5.
Installation and commissioning
5.1 Preparation for installation
Before you can install the CoolAdd, you have to check several of points.
These checks are for safety reasons and to ensure the correct function
of the CoolAdd. Take great care when performing these checks
to ensure that the device functions correctly.
-
Check unit for transport damage.
The packaging for the CoolAdd must not show signs of transport
damage on delivery. Any damage on the packaging is indicative of possible
transport damage. In the worst case this damage may result in the loss of
function.
-
Returning the device in case of transport damage.
If the unit is not returned in the original packaging, the packaging used for return
must comply with the following criteria:
There must be a space of at least 30 mm between the unit and the packaging.
As an installation aid, there is a checklist in the appendix, that you should complete
prior to commissioning.
The commissioning also can be carried out by approved staff. Use the
commissioning certificate included in the appendix for this purpose.
Before the installation of the CoolAdd the stability under load
must be
of the existing cabinet has to be ensured. An additional weight of 41kg
must be taken in to account when installing the CoolAdd to the rear of
the cabinet. Please note the change of the centre of gravity when
opening the door. There must be enough space for maintenance when
the door is opened.
To achieve good air circulation, ensure that there is no packaging
material or other equipment that could hinder or prevent the circulation
of air:
•
in the area of the heat exchanger
•
on the air inlet
•
on the air outlet