17
Transfer protocol
Sensor KNX AQS/TH-UP Touch
• Version: 23.10.2018 • Technical changes and errors excepted.
100 Total CO2 reading
Output
R-CT
[9.8]
DPT_Value_AirQua-
lity
2 Bytes
101 CO2 maximum value request
Input
-WC-
[1.17]
DPT_Trigger
1 Bit
102 Maximum CO2 reading
Output
R-CT
[9.8]
DPT_Value_AirQua-
lity
2 Bytes
103 Reset CO2 maximum value
Input
-WC-
[1.17]
DPT_Trigger
1 Bit
104 CO2 threshold value 1: Absolute
value
Input/
Output
RWC
T
[9.8]
DPT_Value_AirQua-
lity
2 Bytes
105 CO2 threshold value 1: (1:+ | 0:-)
Input
-WC-
[1.2]
DPT_Bool
1 Bit
106 CO2 threshold value 1: Switching
delay from 0 to 1
Input
-WC-
[9.010]
DPT_Value_Time
2 Bytes
107 CO2 threshold value 1: Switching
delay from 1 to 0
Input
-WC-
[9.010]
DPT_Value_Time
2 Bytes
108 CO2 threshold value 1: Switching
output
Output
R-CT
[1.1]
DPT_Switch
1 Bit
109 CO2 threshold value 1: Switching
output block
Input
-WC-
[1.2]
DPT_Bool
1 Bit
110 CO2 threshold value 2: Absolute
value
Input/
Output
RWC
T
[9.8]
DPT_Value_AirQua-
lity
2 Bytes
111 CO2 threshold value 2: (1:+ | 0:-)
Input
-WC-
[1.2]
DPT_Bool
1 Bit
112 CO2 threshold value 2: Switching
delay from 0 to 1
Input
-WC-
[9.010]
DPT_Value_Time
2 Bytes
113 CO2 threshold value 2: Switching
delay from 1 to 0
Input
-WC-
[9.010]
DPT_Value_Time
2 Bytes
114 CO2 threshold value 2: Switching
output
Output
R-CT
[1.1]
DPT_Switch
1 Bit
115 CO2 threshold value 2: Switching
output block
Input
-WC-
[1.2]
DPT_Bool
1 Bit
116 CO2 threshold value 3: Absolute
value
Input/
Output
RWC
T
[9.8]
DPT_Value_AirQua-
lity
2 Bytes
117 CO2 threshold value 3: (1:+ | 0:-)
Input
-WC-
[1.2]
DPT_Bool
1 Bit
118 CO2 threshold value 3: Switching
delay from 0 to 1
Input
-WC-
[9.010]
DPT_Value_Time
2 Bytes
119 CO2 threshold value 3: Switching
delay from 1 to 0
Input
-WC-
[9.010]
DPT_Value_Time
2 Bytes
No Name
Function Flags Data Point Type
Size