3
Troubleshooting
Service Manual
42
Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
FAULT
DESCRIPTION
CORRECTIVE ACTION
Outlet Sensor
Fault
(will require a manual
reset once the condition
has been corrected. Press
the RESET button on the
SMART SYSTEM
display
to reset.)
The control reads the outlet sensor as open
or shorted.
• Check wiring to sensor. Make sure wiring is
connected and not damaged. Reconnect / repair
wiring if necessary.
• Measure the resistance of the sensor and compare
to the resistance in Table 3-2C on page 35 of this
manual. Replace sensor if necessary.
• Replace control module.
Outdoor Sensor
Fault
(Models WH 55 - 285:
will be displayed until
condition has been
corrected.)
The control reads the outdoor sensor as
open or shorted.
• Check wiring to sensor. Make sure wiring is
connected and not damaged. Reconnect / repair
wiring if necessary.
• Measure the resistance of the sensor and compare
to the resistance in Table 3-2B on page 35 of this
manual.
• Replace sensor if necessary.
Outlet Temp Diff
(will require a manual
reset once the condition
has been corrected. Press
the RESET button on the
SMART SYSTEM
display
to reset.)
The control module reads an excessive
temperature difference between the two
sensors.
• Check wiring to sensor. Make sure wiring is connected
and not damaged. Reconnect / repair wiring if
necessary.
• Measure the resistance of the sensor and compare to
the resistance in Table 3-2C on page 35 of this
manual. Replace sensor if necessary.
• Restore control parameter defaults from optional PC
software.
• Replace control module.
Flue Sensor
Fault
(will require a manual
reset once the condition
has been corrected. Press
the RESET button on the
SMART SYSTEM
display
to reset.)
The control reads the flue sensor as open or
shorted.
• Check wiring to sensor. Make sure wiring is
connected and not damaged. Reconnect / repair
wiring if necessary.
• Measure the resistance of the sensor and compare
to the resistance in Table 3-2D on page 35 of this
manual. Replace sensor if necessary.
• Replace control module.
Flue Temp Diff
(will require a manual
reset once the condition
has been corrected. Press
the RESET button on the
SMART SYSTEM
display
to reset.)
The control module reads an excessive
temperature difference between the two
sensors.
• Check wiring to sensor. Make sure wiring is connected
and not damaged. Reconnect / repair wiring if
necessary.
• Measure the resistance of the sensor and compare to
the resistance in Table 3-2D on page 35 of this
manual. Replace sensor if necessary.
• Restore control parameter defaults from optional PC
software.
• Replace control module.