 1 Description of functions and of graphic contexts diplayed on the control panel LMC1112 9 9 1 1 LIGHT function 9 9 1 2 Graphic context station startup 10 9 1 3 Graphic context Stand by 10 9 1 4 Graphic context error state 10 9 1 5 Graphic context waiting state 10 9 1 6 Graphic context functioning state 10 9 1 7 Graphic context adjustment of functioning parame...

Страница 3: ... capacities including children or by people with no experience or and no knowledge The station provides both heating in closed circuit central heating installations as well as hot water Use for other purposes or for additional purposes other than stipulated is considered inappropriate use The manufacturer is not responsible for possible damage resulting from inappropriate use The user is the only ...

Страница 4: ...re on the thermal circuit 30 80 C 30 80 C Temperature on the house hot water circuit 30 55 C 30 55 C Hot water flow t 30 C 10 min 12l min Electric characteristics Input 230V 50 Hz 230V 50 Hz Nominal power EEI pump 0 2 80 W 80 W Construction characteristics Height mm 700 700 Width mm 436 436 Depth mm 303 331 Height with mounted corner 850 850 Weight 32 kg 34 5 Capacity primary heat switch 0 5 l 1 8...

Страница 5: ... maximum 60 humidity between 20 30 C in order to prevent the damaging of electronic components Caution The burning air of the station must not contain substances such as flourine vapours chlorine sulphur dissolvants colorants adhesives or gasoline These substances can lead in time to the corrosion of the equipment and air gas incoming outgoing pipes Legend A Racord tur termoficare B Racord iesire ...

Страница 6: ...ine ammonia alkaline agents halogenated hydrocarbs freon plaster particles lints dirt or dust Installation of the central heating station in the proximity of a swimming pool washing machine or cleaner can result in the contamination of the burning air with these compounds Water pH must be within the following limits 7 5 pH 9 5 It is recommended to check the water and thermal agent pH frequently an...

Страница 7: ... an impurity filter on the return of the thermal circuit installation When installing connecting pipes it is essential for these not to be tensed to avoid creating areas of leakage Maximum working pressure allowed is 3bar Recommended working pressure is 1 5 bar Caution It is forbidden to use the central heating station without thermal agent or partilally filled danger of explosion It is forbidden ...

Страница 8: ... must allow the entire electric insulataion of the central heating station for situations when interventions are required Grid connection is done taking into account the symbolism of colours as follows Brown phase Blue null Green and Yellow earthing The current plug must be accessible so that the user can easily disconnect it Caution It is not allowed to mount the central heating station with a de...

Страница 9: ... Used to switch the station on off J6 RESET Used to reset the electronic control board from an error state J7 Used to change the functioning mode winter summer J8 LIGHT Used to activate deactivate the light on the display Table 4 Description of graphic symbols in the LCD display Tasta Adnotare Descriere S1 It diplays the temperature C set value parameter values informative values various messages ...

Страница 10: ...s of the central heating station are active and all burning requests are accepted if no error is present In this state the display shows pressure and thermal temperature as well as the functioning mode summer winter Possible actions POWER comute between ON OFF states IN SU comute between summer winter functioning modes LIGHT activation or deactivation of light functions CH display and setting of m...

Страница 11: ...emperature is lower than the limit of 60 C When the station functions with high flows the hot water temperature will be the opposite of the hot water flow but lower than the set temperature With instant WHW configuration on request the CONFORT function can be activated deactivated Please contact an authorized service company This function allows the delivery of hot water as soon as possible while ...

Страница 12: ... Malfunction of flame detection Manually resettable by pressing RESET E25 YES BCU malfunction Manually resettable by pressing RESET E30 YES Malfunctioning burnt gases sensor Manually resettable by pressing RESET E31 NO Malfunctioning thermal input sensor Manually resettable by pressing RESET when the cause disappears E32 NO Malfunctioning thermal output sensor Manually resettable by pressing RESET...

Страница 13: ...e 2 by which the user signs that they are aware of the correct way of using the central heating station This statement is also signed by the authorized person who commissioned the central heating station The authorised person who commissions the station has the right to refuse to sign the station commissioning statement if they notice defects of the local connecting installations and will not sign...

Страница 14: ...nce over the window ventilation hole 300mm C distance left right to the window ventilation hole 300mm D E distance from the roof gutter 250mm F distance from the garage roof balcony 250mm G distance to vertical gutter 250mm H distance to internal external corners 250mm H distance to windows doors 300mm I distance to ground balcony 300mm J distance over the door 600m L distance to the door window i...

Страница 15: ...et to function in four modes 4 steps Table 6 Pump functioning modes functioning mode set in the factory UPM3 Flex As m LED 1 red LED 2 yellow LED 3 yellow LED 4 yellow LED 5 yellow 4 5 6 7 To set on another curve please contact the authorized service company NOTE To save on energy and to maintain the possible functioning noises to a low level please choose a low characteristic curve P Pump pressur...

Страница 16: ...put RT Central heating Input A Cold water input PC Boiler circulation pump CMC1X Boiler BCU ACM DHW domestic hot water V3C Three way valve SC Primary heating exchanger 10 4 2 Floor central heating and instant preparation of hot water This note is inform ative KÖBER Ltd don t assum es no responsibility for its proper functioning Legend TA Ambient thermostat SE Exterior temperature sensor TT Central...

Страница 17: ...g exchanger BOTTOM PLAN CMC1X SE SC PC V3C RT TT TA TB TS AR A RB ACM TI PC TS Thermostat TI Thermometer TB Water tank output RB Water tank input 10 4 4 Floor central heating and accumulated preparation of hot water accummulation boiler This note is inform ative KÖ BER Ltd don t assum es no responsibility for its proper functioning Legend TA Ambient thermostat SE Exterior temperature sensor TT Cen...

Отзывы: