43
Parameter setting
Sensor KNX AQS/TH-UP Touch
• Version: 23.10.2018 • Technical changes and errors excepted.
A set offset will be retained until a new value or a change is transferred. The current
value is saved, so that it is retained in the event of a power supply failure and will be
available once the power supply is restored.
Switching output
The output switching delay can be set using objects or directly as a parameter.
Blocking
The switching output can be blocked using an object. Define specifications here for the
behaviour of the output when blocked.
Start offset in °C
valid until first communication
0...20; 3
Increment for offset change via communi-
cation object
0,1°C • 0,2°C • 0,3°C • 0,4°C • 0,5°C • 1°C •
2°C • 3°C • 4°C • 5°C
Hysteresis of the threshold value in %
(for setting in %)
0 ... 50; 20
Threshold value sends
• never
• periodically
• on change
• on change and periodically
At and above change of
(if sent on change)
0.1°C • 0.2°C • 0.5°C • 1.0°C • 2.0°C • 5.0°C
Send cycle
(if sent periodically)
5 s • 10 s • 30 s • 1 min • … • 2 h
When the following conditions apply,
the output is
(TV = Threshold value)
• TV above = 1 | TV - hyst. below = 0
• TV above = 0 | TV - hyst. below = 1
• TV below = 1 |TV + hyst. above = 0
• TV below = 0 |TV + hyst. above = 1
Delays can be set via objects
(in seconds)
No • Yes
Switching delay from 0 to 1
for setting via objects:
valid until 1st communication
None • 1 s • 2 s • 5 s • 10 s • … • 2 h
Switching delay from 1 to 0
for setting via objects:
valid until 1st communication
None • 1 s • 2 s • 5 s • 10 s • … • 2 h
Switching output sends
• on change
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically
Send cycle
(is only sent if periodically is selected)