-8-
7. Main label meanings
RANGE:
33kV
SERIAL No: 012356789
MODEL: KVD-01-33
DATE:
05/2019
System Voltage for this detector.
For traceability purpose.
Model relate to Threshold voltages
Date of Manufacture / Calibration
CLIMATIC CLASS: Normal. The detector will perform correctly
over the temperature range -25°C to +55°C and in 20% to 96%
humidity.
Outdoor. The detector is suitable for use either indoor or outdoor
and in wet conditions.
8. Preparation for use
Cleanliness
Dirt can cause surface tracking and it is therefore necessary to keep
the detector and its accessories clean by using a detergent solution.
The detector and other plastic accessories should then be polished
with the liquid polymer polish provided.
Mechanical damage
If surface scratches or dents can be easily seen by the naked eye
then the equipment should be returned to the manufacturer for repair
since these blemishes act as traps for dirt and moisture. Mechanical
damage to stud or bush screw threads would also necessitate the
return of the equipment to the manufacturer.
Battery check
Depress and release the TEST/ARMING button. The Green High
replace the battery with a new one.
HIGH VOLTAGE DETECTOR
IEC 61243-1
IEC 60068-2-6
IEC 60529
RANGE:
MODEL:
SERIAL No:
DATE:
CLIMATIC CATEGORY: N (NORMAL OUTDOOR)
INDICATION GROUP: III
FREQUENCY: 50/60Hz
www.grupotemper.com
-9-
9. Care and maintenance
Storage
The detector and its accessories should be stored in the proprietary
carrying case/bag when not in use. If the equipment is not going to
be used for an appreciable length of time (one month or more) then
it is a wise precaution to remove the battery. Remember to replace
the battery when the equipment is used again. It's advisable to
replace the battery with a new one.
Transporting
When the equipment is in transit it should be stored in its carrying
should not be subjected to excessive bumps and shocks.
10. Periodic maintenance
Battery Replacement
It is expected that the battery life will be many months of normal
use. It is recommended therefore that the battery be replaced
every six months whether or not it is found to be satisfactory when
testing/arming the detector.
The battery is located on the viewing facia of the detector. Its
turn left anti-clockwise, remove the battery compartment cover.
Slide out the battery and unclip the battery connector. Fit a new
battery type 9V. Insert the battery into its place, the battery cover
tightened (turn clockwise) to ensure a good water seal. There are
no other replaceable or serviceable parts.
Recalibration and Proof Testing
Every twelve months the detector and accessories should be
rechecked. This should include checking the threshold voltage
and voltage proof testing of all the accessories. It is recommended
that this rechecking be done by the manufacturer or its authorised
appointed representative.
www.grupotemper.com