background image

1  

Service

20

SH1 - SH3 Differential Set Point

The 

SH Differential

 sets how many degrees below the offset 

the temperature has to drop before the boiler turns back 
on.  This parameter can only be changed by the installer by 
accessing the 

SH1, 2 and 3 Differential Set Point 

parameters.  

The range is 0°F to 60°F.  The default is 20°F.

3-Way Valve Time

The optional Lochinvar Multi-Temperature Loop Control 
Board (MTLCB) can be used to control the supply temperature 
of up to three (3) sub-loops, corresponding to each of the 
three (3) SH set points, through the use of 3-way mixing 
valves.  To ensure the MTLCB will control these temperature 
properly, it is necessary to let the control know how much 
time these mixing valves require to move from the fully open 
to fully closed positions.  Program this time into the 

3-Way 

Valve Time

 parameter.  Since this parameter applies to all of 

the mixing valves used, the actual open/close time must be 
approximately the same for each one.  The minimum setting 
is 1 second, and the maximum setting is 255 seconds.  The 
default setting is 20 seconds. 

Data Logging

Reset log errors

The reset log errors function clears the last 10 errors log. 

Functions

Service Mode Delay

By pressing the pin button on the front of the display for 
five (5) seconds, the control will be placed in Service Mode.  
This will override all other heat demands.  The Service Mode 
allows the installer to set the unit to any firing rate for the 
purpose of combustion analysis.  The delay sets the length of 
time the boiler will stay in the Service Mode if no keys have 
been pressed before going back to its original state.  This 
parameter can only be changed by the installer by accessing 
the 

Service Mode Delay 

parameter.  The time range of this 

parameter is 1 to 10 minutes.  The default value is 10 minutes.

Freeze Protection Pump On

The SMART SYSTEM control will turn on the boiler and 
system pump outputs whenever the inlet temperature drops 
below this setting.  This is done to prevent the water in the 
heat exchanger from freezing.  Certain low-temperature 
applications (such as snow melt) can operate at temperatures 
around freezing, so this setting needs to be lowered in these 
cases.  The installer can adjust the temperature at which the 
pump outputs are turned on by accessing 

Freeze Protection 

Pump On 

parameter.  The minimum setting is -3°F (-19°C), 

and the maximum setting is 45°F (7.2°C).  The default setting 
is 45°F (7.2°C).

To save any changes and return to the Home Screen, press the 
RIGHT SELECT [HOME] key.  To return to the Status Screen 
without saving the changes, press the LEFT SELECT [EXIT] 
key.

Display Timeout

This is the time in which the display remains illuminated.  The 
range is 10 seconds to 10 minutes.  The default is 3 minutes.

Temperature Settings

Space heating (SH) set point parameters limit boiler operating 
set point.  The exact boiler operating set point is calculated 
using the outdoor reset curve.  Outdoor reset is a feature that 
increases the temperature setting of the boiler as outdoor 
temperatures drop and decreases boiler set point as outdoor 
temperatures rise.  The outdoor reset parameters can be 
accessed through the 

Outdoor Reset

 menu.

Space Heating (SH1, SH2, SH3) Set Point 

There are three (3) individual space heating set points.  These 
are listed as 

SH1 Set Point

 through 

SH3 Set Point

.  These set 

points provide an upper limit to the outdoor reset curve for 
each zone.  If multiple space heating set points are calling for 
heat, the highest set point has priority.  If the outdoor sensor is 
not functioning, the boiler will operate at 

SH Set Point

 and the 

display screen will indicate “Outdoor Sensor Fault”.  The range 
of this parameter is 

SH Minimum Set Point

 to 

SH Maximum Set 

Point

.  The default is 125°F (52°C).

Space Heating (SH) Minimum Set Point

The 

SH Minimum Set Point

 sets the minimum water temperature 

set point allowed for 

SH Set Point (1 - 3)

 adjustment.  The user 

or installer will not be able to program the control with a lower 
SH set point.  This parameter can only be changed by the 
installer by accessing the 

Minimum SH Set Point 

parameter. 

The temperature range is 32°F (0°C) to the space heating 
maximum set point.  The default value is 32°F.

Space Heating (SH) Maximum Set Point

The 

SH Maximum Set Point

 sets the maximum water 

temperature set point that can be used for space heating.  The 
user or installer will not be able to program the control with a 
higher SH set point.  This parameter can only be changed by 
the installer by accessing the 

Maximum SH Set Point 

parameter.  

The temperature range of this parameter is the space heating 
minimum set point to 180°F (82°C).  The default value is 180°F.

SH1 - SH3 Offset Set Point

The SH offset sets how many degrees above set point the 
temperature has to go before the boiler will shut off.  This 
parameter can only be changed by the installer by accessing 

SH1, 2 and 3 Offset Set Point 

parameters.  The temperature 

range of these parameters is 0°F to 20°F.  The default value is 
10°F.

 

CAUTION

Mixing valves are required for the protection 
of any low temperature loops.

 NOTICE

Never put the Freeze Protection Pump 
on a setting lower than the Freeze 
Protection Burner On setting.

      Outdoor Knight Boiler 

Service Manual

Содержание 151

Страница 1: ...chnician Read all instructions including this manual and the Outdoor Knight Boiler Installation and Operation Manual before installing Perform steps in the order given Failure to comply could result in severe personal injury death or substantial property damage WARNING Save this manual for future reference OKB SER Rev A ...

Страница 2: ...but not related to personal injury or property damage CONTENTS 2 Hazard Definitions 2 PLEASE READ BEFORE PROCEEDING 3 Handling Ceramic Fiber Materials 3 When servicing boiler 4 Boiler operation 4 Boiler water 4 Freeze protection fluids 4 WHAT IS IN THIS MANUAL 5 1 SERVICE Near Boiler Piping 6 The Outdoor Boiler Display 7 Control Inputs 8 Control Outputs 9 General Operation 10 Sequence of Operation...

Страница 3: ...r IARC has concluded Crystalline silica in the form of quartz or cristobalite from occupational sources is carcinogenic to humans Group 1 Normal operating temperatures in this appliance are below the level to convert ceramic fibers to cristobalite Abnormal operating conditions would have to be created to convert the ceramic fibers in this appliance to cristobalite The ceramic fiber material used i...

Страница 4: ...nected to remove sediment The high efficiency heat exchanger can be damaged by build up or corrosion due to sediment Do not use petroleum based cleaning or sealing compounds in the boiler system Gaskets and seals in the system may be damaged This can result in substantial property damage Do not use homemade cures or boiler patent medicines Serious damage to the boiler personnel and or property may...

Страница 5: ...eration General Temperature Setting Data Logging Functions DHW Settings Outdoor Reset Anti cycling Control Modes Circulation Pumps Building Management System BMS Service Notification Maintenance Service and maintenance schedules Address reported problems Inspect boiler area and boiler interior Clean condensate trap Check all piping for leaks Check air openings Flue vent system and air piping Check...

Страница 6: ...M SYSTEM FROM TO IMG00377 Near boiler piping This piping reference is included to specify the Near Boiler Piping specific to the outdoor boiler This piping scheme is important for proper operation of the SMART SYSTEM control See the Outdoor Knight Boiler Installation and Operation Manual for more detailed piping diagrams Outdoor Knight Boiler Service Manual ...

Страница 7: ...ht boiler display The information on the bottom of the display shows the functions of the two SELECT keys on either corner and the NAVIGATION dial in the center MENU Left SELECT Key SETPOINTS NAVIGATION Dial Pressing Down SHDN Right SELECT Key Outdoor Knight Boiler Service Manual ...

Страница 8: ...GMENT SYSTEM LOW VOLTAGE CONNECTION BOARD INLET TEMPERATURE SENSOR OUTLET TEMPERATURE HI LIMIT SENSOR FLUE GAS SENSOR FLAME SENSOR LOW WATER CUTOFF BLOCKED DRAIN SWITCH DISPLAY PANEL PC INTERFACE SMART CONTROL MODULE AIR PRESSURE SWITCH SYSTEM PUMP SPEED CONTROL O TEMP HEAT EXCHANGER SWITCH IMG00006 Control inputs Outdoor Knight Boiler Service Manual ...

Страница 9: ...OLTAGE CONNECTION BOARD SMART CONTROL MODULE ALARM BELL RUN TIME CONTACTS BUILDING MANAGEMENT SYSTEM BOILER PUMP SYSTEM PUMP DHW PUMP IGNITOR BLOWER GAS VALVE DISPLAY PANEL PC INTERFACE Control outputs Outdoor Knight Boiler Service Manual ...

Страница 10: ... temperature or system supply temperature depending on the parameter setting Sequence of operation Table 1 1 shows control module normal sequences of operation for space heating and DHW operation The combined operation sequence is for a typical application programmed to provide DHW priority Access modes User The user can adjust space heating and tank target temperatures by pressing the NAVIGATION ...

Страница 11: ...ng the blower 5 The control starts the trial for ignition by firing the spark electrode and opening the gas valve 6 If flame is not detected after the sparking ends the control will perform a postpurge then start another prepurge cycle and try to light the burner again The control will perform a total of 4 attempts before locking out 7 If flame is detected it holds the firing rate steady for a few...

Страница 12: ...the outlet temperature to the DHW boiler set point 9 If the boiler is not part of a Cascade and both the space heating and DHW calls for heat remain active long enough the boiler will switch back and forth between the two heating modes until one of them is satisfied 10 Once both calls for heat are satisfied the control will turn off the burner The blower will continue to run during the postpurge p...

Страница 13: ...MENU for five 5 seconds Rotate the NAVIGATION dial clockwise until 5 is displayed first digit on the left Press the NAVIGATION dial to select the next digit Rotate the NAVIGATION dial clockwise until 3 is shown in the display Press the NAVIGATION dial 2 times to move to the last digit Rotate the NAVIGATION dial counterclockwise until 9 is displayed SAVE Press the RIGHT SELECT soft key SAVE Rotate ...

Страница 14: ...NGS Press the NAVIGATION dial one time Rotate the NAVIGATION dial counterclockwise until the arrow is next to MIN SETPT Press the NAVIGATION dial one time Rotate the NAVIGATION dial to the desired temperature SAVE Press the RIGHT SELECT soft key SAVE one time EXIT Press the LEFT SELECT soft key EXIT if all desired changes have been made HOME Press the LEFT SELECT soft key HOME Table 1 3 This is a ...

Страница 15: ...Night Setback Off Times 19 No No Yes Yes Display Timeout 20 No No Yes Yes SH1 Set Point 20 Yes Yes No No Minimum SH Set Point 20 No No Yes Yes Maximum SH Set Point 20 No No Yes Yes SH1 Offset 20 No No Yes Yes SH1 Differential 20 No No Yes Yes SH2 Set Point 20 Yes Yes No No SH2 Offset 20 No No Yes Yes SH2 Differential 20 No No Yes Yes SH3 Set Point 20 Yes Yes No No SH3 Offset 20 No No Yes Yes SH3 D...

Страница 16: ... No Yes Yes Set Point 1 at Low Outdoor Temp 1 22 No No Yes Yes Set Point 1 at High Outdoor Temp 1 22 No No Yes Yes Outdoor Air Shutdown SH1 22 No No Yes Yes Outdoor Air Shutdown Differential SH1 23 No No Yes Yes Shift Reset Curve SH1 23 No No Yes Yes Outdoor 2 Low 22 No No Yes Yes Outdoor 2 High 22 No No Yes Yes Set Point 2 at Low Outdoor Temp 2 22 No No Yes Yes Set Point 2 at High Outdoor Temp 2 ...

Страница 17: ...us T O 25 No No Yes Yes Cascade Address 25 No No Yes Yes Cascade Type 25 No No Yes Yes Max Cascade Set Point 25 No No Yes Yes Cascade Offset 25 No No Yes Yes Cascade Differential 25 No No Yes Yes Min On Off Time 25 No No Yes Yes Min Next On Time 25 No No Yes Yes Boiler Size 25 No No Yes Yes System Pump Delay 25 No No Yes Yes Boiler Pump Delay 26 No No Yes Yes DHW Pump Delay 26 No No Yes Yes Boiler...

Страница 18: ...s Yes Rate at Min Volts 26 No No Yes Yes Rate at Max Volts 26 No No Yes Yes Set Point at Min Volts 27 No No Yes Yes Set Point at Max Volts 27 No No Yes Yes On Volts 27 No No Yes Yes Off Differential Volts 27 No No Yes Yes Service Notification Months 27 No No Yes Yes Service Notification Running Time 27 No No Yes Yes Service Notification Cycles 27 No No Yes Yes Reset Maintenance Reminder 27 No No Y...

Страница 19: ...f desired When a start trigger and a stop trigger are set to the same time the stop trigger has priority The installer may adjust the space heating night setback start triggers by accessing the SH Night Setback On Times parameter The DHW start triggers in the DHW Night Setback On Times parameter This screen shows the start trigger number the day of the week and the time of day 1 When the screen is...

Страница 20: ...HT SELECT HOME key To return to the Status Screen without saving the changes press the LEFT SELECT EXIT key Display Timeout This is the time in which the display remains illuminated The range is 10 seconds to 10 minutes The default is 3 minutes Temperature Settings Space heating SH set point parameters limit boiler operating set point The exact boiler operating set point is calculated using the ou...

Страница 21: ... heating demand and it receives a DHW demand it will immediately switch to the DHW demand and start a timer Once the timer has expired the boiler will switch back to the space heating demand and start another timer Once this timer expires it will switch back to the DHW demand The installer can adjust the length of time the boiler will service the space heating demand by accessing SH DHW Switching ...

Страница 22: ...t High Outdoor Temp 1 3 parameters FIG 1 1 This parameter can be changed by the installer by accessing the Outdoor 1 3 High parameters The temperature range is low outdoor air temperature set point to 104 F 40 C The default value is 70 F 21 C Set Point 1 3 at Low Outdoor Temperature When the outdoor air temperature drops to the Outdoor 1 3 Low parameter the set point will be at this setting FIG 1 ...

Страница 23: ... SH1 SH3 The outdoor air shutdown differential parameter is the number of degrees below Outdoor Air Shutdown SH1 SH2 and SH3 parameters the outdoor air temperature must go before the boiler will respond to a SH demand These parameters can be changed by the installer by accessing the Outdoor Air Shutdown Differential SH1 SH2 and SH3 parameters The temperature range of this parameter is 0 F 0 C to 5...

Страница 24: ... rate of the next to last boiler to 40 thus eliminating the sudden drop in total output of the Cascade When finished the installer can press the RIGHT SELECT SAVE key to store the new settings or the LEFT SELECT EXIT key to return to the Anti Cycling parameter list without saving the changes The delay value can be set between 0 minutes and 20 minutes The limit value can be set between 0 and 100 Co...

Страница 25: ... temperature must go below the turn off temperature Set point Offset before the lead boiler turns on This parameter can be adjusted by the installer by accessing the Cascade Differential parameter The temperature range of this parameter is 0 F to 60 F 33 C The default value is 20 F 11 C Minimum On Off Time In order to prevent units in a Cascade from short cycling this parameter defines the minimum...

Страница 26: ...mum Volts parameter The minimum value is the Rate at Minimum Volts setting and the maximum is 100 The default value is 100 Boiler Pump Delay The SH pump delay parameter sets the length of time the boiler pump will run after a SH demand has been satisfied Setting the delay time to 0 will disable the pump This parameter is adjustable by the installer by accessing the Boiler Pump Delay parameter The ...

Страница 27: ...e Notification Running Time parameter The time range for this parameter is 0 hours to 17 500 hours The default time is 8 760 hours Service Notification Cycles When the boiler control determines that a scheduled service is due based on the number of boiler cycles the boiler display will alternate the standard boiler display text with the message SERVICE DUE every 5 seconds This parameter is adjusta...

Страница 28: ...on Manual Flame inspection stable uniform Flame signal at least 10 microamps at high fire Clean the heat exchanger if flue temperature is more than 54 F above return water temperature If combustion or performance indicate need Clean heat exchanger Remove and clean burner using compressed air only Clean the blower wheel ANNUAL START UP Owner maintenance see the Outdoor Knight User s Information Man...

Страница 29: ...e removed Inspect boiler interior 1 Remove the front access cover and inspect the interior of the boiler 2 Vacuum any sediment from inside the boiler and components Remove any obstructions Clean condensate trap 1 Inspect the condensate drain line condensate PVC fittings and condensate trap 2 Remove the PVC cap retaining screw from the PVC cap FIG 2 1 3 Remove the 2 inch PVC cap with the switch loc...

Страница 30: ...ler Installation and Operation Manual before proceeding further Safety relief valves should be re inspected AT LEAST ONCE EVERY THREE YEARS by a licensed plumbing contractor or authorized inspection agency to ensure that the product has not been affected by corrosive water conditions and to ensure that the valve and discharge line have not been altered or tampered with illegally Certain naturally ...

Страница 31: ...just if necessary Perform start up and checks 1 Start boiler and perform checks and tests specified in Section 7 Start up of the Outdoor Knight Boiler Installation and Operation Manual 2 Verify cold fill pressure is correct and that operating pressure does not go too high Check burner flame 1 Inspect flame through observation window 2 If the flame is unsatisfactory at either high fire or low fire ...

Страница 32: ...n severe personal injury WARNING 9 Allow the heat exchanger to thoroughly dry 10 Remove the field supplied rear refractory cover from the back of the combustion chamber of the heat exchanger and reassemble 11 Close isolation valves on piping to isolate boiler from system Attach a hose to the boiler drain and flush boiler thoroughly with clean water by using purging valves to allow water to flow th...

Страница 33: ...ches w c natural 8 inches w c LP with gas flowing verify during boiler startup Check control module fuses ALWAYS check control module fuses before replacing control module or any major components blower etc If one of these fuses is blown it can prevent the control module or other components from operating 1 Turn OFF the power to the boiler at the external line switch 2 Remove top access cover 3 Re...

Страница 34: ...Outside air temperature above Warm Weather Shutdown WWSD set point for main control board Check location of outside air sensor Check resistance of outdoor air sensor and compare to Table 3 2B on page 35 of this manual Unit locked out on fault Consult display for specific fault Refer to fault descriptions on page 37 of this manual for corrective actions Unit in Shutdown Mode Take unit out of Shutdo...

Страница 35: ...the flue and outlet water sensors have two temperature sensing devices in one housing These devices are designated as S1a S1b outlet sensor and S3a S3b flue sensor Please reference the wiring diagram in the Outdoor Knight Boiler Installation and Operation Manual for correct terminal location S1a Wire Color R BK and Y S1b Wire Color G and Y Temperature Resistance Temperature Resistance Temperature ...

Страница 36: ...ng of the Outdoor Knight Boiler Installation and Operation Manual for minimum flow rates Verify that the boiler is piped in a primary secondary fashion and that the boiler and system pump are running on a call for heat Air in the piping system Properly purge all air from the piping system Low system water pressure Verify system pressure is a minimum of 12 psi No Pump Operation Boiler Pump System P...

Страница 37: ...ow Voltage Connection Board Check for the addition of a device wired across the gas pressure switch terminals on the Low Voltage Connection Board Flow Switch LWCO will require a manual reset once condition has been corrected Press the RESET button on the SMART SYSTEM display to reset Either the optional flow switch or the optional low water cutoff is not making Check boiler pump operation on a cal...

Страница 38: ...nger if refractory is broken and unit has fired Check continuity across two contacts Wires should be connected at both poles of the normally closed switch Faulty O Temp HEX Switch Replace switch Anti cycling The main control board has received a call for heat too quickly after the previous call for heat has ended The control board will release the call for heat after a set time period The control ...

Страница 39: ...ensure the valve is flowing gas With a manometer connected to the outlet tap of the gas valve when the unit is in the prepurge period there should be a negative pressure present When the valve is energized a change in pressure should occur If the pressure change does not occur the gas valve is not opening Replace the gas valve Inspect flame sensor and associated wiring Reference page 31 of this ma...

Страница 40: ...pump ensure that the system flow is not less than the boiler flow If operating on something other than an outlet sensor check temperature setting of the main control board If the optional manual reset high limit has tripped check setting of the device Check resistance of water sensors and compare to Table 3 2A on page 35 of this manual Replace sensor if necessary Replace high limit Outlet MRHL wil...

Страница 41: ...pare to Table 3 2A on page 35 of this manual Replace sensor if necessary Replace high limit Fan Low High OR Fan Speed Low High will require a manual reset once the condition has been corrected Press the RESET button on the SMART SYSTEM display to reset The actual fan RPM is 30 lower than what is being called for Check for obstruction or blockage in the vent air intake pipes or at terminations Chec...

Страница 42: ... this manual Replace sensor if necessary Replace control module Outlet Sensor Fault will require a manual reset once the condition has been corrected Press the RESET button on the SMART SYSTEM display to reset The control reads the inlet sensor as open or shorted Check wiring to sensor Make sure wiring is connected and not damaged Reconnect repair wiring if necessary Measure the resistance of the ...

Страница 43: ...necessary Measure the resistance of the sensor and compare to the resistance in Table 3 2D on page 35 of this manual Replace sensor if necessary Restore control parameter defaults from optional PC software Replace control module Flue Temp Limit will require a manual reset once the condition has been corrected Press the RESET button on the SMART SYSTEM display to reset The stack temperature has exc...

Страница 44: ...per piping methods for the outdoor boiler Check for 120 vac to the boiler pump motor on a call for heat If voltage is not present check the wiring back to the main control board Replace the main control board if necessary If 120 vac is present on a call for heat and the boiler pump is not operating replace the pump Verify that the boiler pump is set to the proper speed or that the pump is the prop...

Страница 45: ...ain control board must be reset Press the ENTER RESET button on the SMART SYSTEM display panel Service Blk While the unit is in Service Mode the outlet temperature has exceeded 185 F Establish a heating load to remove the heat from the boiler loop Verify that the system is full of water and that all air has been properly purged from the system Verify that the boiler is piped properly into the heat...

Страница 46: ...Natural Gas Propane CO2 O2 CO2 O2 8 0 10 3 0 6 5 9 0 11 4 1 6 9 7 Once the combustion analysis is complete test the safety shutoff device by turning the manual shutoff switch to the OFF position and ensuring that the boiler shuts down and registers an alarm Turn the manual shutoff switch to the ON position reset the control and return to Service Mode 8 Turn the main power off to the boiler 9 Place...

Страница 47: ...t procedure If adjustment of the gas valve is deemed necessary use the following procedure Locate the throttle adjustment screw on the side of the venturi valve FIG 3 2 Using a screwdriver turn the screw a 1 4 turn counterclockwise to increase CO2 levels or a 1 4 turn clockwise to decrease CO2 levels After performing one adjustment on the valve follow the Combustion Analysis Procedure on page 46 o...

Страница 48: ...Revision Notes Revision A ECO C11234 initial release OKB SER Rev A 10 12 ...

Отзывы: