TESTING FOR EMERGENCY LUMINAIRES

Recommended routine test procedure in accordance with BS5266
• 

Daily check

 – check LED charge indicator is illuminated

•  

Monthly functional test 

– simulate a mains supply failure for approx. 30 seconds by operation of key 

switch or switching off circuit breaker. Ensure normal supply is restored after test and ensure charge 
indicator is illuminated

•  

Annual three hour duration test

 - simulate a mains supply failure for a three hour continuous test 

by operation of key switch or switching off circuit breaker. Ensure normal supply is restored after test and 
ensure charge indicator is illuminated

•  If the luminaire fails any of the above tests, please contact a qualified electrician 

Please note: the Switched Live should not be re-energised during the emergency test