KNX TH-UP Indoor Sensor • Date of issue: 13/01/2010 • Technical changes reserved. Errors reserved.
2
Description
The Indoor Sensor KNX TH-UP measures temperature and humidity and calculates the
dew point. The sensor can receive external measured values via the bus and process
them with the own data to an overall temperature and overall air humidity (mixed
values).
The KNX TH-UP provides seven switching outputs with adjustable threshold values as
well as additional AND and OR logic gates. The sensor has got a PI controller for
heating and cooling (depending on temperature) and for ventilation (depending on air
humidity) and it can emit a warning to the bus as soon as the area of optimum comfort
(according to DIN 1946) is left.
The integrated display shows the own values and data received from the bus (e. g. date,
time). The housing is completed with a frame of the switching series installed in the
building and thus merges with the interior.
Functions:
•
Measurement of
temperature and air humidity
(relative, absolute), calculation
of dew point
•
Display
1-3 rows (own values or values received from the bus)
•
Mixed values
from own measured values and external values (proportions can
be set in percentage)
•
PI controller for heating
(one or two step) and cooling (one or two step)
depending on temperature
•
PI controller for ventilation
depending on humidity: Dehumidify/humidify (one
step) or dehumidify (one or two step)
•
7 switching outputs
with adjustable threshold values (Threshold values can be
set by parameter or via communication objects)
•
4 AND and 4 OR logic gates
with each 4 inputs. Every switching incident as
well as 8 logic inputs (in the form of communication objects) may be used as
inputs for the logic gates. The output of each gate may optionally be configured as
1 bit or 2 x 8 bits
Configuration is made using the KNX software ETS. The
programme file
(format VD2)
and the
manual
can be downloaded from the Elsner Elektronik homepage on
www.elsner-elektronik.de
in the “Service” menu.
Scope of delivery
•
Housing with display and sensor board
•
Base plate
You will need in addition (not supplied):
•
Socket
∅
60 mm, 42 mm deep
•
Frame (for element 55 x 55 mm), suitable for the switching programme used in the
building