3.6.2
Binary - Push button
Parameter name
Values
Long press time
1 ...
10
... 50 (x 0.1 s)
Short press action
None
Send binary values
Dimmer control
Shutter control
Scene control
Long press action
Same options as for Short press action
Enable locking object
[Checkbox]
Binary inputs in push button mode can trigger different actions for “short press” and “long press”
operations. The
Long press time
parameter defines the minimum press time to differentiate
between short and long presses.
The specific actions to be triggered are configured with the
Short press action
and
Long press
action
parameters. Additional options for each type of action are described next.
The
Enable locking object
checkbox enables an additional communication object that can be
used to lock operation of this input. While the input is locked, short and long presses are ignored,
and no actions are triggered.
Send binary values
Parameter name
Values
Send value
Send 0
/ Send 1 / Toggle
If the “Send binary values” action is selected, a binary value will be sent to the bus when the
action is triggered. The
Send value
parameter determines the value to send: This can be 0, 1, or
“Toggle” (alternates between 0 and 1).
3.6
Inputs